MODU-FIRE
®
Forced Draft Gas-Fired Boiler 2500-3000
38
5.6.3 Low
Gas
Pressure
The low gas pressure switch opens when there is insufficient gas pressure available for proper operation of the
boiler. LOW GAS PRESSURE is displayed, and burner operation is interrupted. If a gas-supply shut-off valve is
closed for any reason, a low gas condition will result. When gas pressure is restored, LOW GAS PRESSURE will
remain on the display panel. A manual reset is required to restart the boiler, provided that all other limits are
satisfied.
5.6.4
High Gas Pressure
The high gas pressure switch opens when there is excessive manifold gas pressure for the proper operation of
the boiler. HIGH GAS PRESSURE is displayed and the burner operation is interrupted. When proper gas
manifold pressure is restored, HIGH GAS PRESSURE remains on the display panel. A manual reset is required
to restart the boiler, provided that all other limits are satisfied.
5.6.5 High
Water
Temperature
When the boiler water has exceeded both the operating and high-limit temperature the high limit switch opens,
and HIGH LIMIT
is shown on the display. When the water temperature falls below the high-limit temperature, the
boiler will remain locked out until the water high limit switch is manually reset and the front panel reset button is
pressed. Once the switch and the control are reset, the sequence returns to Step 3 to await heat demand
provided that the other limits are satisfied.
5.6.6 Low
Air
The air switch has been factory set and should not be adjusted in the field.
If the display panel indicates AIR SWITCH NOT OPEN
or AIR SWITCH NOT CLOSE this indicates improper air-
flow through the boiler. Check the hoses leading to the air switches. Verify proper blower operation. An air switch
error does not necessarily mean that the air switch is defective.
When
AIR SWITCH NOT OPEN is shown on the display, check that the air switch is open when the fan is off.
Check that there is no air flow through the boiler when the fan is off.
When AIR SWITCH NOT CLOSE is shown on the display, check that the air switch is closed when the fan is
running. If the air switch does not close within 5 minutes during purge, the boiler locks out. Check that the burner
is clean and that there are no obstructions to airflow in the intake or exhaust ducts.
5.6.7
Vent Pressure
BLOCKED FLUE
indicates that the high exhaust back pressure switch has tripped. This may be caused by a
blocked stack, a blocked air inlet, or a blocked condensate system. When the blockage is removed, the boiler will
automatically restart.
5.6.8 Ignition
Failure
In the event the flame is not detected by the UV scanner during the 4 second trial-for-ignition period (Step 9), the
gas valve and spark ignition are de-energized. At this time a safety lockout occurs. A manual reset of the
programmer (located inside the control panel) is required.
5.6.9 Flame
Failure
In the event of a flame failure, the main fuel valves are de-energized and a manual reset lockout occurs. IGNI-
TION ERROR or FLAME ERROR is shown on the display. The cause of flame failure must be diagnosed and re-
paired before the control is reset.
When IGNITION ERROR is shown on the display, the boiler has not lit during a trial for ignition. Check that the
spark, electrode, ignition wire, and gas valve are functioning properly.
When FLAME ERROR is shown on the display, the boiler has lost the flame during run. Check that the combus-
tion is setup properly, the gas pressure is correct, as well as other combustion parameters.
Summary of Contents for 1004905923
Page 2: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 2 ...
Page 45: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 45 6 1 3 Wiring Schematic ...
Page 48: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 48 6 1 6 Rear Junction Box ...
Page 49: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 49 6 1 7 Customer Connections ...
Page 56: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 56 ...