For a Pool/Spa Setup selection of “Pool Only”, “Spa Only” or “Pool and Spa-Std”, Heater1 and/or

Heater2 will keep the filter pump running. For “Pool and Spa-Dual”, Heater1 will keep the spa filter

running and Heater2 will keep the pool filter running.

Allow Low Speed

This menu only appears if the filter is configured for 2-speed operation.  During default operation,

high speed mode is used whenever the heater is on.  If Allow Low Speed is enabled, low speed will be

allowed even if the heater is on.

Minimum Speed

This menu only appears if the filter is configured for variable speed operation.  This is the minimum

speed the pump will run at when the heater is on. The selection is from Filter Lowest to Filter Highest

speed.

Heater2 is Heatpump

This menu appears in the Heater2 configuration menu if Heater2 is enabled.  If set to “Yes”, Heater2

will only be allowed to be on if the Air Temperature is >  50°F. Also, two new menus, Spa Heater2

Priority and Pool Heater2 Priority, will appear in the Settings Menu. Refer to the Settings Menu for

more information on these new menus.

Solar Config.

+ to view/change

Solar

Disabled

Solar-Extend 

Disabled

Solar Priority

Disabled

Push to access solar options

Toggle between Enabled and Disabled (default) Solar

Toggle between Enabled and Disabled (default) Solar Extend

Toggle between Enabled and Disabled (default) Solar Priority

Move to previous/next configuration menu

Move to next menu item or previous/next configuration menu

Move to next menu item

Move to next menu item

if “Solar” is enabled

if “Solar” is enabled

Allow Low Speed 

Disabled

Toggle between Enabled and Disabled (default) 
Move to next menu item or previous/next configuration menu

if “Solar” is enabled and
“2-speed Filter” is selected

Solar

The Solar configuration menu will 

NOT

 appear if “Pool and Spa - Dual” has been selected in the Pool/

Spa setup menu.  If the solar control logic is “Enabled”, several additional steps must be taken to

ensure proper operation of the solar heating system.  If the solar is operated by a valve, then a valve

(Valve3 or Valve4) output must be setup for solar logic (page 29).   If the solar is operated by a pump,

then one of the AUX relays must be set up for solar logic (page 27).  Also, the “solar” temperature

sensor must be installed.  This sensor is typically mounted near the collector array and is used to

sense whether sufficient solar heat is available.

If solar is “Enabled”, the valve or solar pump relay will turn on when the water temperature is less than

the desired temperature setting AND the solar sensor is hotter than the water by at least 8ºF.  The

desired temperature is in the “Settings Menu”.  If applicable, the homeowner will be prompted to enter

separate pool and spa desired temperature settings.  Depending on the position of the pool/spa

suction valve, the proper temperature setting will be used.

Solar Extend

If “Enabled”, the filter extend logic keeps the filter pump running beyond the normal turn-off time if

solar heat is still available.  When solar heat is no longer available, both the solar valve/pump and filter

pump will turn off simultaneously.  Solar extend will NOT cause the filter pump to turn on, it will only

delay the turn off time when solar is operating.

Solar Priority

If both “Solar Control” and “Heater Control” are enabled, the Solar Priority feature will keep the

conventional heater off whenever solar heat is available.  This provides the most cost effective way of

heating the pool.  When solar heat is not available, the conventional heater will operate normally.

Allow Low Speed

This menu only appears if the pool filter is configured for 2-speed operation.  During default operation,

high speed mode is used whenever the solar heater is on.  If Allow Low Speed is enabled, low speed

pump operation will be allowed during solar heating except for the first 3 minutes after solar heat turns

on.

only if optional ColorLogic Network

Module is detected at power up

ColorLogic Config.

+ to view/change

Push to activate ColorLogic options

Move to previous/next configuration menu

ColorLogic Config.

This menu appears if the optional ColorLogic Network Module is installed and detected at power up.

Refer to the AQL-COLOR-MODHV manual for detailed installation and operation instructions.

External Input

Active Closed

Toggle between Open and Closed (default) 
Move to next menu item or previous/next configuration menu

External Input

The external input device can either be normally open or normally closed.  In this menu, select the state

of the external input device when active. For example, if the switch is normally open and closes when

active, set External Input to “Active Closed”.

NOTE: If an AQL-COLOR-MODHV ColorLogic Network Module is detected at startup, only the Lights Name menu will appear
under Lights Configuration. Refer to the AQL-COLOR-MODHV manual for more information.

Lights Config.

+ to view/change

Lights Function

Manual On/Off

Lights Name

Pool Light

Lights Relay

Standard

Push to access Lights options

Rotates between 

Manual On/Off (default), Countdown Timer, Low Speed- Filter,

Timeclock, Solar, Low Speed-Spa Filter, Group, Super Chlorinate, and pH Dispense

Rotates between all available names 

Toggle between Standard (default), Dimmer and VSP 

Move to previous/next configuration menu 

Move to next menu item

Move to next menu item or previous/next configuration menu

Move to next menu item or previous/next configuration menu

Lights Interlock

Disable

Lights Freeze

Disable

Toggle between Enabled and Disabled (default) Lights Interlock

Toggle between Enabled and Disabled (default) Lights Freeze

Move to next menu item

Move to previous/next configuration menu 

for all functions except solar, dimmer relay, super chlorinate
pH dispense, low speed, and group

for all functions except solar, dimmer relay, super chlorinate
pH dispense, low speed, and group

f

 

pH dispense, low speed, and group

or all functions except dimmer relay, super chlorinate

if filter pump is set to variable speed

and the relay type is set to standard

for manual on/off, countdown
timer and timeclock functions

Lights Group

Filter: Unaffected

Lights Group

Timer: None(Manual)

Options available depend on the function that is selected

Rotates between Manual On/Off (default),Countdown Timer and Timeclock

Move to previous/next menu item or next configuration menu

Move to next menu item

for group function only

for group function only

Lights Ext Input

Disabled

Toggle between Enabled and Disabled (default)
Move to previous/next configuration menu

Lights Pump Spd

Settings Menu

Select Settings Menu (default) or desired pump speed (Filter Lowest to Highest)
Move to previous/next configuration menu 

Lights Name

The Aqua Plus 16v allows you to assign any one of a number of names (e.g. “Pool Light, Spa Light,

Deck Light, etc.) to this control function.  Note that other lights may be assigned to other  Aux

outputs.  This will make the Aqua Plus 16v much more user friendly to the homeowner when they want

to turn various lights on or off.   A sheet of small name labels is included with the Aqua Plus 16v main

unit and each remote display/keypad so that the “Lights” pushbutton can be labeled the same as the

name that you have assigned.  At this time it is also a good idea to make sure that the relay in the

control box is also labeled (hand written) with the same name as a help to technicians who may service

this system at a later date.

Summary of Contents for Aqua Plus 16v

Page 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Page 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Page 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Page 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Page 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Page 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Page 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Page 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Page 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Page 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Page 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Page 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Page 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Page 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Page 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Page 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Page 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Page 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Page 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Page 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Page 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Page 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Page 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Page 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Page 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Page 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...

Reviews: