Filter Pump

For 2-speed pumps:  When a 2-speed pump is configured, one of  the AUX relays must also be

configured to control the low speed motor winding on the pump.  Refer to the appropriate sections in

the Installation manual for specific information regarding the control logic for 2-speed and variable

speed pump operation.

For the Hayward variable speed pump:  The Filter relay is used to supply input power to the pump.

The relay will be on when the filter pump output is on.  When the filter pump output is off, the relay will

be off.  On , off and speed is controlled by commands sent to the pump.

Lowest Speed

This is the lowest speed that the variable speed pump is allowed to run at. It is used as the lower limit

in the Low Speed Settings Menu. Set lowest speed from 10% (default) to 50%.

Highest Speed

This is the highest speed that the variable speed pump is allowed to run at. It is used as the upper limit

in the High Speed Settings Menu.  Also, this is the speed that the pump will run at during the first 3

minutes of operation anytime the pump has been off for more than 30 seconds. Set highest speed from

20% to 100% (default).

Flow Monitor

This feature will help protect the filter pump from damage due to no flow.  When used with a Hayward

flow switch, the Aqua Plus 16v monitors the state of water flow when the filter pump is on.  If no flow

is detected for more than 15 minutes, the Aqua Plus 16v will shut down the pool pump and the “Check

System” LED will indicate an error.  The error will be cleared the next time the pump is turned on.

Freeze Protection

Freeze protection is used to protect the pool and plumbed equipment against freeze damage.  If freeze
protection is enabled and the AIR temperature sensor falls below the freeze threshold (see below), the
Aqua Plus 16v will turn on the filter pump to circulate the water. If “Pool and Spa” is selected in the
Pool/Spa sub-menu (see page 18), the valves will also alternate between the pool and spa every 30
minutes and the filter pump will turn off while the valves are turning.  The chlorinator will not operate
if freeze protection is the only reason the pump is running.

Freeze Protection Speed

This menu only appears if freeze protection is enabled and the pump is configured for 2-speed or

variable speed pump operation. If the pump turns on due to freeze protection only, the pump will run

at this speed.

2-Speed pumps: Select high (default) or low speed operation.

Variable Speed pumps: Select the desired speed (from Filter Lowest to Filter Highest speed).

Freeze Protection Temperature

Select the temperature to be used for freeze protection.  Temperature is adjustable from 33ºF-42ºF (1ºC-
6ºC).  38ºF (3ºC) is default. This threshold will be used for all outputs that have freeze protection
enabled.

External Input Interlock

When enabled, the filter pump will be forced off when the external input is active.  Note that freeze

protection will have precedence over this feature.

27

Aux1 Name

The Aqua Plus 16v allows you to assign any one of a number of names (e.g. “Cleaner Pump, Waterfall,

Gazebo Light, etc.) to each of the aux outputs control function.  This will make the Aqua Plus 16v much

more user friendly to the homeowner when they want to turn various aux equipment on or off or

program the timeclocks.  A sheet of small name labels is included with the Aqua Plus 16v main unit and

each remote display/keypad so that the “Aux” pushbutton can be labeled the same as the name that

you have assigned. At this time it is also a good idea to make sure that the relay in the control box is

also labeled (hand written) with the same name as a help to technicians who may service this system

at a later date.

Aux1 Function

Manual On/Off (default)

—the aux relay will alternate between turning on and off when the aux button

is pressed.  There is no automatic control logic.

Countdown Timer

 – the aux relay will turn on when the AUX button is pressed and then will turn off

automatically after a programmed time (see Timers Menu in the Operations Manual).  The AUX button

can also be used to turn the output off.

Low Speed of a 2-speed Filter Pump

 – the Aqua Plus 16v will operate the aux relay whenever the low

speed operation of the filter pump is required.  It is very important that the “2-speed” filter pump

option be selected under the “Filter Config.” Menu for proper operation.

Timeclock

 – the aux relay will turn-on and turn-off at the times set for the aux timeclock in the Timers

Menu (see Operations Manual).  The AUX button can also be used to turn the output on and off.

Solar

 – the aux relay operates a solar booster pump which will turn on when the filter pump is running

and solar heat is available and the water is less than the desired temperature setting.  It is important to

note that “Solar” must be enabled in the “Solar Config.” menu for proper operation to occur.

Low Speed of a 2-Speed Spa Filter Pump

 – the Aqua Plus 16v will turn on the aux relay whenever the

low speed operation of the Dual Equipment Spa filter pump is required.  “Pool and Spa-Dual” (located

in Pool/Spa Setup menu) and “2-Speed” (located in Spa Filter Config. menu) must be selected for

proper operation.

Group 

 – the aux relay operates when the Group function is initiated and shuts off when the Group

function is terminated.  See Aux1 Group section for operation information for the Group function.

Super Chlorinate 

 – The Super Chlorinate function can be assigned to any Aux, Lights or Valve

button.  This allows the user to simply hit a button to start a Super Chlorinate cycle, rather than using

the Settings Menu.  Note that only one button can me assigned to this function.

pH Dispense 

 – When Chemistry Sensing is enabled and pH Reduction Control is NOT disabled, the

Aqua Plus 16v will turn on the Aux relay when there is a need to energize the pH dispensing device.

The pH Dispense function can be assigned to any Aux or the Lights output. Once programmed for pH

Dispense, the Aux button will have no function.  Requires the use of the AQL-CHEM sensing kit.

Aux1 Relay

This feature allows the user to select either “Standard” (default), “Dimmer”, “ColorLogic” or “VSP”

type relay for the Aux1 output.  The optional AQL-DIM dimmer kit must be installed if “Dimmer” is

desired.  The AQL-COLOR-MODHV ColorLogic Network Module must be installed if “ColorLogic” is

desired.

When “Dimmer” is selected, and the Aux1 output is manually turned on, the “+” and “-” buttons

adjust the level from 20% to 100% (default).  The level is saved for the next time the aux1 output is

turned from off to on.

If “ColorLogic” is selected (Network Module must be detected at startup for this option to appear),

additional menus will prompt you for configuration information.  Refer to the AQL-COLOR-MODHV

manual for details on how to configure an Aux output for use with Generation 3 or later ColorLogic

lights.

If “VSP” is selected, the Aux relay is used to supply power to a Hayward Variable Speed Pump (VSP).

The relay will be on when the Aux output is on and off when the output is off.  On, off and speed are

controlled by commands sent to the VSP.  Note: Up to 6 Lights/Aux outputs can be configured as VSP

relays.

Aux1 Interlock

If “Enabled”, this feature will override the function (Manual On/Off, Countdown Timer, Timeclock),

selected above and turn the aux1 off when:  filter pump is off, first 3 minutes of filter pump operation

(allows the pump to prime and get water flowing), when the pool/spa suction return valves are in any

Summary of Contents for Aqua Plus 16v

Page 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Page 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Page 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Page 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Page 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Page 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Page 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Page 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Page 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Page 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Page 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Page 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Page 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Page 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Page 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Page 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Page 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Page 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Page 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Page 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Page 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Page 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Page 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Page 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Page 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Page 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...