Hayward Aqua Plus 16v Operation Manual Download Page 17

14

This menu is only available if the system has been setup for Dual Equipment.  For one speed pumps,

this is the first spa filter timeclock and will determine the normal hours of filtration for the spa.  For

pool/spa combination systems with spillover enabled, the valves will automatically switch to pool

only at the start of the filtration period.

For two speed or variable speed pumps, this setting will be the period of time when the spa pump runs

at high speed (the word “Spa Filter T1” in the display will be replaced with “Spa Filter Hi”).  There is

a separate timeclock for the low speed operation (see below).  If the high speed and low speed periods

overlap, then the pump will operate in low speed during the overlap period.

There are several reasons the spa filter pump may be running at times other than the timeclock period

set above.  These include spa operation, manual operation, heater cooldown and freeze protection.

For one speed spa pumps, this is the second filter timeclock

For two speed or variable speed pumps, this timeclock will set the normal time period for 

spa filter

pump low speed operation 

 (the word “Spa Filter T2” in the display will be replaced with “Spa Filter

Lo”).  If the filter pump is off for more than 30 seconds, the pump will first turn on at high speed for 3

minutes to prime and establish water flow.  Afterwards, it will drop down to low speed for the remainder

of the programmed low speed time period.  While this time clock will override the high speed timeclock

(see above), there are several reasons why the pump will automatically switch to high speed operation

during this programmed time period.  These include manual operation, spa operation, or heating

operation.

Aux1 - Aux6 configurations are identical.

This menu will appear only if the Aux1 is configured for timeclock.  The Aux1 output will turn on and

off at the designated times.  If the Aux1 relay is off during the programmed on time— note that some

pool equipment (example pressure side pool cleaner) can only be operated when the filter pump is

running and the pool/spa valves are in the pool-only position—the Aqua Plus 16v will keep the relay

off until these other conditions are suitable for operation.  If the Aux1 relay is on during the programmed

off time, it may be because of freeze protection.  Also, manual operation overrides the timeclock. Refer

to page 12 for general notes regarding timeclock programming.

This menu will appear only if the Aux1 is configured for countdown timer.  This setting is the time after

you manually turn on the Aux1 relay until the Aqua Plus 16v automatically turns off the relay.  You can

also manually turn off the relay at an earlier time by pressing the AUX1 button.

33

Quick “How To” Guide

Operate the Spa—Manually

1. Press the “Pool/Spa” button to go to “spa-only” operation (“SPA” LED illuminated).  In some cases,

this may take more than one press of the button.

2. If the filter pump is not already on, press the “FILTER” button to turn it on.

3. If the spa is below the desired temperature, the heater will turn on automatically when the filter pump

is on and the valves are in the spa-only position.  If you have not already set the desired temperature

for the spa, see “Set Heater Temperature” below

4. If the spa has a separate  jet pump and or blower, determine if the jet pump/blower is controlled by

any Aux or the Lights relay (it should be marked on the label inside the door).  Then press the appro-

priate button to turn on the jets/blower.

Operate the Spa—Automatically

1. Press the “MENU” button repeatedly until “Timers Menu” is displayed

2. Press the “>” button repeatedly until the “Spa—all days” or “Spa—weekends” is displayed.

3. Use the “+” and “-“ buttons to set the desired start time, then press “>” to switch to the off time.  Use

the “+” and “-“ buttons to adjust the off time.  If you are setting the “weekend” timeclock, press “>” to

go to the “weekday” settings.

Note:  During the programmed spa time, the valves will automatically switch to the “spa-only”

position, the filter pump will turn on, and, if the spa is not up to the desired temperature, the

heater will start.  This operation is the highest priority and will take precedence over other

automatically programmed operations.  At the end of the spa period, the Aqua Plus 16v will

return to its normally programmed operation state

.

Set the Heater Temperature (or turn heater permanently off)

1. Press the “MENU” button repeatedly until “Settings Menu” is displayed

2. Press the “>” button repeatedly until the “Spa Heater” or “Pool Heater” is displayed.

3. Press the “+” or “-“ buttons repeatedly to adjust the temperature.  If you adjust the temperature below

65ºF or above 104°F the display will indicate “off” and the heater will not operate regardless of

temperature.

Note:  Separate temperatures for the pool and spa must be set.  If the valves are in the pool-only

or spa spillover positions, then the heater will use the pool setting.  If the valves are in the spa-

only position then the heater will operate according to the spa setting.

Set the Chlorinator Output

1. Press the “MENU” button repeatedly until “Settings Menu” is displayed.

2. Press the “>” button repeatedly until the “Spa Chlorinator” or “Pool Chlorinator” is displayed.

3. Press the “+” or “-“ buttons repeatedly to adjust the setting.  If you adjust the setting to 0% the

chlorinator will be off all the time.

NOTE: After the ideal "Desired Output %" setting has been found, you may need to raise the

setting when the pool water temperature increases significantly, when there is higher than

normal bather load or when your chlorinator cell ages.  You may need to lower the setting when

the pool water temperature decreases significantly or there are long periods of inactivity.

Set Day and Time

Wednesday 10:37P

Adjust time setting
Move between start and stop times & to previous/next menu item

Spa Filter  T1-all 

8:30A to 4:00P

Spa Filter  T1-wkend

8:30A to 4:00P

Spa Filter  T1-wkday

8:30A to 4:00P

Adjust time setting

Adjust time setting

Move between start and stop times & to previous/next menu item

Move between start and stop times & to previous/next menu item

or

Set Day and Time

Wednesday 10:37P

Adjust time setting
Move between start and stop times & to previous/next menu item

Spa Filter  T2

8:30A to 4:00P

-all

Spa Filter  T2-wkend

8:30A to 4:00P

Spa Filter  T2-wkday

8:30A to 4:00P

Adjust time setting

Adjust time setting

Move between start and stop times & to previous/next menu item

Move between start and stop times & to previous/next menu item

or

Set Day and Time

Wednesday 10:37P

Adjust time setting
Move between start and stop times & to previous/next menu item

Aux1-all

8:30A to 4:00P

Aux1-wkend

8:30A to 4:00P

Aux1-wkday

8:30A to 4:00P

Adjust time setting

Adjust time setting

Move between start and stop times & to previous/next menu item

Move between start and stop times & to previous/next menu item

or

or

Aux1-CountDn

0:20

Adjust time setting (Manual On/Off, 0:05, 0:10, 0:15...)
Move to previous/next menu item

Summary of Contents for Aqua Plus 16v

Page 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Page 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Page 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Page 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Page 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Page 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Page 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Page 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Page 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Page 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Page 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Page 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Page 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Page 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Page 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Page 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Page 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Page 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Page 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Page 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Page 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Page 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Page 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Page 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Page 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Page 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...

Reviews: