Setting item
Description
All ways turn on alarm
Maintain alarm on operation
Maintain alarm on fixed control operation
Maintain alarm on program control operation
4 buttons in the system alarm setting screen [FIG 100] on the above select the operation
condition (Operation condition related to the set value) and information is as follows.
[FIG.100] System alarm setup screen
[FIG.101] System alarm code setting
71
The TH500 / 300 is equipped with the total 16 PID ZONEs. As shown in the chart below, the four
temperature zones and four humidity zones are combined with each other, so you can control the
temperature and humidity with the optimized PID value. You are free to change the zone boundary
of temperature and humidity.
Humi. Zone
Temp. Zone
0≤Humi. SV≤HZ
1
HZ
1
≺Humi. SV≤HZ
2
HZ
2
≺Humi. SV≤HZ
3
HZ
3
≺Humi. SV≤HZ
4
-100≤Temp. SV≤TZ
1
Zone 1
Zone 5
Zone 9
Zone 13
TZ
1
≺Temp. SV≤TZ
2
Zone 2
Zone 6
Zone 10
Zone 14
TZ
2
≺Temp. SV≤TZ
3
Zone 3
Zone 7
Zone 11
Zone 15
TZ
3
≺Temp. SV≤TZ
4
Zone 4
Zone 8
Zone 12
Zone 16
6.5 P.I.D Setting
※ TZ : Temp.Zone, HZ : Humi.Zone