MODU-FIRE
®
Forced Draft Gas-Fired Boiler 2500-3000
44
6.1.2
Terminal Block Assignments – Low Voltage Circuit (TB1)
Terminal
Number
Label Description
1
Enable / Disable
Boiler Enable, Contact Closure.
DO NOT ENERGIZE.
2
3
Auxiliary Low Water Cutoff External Limit, Contact Closure.
DO NOT ENERGIZE.
4
5 External
Interlock
External Limit, Contact Closure.
DO NOT ENERGIZE.
6
7
Outdoor Temp Sensor
Outdoor Temperature Sensor Circuit
8
9
DHW Stat or Sensor
Domestic Hot Water Thermostat (contact closure) or
Temperature Sensor
10
11
Header Temp Sensor
Header Temperature Sensor
12
13
DHW Flow Switch
DHW Flow Switch (contact closure)
14
15
0-10V Analog Input
0-10VDC Remote Control Input
16
0V Analog Input
0VDC Remote Control Common
17
For Future Use
18
For Future Use
19 MODBUS
®
COM 1A
20 MODBUS
®
COM 1B
21
CASCADE A TO A
22
CASCADE B TO B