NOTE:  Heater1 and Heater2 configuration are identical.  If Heater2 is enabled then Valve4 will automatically be disabled due

to the fact that they use the same output relay and only 1 function can be assigned to that relay.

Heater1 Config.

+ to view/change

Heater1 

Disable

Heater1 Cooldown 

Disabled

Heater1 Extend 

Disabled

No

Push to access heater options

Toggle between Enabled and Disabled (default) Heater 1

Toggle between Enabled and Disabled (default) Heater 1 Cooldown

Toggle between Enabled and Disabled (default) Heater 1 Extend

Toggle between Enabled and Disabled (default) 

Move to previous/next configuration menu

Move to next menu item or previous/next configuration menu

Move to next menu item

Move to previous/next configuration menu

Move to previous/next configuration menu

if “Heater1” is enabled

if “Heater1” is enabled

if “Heater1” is enabled

display for Heater2 if "Heater2" is enabled

Heater1 Name

Gas Heater

Rotates between all available names 
Move to next menu item

Allow Low Speed 

Minimum Speed

Disabled

50%

Toggle between Enabled and Disabled (default) 

Select the desired minimum filter pump speed for Heater 1 (Filter Lowest to Highest) 

Move to 

Move to 

next menu item or previous/next configuration menu

next menu item or previous/next configuration menu

if “Heater1” is enabled and

if “Heater1” is enabled and

2-speed filter pump is selected

variable speed filter pump is selected

Heater1

If the heater is “Enabled”, the heater relay will turn on when the water temperature is less than the
desired temperature setting and the filter pump is running.  The desired temperature is in the “Settings
Menu”.  If applicable, the homeowner will be prompted to enter separate “pool” and “spa” settings.
Depending on the position of the pool/spa suction valves, the proper temperature setting will be
used.

Heater Name

The Aqua Plus 16v allows you to assign any one of a number of names (e.g. “Gas Heater, Heat Pump,
etc.) to each of the heater control functions. This will make the Aqua Plus 16v much more user
friendly to the homeowner when they want to turn various heaters on or off or set temperatures. A
sheet of small name labels is included with the Aqua Plus 16v main unit and each remote display/
keypad so that appropriate pushbuttons can be labeled the same as the name that you have as-
signed.

Heater Cooldown

This feature ensures that the heater cools down before water circulation is stopped.  When enabled,
the Aqua Plus 16v will continue to run the filter pump for 5 minutes after the heater turns off.  During
this period the filter pump LED will flash and also a “Heater Cooldown, X:XX remaining” message will
scroll on the display.

When the filter pump is running and the heater is on:  Pressing the “Filter” button once will cause the
heater to turn off, but the filter pump will continue to run for heater cooldown (filter LED flashing and
message on display).  Pushing the filter button a second time will override the heater cooldown
operation and turn the filter pump off.

For a Pool/Spa Setup selection of “Pool Only”, “Spa Only” or “Pool and Spa-Std”, Heater1 and/or

Heater2 cooldown affect the filter pump. For “Pool and Spa-Dual”, Heater1 is associated with the spa

filter and Heater2 with the pool filter.

Heater Extend

If “Enabled”, the filter extend logic keeps the filter pump running beyond the normal turn-off time until
the pool (or spa) is heated up to the desired temperature setting (see Settings Menu).    Heater extend
will NOT cause the filter pump to turn on, it will only delay the turn off time when the heater is
operating.

25

Lights Function

Although designated as the “Lights” output, the function of the lights relay is similar to the Aux

relays.  If pool lights are wired to the lights relay, some options including Solar function, Low Speed

of a 2-Speed Filter Pump, Lights Interlock and Lights Freeze Protection are not applicable and should

be disabled.  If no pool lights are used, the lights relay can be used to control other pool devices that

may require these options.  The function of each option is shown below.

Manual On/Off

—the lights relay will alternate between turning on and off when the LIGHTS button is

pressed.  There is no automatic control logic.

Countdown Timer

—the lights relay will turn on when the LIGHTS button is pressed.  The lights relay

will turn off automatically after a programmed time (see Timers Menu).  The LIGHTS button can also

be used to turn the output off.

Low Speed of a 2-speed Filter Pump

 – the Aqua Plus 16v will turn on the lights relay whenever the low

speed operation of the filter pump is required.  It is very important that the “2-speed” filter pump

option be selected under the “Filter Config.” Menu for proper operation.

Timeclock

 – the lights relay will turn-on and turn-off at the times set for the lights timeclock in the

Settings Menu (see Settings Menu).  The LIGHTS button can also be used to turn the output on and

off.

Solar

 – the lights relay can operate a solar booster pump which will turn on when the filter pump is

running and solar heat is available and the water is less than the desired temperature setting.  Note

that “Solar” must be enabled in the “Solar Config.” menu for proper operation to occur.

Low Speed of a 2-Speed Spa Filter Pump

 – the Aqua Plus 16v will turn on the lights relay whenever

the low speed operation of the Dual Equipment Spa filter pump is required.  “Pool and Spa-Dual”

(located in Pool/Spa Setup menu) and “2-Speed” (located in Spa Filter Config. menu) must be selected

for proper operation.

Group 

 – the lights relay operates when the Group function is initiated and shuts off when the Group

function is terminated.  See Lights Group section for operation information for the Group function.

Super Chlorinate 

 – The Super Chlorinate function can be assigned to any Aux, Lights or Valve

button.  This allows the user to simply hit a button to start a Super Chlorinate cycle, rather than using

the Settings Menu.  Note that only one button can me assigned to this function.

pH Dispense 

 –When Chemistry Sensing is enabled and pH Reduction Control is NOT disabled, the

Aqua Plus 16v will turn on the Lights relay when there is a need to energize the pH dispensing device.

The pH Dispense function can be assigned to any Aux or the Lights output. Once programmed for pH

Dispense, the Lights button will have no function.  Requires the use of the AQL-CHEM sensing kit.

Lights Relay

This feature allows the user to select either “Standard” (default), “Dimmer” or “VSP” type relay for the

Lights output.  The optional AQL-DIM dimmer kit must be installed if “Dimmer” is desired.

When “Dimmer” is selected, and the Lights output is manually turned on, the “+” and “-” buttons

adjust the level from 20% to 100% (default).  The level is saved for the next time the lights are turned

from off to on.

If “VSP” is selected, the Lights relay is used to supply power to a Hayward Variable Speed Pump

(VSP).  The relay will be on when the Lights output is on and off when the output is off.  On, off and

speed are controlled by commands sent to the VSP.  Note: Up to 6 Lights/Aux outputs can be

configured as VSP relays.

Lights Interlock

If enabled, this feature will override the function (Manual On/Off, Countdown Timer, Timeclock)

selected above and turn the lights relay off when:  filter pump is off, first 3 minutes of filter pump

operation (allows the pump to prime and get water flowing), when the pool/spa suction return valves

are in any position other than “pool only”, or for the first 3 minutes after solar turns on (allows air in

the solar panels to be purged).  Interlock is not available for solar, low speed filter pump, dimmer,

group, super chlorinate, or pH dispense functions.

Lights Group

The Lights Group function allows the user to perform multiple tasks with a single push of the “Lights”

button. When setting up a Group function, refer to page 15 for specific programming information.

There are two Group menus; the first menu determines how the group command will be initiated

(Manual On/Off, Countdown Timer, or Timeclock) and the second menu selects the desired functions

and their respective control parameters.

Summary of Contents for Aqua Plus 16v

Page 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Page 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Page 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Page 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Page 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Page 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Page 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Page 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Page 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Page 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Page 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Page 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Page 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Page 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Page 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Page 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Page 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Page 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Page 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Page 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Page 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Page 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Page 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Page 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Page 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Page 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...

Reviews: