Hayward Aqua Plus 16v Operation Manual Download Page 8

5

VSP Relay

:  This selection is used to configure a Lights/Aux output to supply power and control a Hayward

Variable Speed pump (VSP).

Pool/Spa Valves

Pool-only or Spa-only systems:

  The POOL/SPA/SPILLOVER button has no function.

Standard Pool and Spa systems without spa spillover:

  In pool-only mode (“POOL” LED illuminated), press

the “POOL/SPA/SPILLOVER” button to switch to spa-only operation (“SPA” LED illuminated).  Pressing the

“POOL/SPA/SPILLOVER” button again will switch back to pool-only.  Note that the filter pump will turn off

while the pool/spa valves are turning.

Standard Pool and Spa systems with spa spillover:

  When currently in the pool-only mode (“POOL” LED

illuminated), press the “POOL/SPA/SPILLOVER” button to switch to spa-only operation (“SPA” LED illumi-

nated).  Press the button again to switch to spa spillover operation (“SPILLOVER” LED illuminated).  Pressing the

“POOL/SPA/SPILLOVER” button again will switch back to pool-only mode. Note that the filter pump will turn

off while the pool/spa valves are turning.

Dual Equipment Pool and Spa systems without spa spillover

:  The POOL/SPA/SPILLOVER button has no

function.  The “POOL” LED will always be illuminated.

Dual Equipment Pool and Spa systems with spa spillover

: When currently in the separate Pool and Spa loops

mode (“POOL” LED illuminated) and the Spa Filter is off, press the POOL/SPA/SPILLOVER button to switch

to spa spillover operation (“SPILLOVER” LED illuminated). Press the POOL/SPA/SPILLOVER button again to

return to the separate Pool and Spa loops mode of operation. Note that the Pool Filter pump will shut off while the

pool/spa return valve is turning.  The system will automatically switch out of spillover whenever the spa filter pump

is turned on. NOTE: For Dual Equipment Pool and Spa systems, there is no Spa Only mode.

Heaters

This description applies to Heater1 and to Heater2, if programmed (note that the function of the Valve4 button

changes to Heater2 when Heater2 is enabled). Pressing the “HEATER” button causes the Aqua Plus 16v to switch

the heater control output between a “forced off” state and a normal, automatic thermostatic control operating state.

System Off

Each remote display/keypad has a red “SYSTEM OFF” button on the upper left corner of the keypad. Pressing

this button will turn all outputs off and they will remain off, regardless of any programmed control logic, until either

the “SYSTEM OFF” button (on any remote display/keypad) is pressed again or the “SERVICE” button is pressed

on the display/keypad at the main unit. The red “SYSTEM OFF” LED will illuminate to indicate that all outputs and
being forced off.

!

WARNING: pressing the “SYSTEM OFF” button overrides any programmed freeze protection

and may cause damage to your system in freezing conditions.

Service

The main unit keypad has a “SERVICE”  key.  This button is used primarily during servicing of the pool equipment.

If you want to completely disable the automatic operation and operate the system manually, you can put the system

into Service or Service-Timed mode by pressing the “SERVICE” button.  Pressing the “SERVICE” button once

will switch the system into service mode which means that all automatic functions are disabled, and the remote

display/keypads are disabled (except for manual turn off for emergencies).  The red “SERVICE” LED will be

illuminated and the Aqua Plus 16v will remain in this mode of operation until manually taken out of service mode.

Pressing the “SERVICE” button again will cause the Aqua Plus 16v to switch to service-timed mode which is very

similar to service mode, except that the Aqua Plus 16v will automatically return to normal operation after 3 hours.

During service timed operation, the “SERVICE” LED will flash and the time remaining will be displayed on the

remote display keypad(s).

Pressing the “SERVICE” button again, will return the Aqua Plus 16v to normal (automatic) operation.  See Trouble-

shooting/Diagnostic Information for more information about the service modes.

42

pH Timeout - Check Feeder 

-- If the unit has been dispensing pH for more than the selected timeout without

reaching the desired level. Check the chemical supply and the feeder.  If both are OK, the timeout may need to

be increased.  Press the “+” button to reset the alarm and resume dispensing.

pH Calibration Error 

-- When using the pH Calibration Wizard and the entered test result was different from

the measured pH level by ± 1.0 or more.  The pH probe may need to be cleaned or replaced.

ORP Probe Error 

-- If the CSM indicates that there is a problem with the ORP probe.

ORP Low - Check Chlor 

-- If an ORP level of 350mV or less is detected. Check the chlorinator for proper

operation.

ORP High - Check Chlor 

-- If an ORP level of 950mV or higher is detected. Check the chlorinator for proper

operation.

ORP High -  Chlor Off 

-- If an ORP level of 950mV or higher is detected and the chlorine feed mode is ORP

Auto Sensing, the chlorinator has been turned off. Check the chlorinator for proper operation.

ORP Timeout -Chlor Off 

-- If the unit has been chlorinating for more than the selected sanitizer timeout

without reaching the desired level, the chlorinator has been turned off. Press the “+” button to reset the alarm

and resume chlorination.

Ambient Sensor-

- If the Aqua Plus 16v internal temperature sensor is either an open or short circuit.

For helpful troubleshooting information on any of these issues, go to the Diagnostic Menu and then scroll through

the various items until you see the cause for the “CHECK SYSTEM” LED being illuminated.

Diagnostic Menu

To enter the Diagnostic Menu, press the “Menu” button repeatedly until the display shows “Diagnostic Menu”.  At

this point, you can use either the “<” or “>” buttons to scroll through the various menu items which are described

below:

Set Day and Time

Wednesday 10:37P

Move to previous/next menu item

+23.45     +6.75A

84°F      3200PPM

Press to switch chlorinator operation to opposite polarity (15 second delay)

+/- 23.45V is the voltage applied to the chlorinator cell

+/-6.75A is the current (amps) through the cell

84ºF is the water temperature at the cell

3200PPM is the “instant” salt level at this time

This display will be shown only if the chlorinator is enabled.

 For the chlorinator to be operating,

several other things must be happening: the filter pump must be running, the flow switch must be

detecting flow, the chlorinator setting must be set greater than 0%, the water temperature at the cell

must be between 50ºF and 140ºF, and the salt level must be within the operating range.  If any of these

conditions are not met, the chlorinator diagnostic display will tell you the reason.  It’s possible to have

more than one reason, in which case after you rectify what was displayed the first time, a second

display will appear.

If the current (amps) display is 0.00A, then the chlorinator is operating normally but is in the off part

of its normal operating cycle.  Simply press either the “+” or “-“ key to start a new cycle.

The Aqua Plus 16v periodically reverses the polarity of the voltage applied to the cell in order to

automatically clean off any calcium deposits.  It is important that you check the chlorinator operation

in both polarities.  To do this, press either the “+” or “-“ buttons and the chlorinator will turn off, wait

for 15 seconds and then turn on in the opposite polarity.

If a conventional or solar heater is operating, it is likely that the temperature of the water at the cell is

higher than the pool/spa water temperature displayed on the Aqua Plus 16v default display.

Summary of Contents for Aqua Plus 16v

Page 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Page 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Page 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Page 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Page 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Page 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Page 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Page 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Page 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Page 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Page 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Page 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Page 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Page 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Page 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Page 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Page 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Page 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Page 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Page 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Page 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Page 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Page 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Page 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Page 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Page 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...

Reviews: