H B X Z O N - 0 6 0 0 Z o n e C o n t r o l
V e r s i o n 1 . 0 . 0
Page 4
7. HUMIDITY OUTPUT
This output is used for a humidity demand. This can
be used to humidify or dehumidify.
8. THERMOSTAT INPUT 1 - 4
These terminals are used for power and
communication for thermostat inputs. Only THM-0600
thermostats are compatible with this control.
WIRING
We recommend all signal wiring to be a minimum of 18AWG shielded wire at a maximum of 500ft.
2. ZONE 1 - 4 OUTPUT
These are the outputs for the zone device. This can be a
pump or a valve depending on what power is supplied
to terminals 5-6. These outputs can also be used for
Damper Zones (terminals 1 & 3) or a 4 pipe system.
1. DEMAND OUTPUTS
These are the outputs for the demands. These can be
a Heating, Cooling, Auxiliary, and App demand, 24VAC
contact, dry contact TT/Low Temperature demand for
a boiler, or DHW/High Temperature demand.
5. ZONE POWER
This input is used to power the zone outputs and is
rated for 240VAC, 120VAC or 24VAC.
6. FANCOIL OUTPUT
These are the outputs for the Fancoil demands. These
can be a Fan Demand or an HRV Demand.
DO NOT CONNECT
POWER HERE
GR
POWER
120
17
N
L
16
15
0
4
3
I
TT1
0
6
5
I
TT2
5
TH1
10
9
6
5
12
11
6
5
14
13
6
5
16
15
6
2
Y
G
20
19
2
X
21
2
5A
1
PUMP 1
1 2
1
1
PUMP 2
3 4
1
5A
HBX
ZON-0600
Zone Control
N
ZN 1
7 8
H
N
9 10
H
ZN 2
N
11 12
H
ZN 3
N
13 14
H
ZN 4
N
5 6
H
ZONE
POWER
5A
5A
5A
5A
1
2
1
1
W R
Fancoil
Outputs
0
8
7
I
TT3
Demand
Outputs
1
18
17
1
Thermostat
Signal
Communication
Fancoil
Outputs
EXT
THM
TH2
TH3
TH4
Aux. Therm
Input
Humidity Output
Fan Control Output
Fancoil Cooling Output
External Thermistor Input
Zone 4 Thermostat
Zone 3 Thermostat
Zone 2 Thermostat
Zone 1 Thermostat
Fancoil Heating Output
Fancoil Input
TT1 Demand Output
TT2 Demand Output
TT3 Demand Output
1
6
8
6
9
7
Control Input Power
Zone 4 Output
Zone 3 Output
Zone 2 Output
Zone 1 Output
Pump 1 Output
Pump 2 Output
Zone Power Input
5
3
4
2
WIRING AND INSTALLATION
3. PUMP OUTPUTS
These are dry contact outputs that can be used
to control a pump for the following: System pump,
Heating pump, Colding pump, Auxiliary pump (DHW),
App demand pump, Fancoil Heat/Cool pump, Fancoil
heat, Fancoil cool
4. INPUT POWER
This input is to power the ZON-0600. 0.5 Amps at 120
VAC is required to power this device.
9. AUXILIARY INPUT
This terminal is an input for an external thermistor
to monitor any temperature or read outdoor
temperature, or run a heating setpoint.