MODU-FIRE
®
Forced Draft Gas-Fired Boiler 2500-3000
15
NOTICE!
1. The required size of openings for combustion and ventilation air shall be based on the net free area of the
opening.
2. Screens shall be not smaller than ¼”
3. Motorized louvers shall be interlocked with the appliance so that they are proven open prior to main burner
ignition and operation.
Table of US Minimum area of ventilation openings per boiler (sq inches)
MFD
MODEL
AIR SOURCE
INDOOR AIR SUPPLY
OUTDOOR AIR SUPPLY
SAME FLOOR
DIFF FLOORS
ONE OPENING
TWO OPENINGS
DIRECT
VERT
DUCT
HORIZ
DUCT
N2500 2500
5000
833.3 625
625 1250
N3000 3000
6000
1000 750
750 1500
3.5.2.2
Air Inlet Requirements – Canada (CAN/CSA B149.1)
A. Ventilation of the space occupied by fuel burning appliance(s) or equipment shall be supplied by a ventilation
opening at the highest practicable point communicating with the outdoors. The total cross sectional area of
the ventilation opening must be either 10% of the net free area required for combustion air or 10 sq. in. (6500
mm
2
), whichever is greater.
B. Use the following opening calculation for MACH
®
condensing boilers
or MODU-FIRE
®
Forced Draft boilers:
When combustion air is supplied for a forced draft burner by natural airflow from the outdoors and there is no
draft regulator or draft hood in the same space, there shall be a permanent opening with a cross sectional ar-
ea not less than 1 sq. in/ 30,000 Btu/Hr (70 mm
2
/kW) of the total rated input to the burner(s). This opening
must not interfere with the ventilation air opening defined in paragraph A.
C. Use the following opening calculation for P-K THERMIFIC
®
boilers or other natural draft or fan-assist appli-
ances:
When combustion air is supplied for natural or fan-assisted burners by natural airflow from the outdoors, there
shall be a permanent opening with a cross sectional area not less than 1 sq. in/ 7000 Btu/Hr (321 mm
2
/kW)
up to and including 1,000,000 Btu/Hr plus 1 sq. in. / 14,000 Btu/Hr (155 mm
2
/kW) in excess 1,000,000 Btu/Hr.
This opening must be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in.
(150 mm) above floor level. This opening is in addition to the ventilation air opening defined in paragraph A.
D. When combustion air is supplied by natural airflow into a space containing both types of appliances described
in paragraphs B and C, the cross sectional area of the opening shall be not less than the sum of the cross
sectional areas for all appliances in the space as calculated by the applicable method . This opening is in ad-
dition to the ventilation air opening defined in paragraph A.
E. When a duct is used to meet the requirement for combustion air supply, as described in paragraphs A through
D, above, the opening of the duct shall be located so there is no possibility of cold air affecting steam or water
piping, electrical equipment or mechanical equipment.
F. When combustion air is supplied by mechanical means, an airflow-sensing device must be installed. It must
be wired into the pre-ignition limit string to prevent the burner from starting or to stop an operating burner in
case of air supply failure.
G. When all combustion air is supplied through a make-up air heater, and the appliance is interlocked to the
heater, the requirements of paragraphs A through F do not apply.
Summary of Contents for 1004905923
Page 2: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 2 ...
Page 45: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 45 6 1 3 Wiring Schematic ...
Page 48: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 48 6 1 6 Rear Junction Box ...
Page 49: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 49 6 1 7 Customer Connections ...
Page 56: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 56 ...