background image

93

Bias(Deviation)

Dry· Wet sensor Bias
Scaling
LPF
Detection of sensor
disconnection
Operation method selection
Temperature
Humidity
Pattern
Segment
P.I.D group
Auto Tuning

Proportional
Band

Integral Time
Derivative Time
ON/OFF control
Direct/Reverse action
ON/OFF
Hysteresis
Temp•Humidity
Scaling
Setting Alarm
Alarm type

Process Alarm

Deviation Alarm

Hysteresis

Memory

Memory function

Input

Control mode

Control

output

Control

Action

Retransmission

Output

Alarm

Setting

Storage

against Power

failure

Temp. : -100.00 ~ 100.00 (℃)         

Humidity : -100.0 ~ 100.0 (% R.H)

After removing gauze from wet sensor, correct the difference between dry and wet sensor.

V d.c : Input scale in accordance with conversion range

2 ~ 180 sec

1 ~ 180 sec

Up scale(In case of R.T.D input),

Stop operation when it is over ±5 % of its range

Fix Control / Program Control

SSR/SCR 4  - 20 ㎃ d.c

SSR (Pulse Voltage)

SSR/SCR 4  - 20 ㎃ d.c

SSR (Pulse Voltage)

100 patterns (1 pattern/100 segments)

6,000 max segments

2,000 max segments

16 Groups (Temp 4 zones x Humidity 4 zones)

Auto Tuning according to SV(Setting Value)

Temp. : 0.00 ~ 600.00 ℃

Humidity : 0.00 ~ 200.00 %                 

0.00% = ON/OFF control

0.0 ~ 6.000 sec ( 0 sec = OFF )
0.0 ~ 6.000 sec ( 0 sec = OFF )

Set the Proportional Band as 0.0

Select Direct or Reverse action in control output.

0.1 ~ 300 ℃                      0.1 ~ 600.0 ℃

(In case of humidity, it is a web bulb temperature or converted value)

4 - 20 ㎃ d.c, Select among PV,SV and MV(Manipulated Value)

Perform scaling of the High· Low deviation range 4 - 20 ㎃ d.c automatically

System Alarm : 4 points Alarm per pattern : 4 points

Including HighoLow /Low deviation alarm etc. 20 types of alarm are available.

Temp. : -100.0 ~ 200.0 ℃

Temp. : -100.0 ~ 500.0 ℃

Humidity : 0.0 ~ 100.0 % RH

Temp. : -300.0 ~ 300.0 ℃

Temp. : -600.0 ~ 600.0 ℃

Humidity : 0.0 ~ 100.0 % RH

Temp. : 0.0 ~ 300.0 ℃

Temp. : 0.0 ~ 600.0 ℃

Humidity : 0.0 ~ 100.0 % RH

Humidity : 0.0 ~ 100.0 % RH

Internal Flash Memory and FRAM

Program Information and SV(Setting Value) backup and restoration.

Storage of Temperature-Humidity setting value and PV

8.5 Functions

Model

TH500

TH300

0.00 ~ 100.00 % 
0.00% = ON/OFF control

th300_500_통합본_th300_500_통합본.qxp  19. 6. 26.  오후 1:36  페이지 93

Summary of Contents for TH500

Page 1: ...Manual Programmable Temperature and Humidity Controller th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 32 페이지 2 ...

Page 2: ...r type setting 59 6 2 Control output setting 63 6 3 Retransmission output setting 66 6 4 Inner signal and alarm setting 67 6 5 P I D setting 71 6 6 Digital input D I configuration setting 74 6 7 Digital output D O configuration setting 76 6 8 Communication setting 80 6 9 Other setting 81 7 1 Input related setting 82 7 2 Output related setting 84 7 3 Inner signal setting 85 7 4 Fix control 86 7 5 P...

Page 3: ... the product Information in this manual may changed without prior notification If you have any question or find error in this manual please contact us Copying or reprinting this manual without notifying us is prohibited Service A S Please send product to the nearest distributor agency or head quarter for A S When willing to have an on site A S please call our A S center and make an appointment Bef...

Page 4: ...is incorrect model type or find any abnormal parts scratches on the outside please contact to our nearest sales office Standard Type Fixing bracket Resistance 250 Ω 2 Manual 1 1 1 TH500 I O Board 1 40p cable Additional Type Fixing bracket Resistance 250 Ω 2 Manual Standard 1 TH500 1NN Additional 1 TH500 21N th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 32 페이지 5 ...

Page 5: ...2 TH500 24N I O Board 1 I O Board 2 40p cable 20p cable Additional Type Manual Fixing bracket Resistance 250 Ω 2 Resistance 250 Ω 2 Fixing bracket 40p cable 20p cable Manual Resistance 250 Ω 2 Fixing bracket Manual th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 6 ...

Page 6: ...l gas ammonia etc combustible or explosive gas does not occur Do not give impact to products It can cause of damage or malfunction When you wire it please cut out all of electric power Please do not block ventilating windows It may cause of break down To avoid electric shock please use it after installation to panel Do not operate controller with wet hand it may cause of electric shock This contro...

Page 7: ...g environment is DegreeII 1 3 Quality guarantee Unless it is included company s conditions for warrantee we are not responsible for any warranties or guarantees We are not responsible for any damages and indirect loss of the use or third person due to unpredicted natural disasters The warranty for this product is valid for 1 year from purchase and we will fix any breakdowns and faults from proper ...

Page 8: ...ket Panel Insertion direction Thickness of panel 1 10 Fixing bracket Fixing bracket To prevent electric shock please check turn off power Before turn on power please connect over the third class grounding During retransmission it may cause electric shock so please do not touch terminal Please wire it after turn off main power Please contact around 2A fuse to main electronic power line TH500 TH300 ...

Page 9: ...t 12 points Temp Humidity control output SSR SCR D I 8 points D O 12 points Relay Output SMPS 24V d c 18 W Input Output Board 2 Open Collector 8 points external terminal board Input Output Board 3 Relay output 8 points output board Input Output Board 1 Output Board 2 Input Output Board 1 Output Board 3 No Output Board In case of selecting standard body Korean English Standard English Simple Chines...

Page 10: ...11 186 min 147 min 186 min 147 mi n 2 3 Dimension and panel cutout 2 3 1 Type TH500 1 Standard Unit Unit TH500 2 Additional th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 11 ...

Page 11: ...body Connector 40 Pin Power Supply for sensor 24 V d c 18 W max D I 8 Points C Connector 20 Pin Unit Unit Input Output board 1 Output board 2 External terminal board th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 12 ...

Page 12: ...13 2 3 3 Standard type TH300 Output board 3 Connector 20 Pin Unit Unit th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 13 ...

Page 13: ...14 2 4 Connection Diagram 2 4 1 Model TH500 1 2 4 2 Model TH500 2 th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 14 ...

Page 14: ...retransmission out Power supply voltage Communication terminal Humidity input sensor Temperature input sensor Connector 40 Pin C Power Supply for sensor 24 V d c 18 W max C Connector 20 Pin Connector 20 Pin Input output board 1 Out put board 3 Output board 2 th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 15 ...

Page 15: ...nce difference among three wires Please connect Input Output signal wire separately from power line In case of current input please attach resistance 250 Ω 0 1 at the end of input terminals and use it accordingly SSR or SCR r recorder indicator and etc Sensor Input Connection of Temp Humidity control output and retransmission output RTD Input Connection of Temp Humidity control output Temp Humidit...

Page 16: ...17 Transistor output With TH300 D O 1 4 Relay output 1c Contact Only with TH500 Relay output 1a Contact Digital output D O th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 17 ...

Page 17: ...5 Digital Input D I When using open collector please use as follows Voltage of both ends should be below 2 V and leakage current should be below 100 2 5 Communtcation connection 2 5 1 RS232C Connection base on 9pin connector th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 18 ...

Page 18: ... 2 5 2 RS422 RS485 arrangement maximum 32 machines Please contact Terminating Resistance 100 200 Ω 1 4 W to the both of ends for retransmission lines 2 Wire connection Terminating resistance T Terminating resistance th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 19 ...

Page 19: ...en will be displayed after the Logo display FIG 1 screen and check FIG 2 screen are displayed sequentially Users can edit the logo display screen and system check screen 3 1 Initial screen FIG 1 Logo display TH500 TH300 TH500 TH300 FIG 2 System check th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 33 페이지 20 ...

Page 20: ...mbers or the text input box Fig 4 to Fig 7 will appear epending on situations Then you have only to press the set value This box is inactive under current conditions or situations However if you put it under certain conditions or situations it will turn into the active input box as shown above The Fig 3 is the basic number input box You can enter integral numbers or real numbers decimal point ther...

Page 21: ...rt of initial screen Number input screen Fig 4 is going to be displayed Set up by displaying the input screen of number Korean English and symbol with using the 3 2 2 Number Korean English sign Input Program operation setting 3 2 3 Number Input Mode Delete all the current texts entered Delete one letter ahead of the current cursor Save the text indicated up to the current cursor into the internal ...

Page 22: ... on the Fig 5 All the keys except the keys consist of duplicate keys There is also an additional function key The principle of using function keys is the same in every mode If you want to enter double consonants such as ㄲ ㄸ ㅃ ㅆ ㅉ you should press the consonant three times You should press the key if you go to the next letter while entering letters Or you can also use such key when entering the bla...

Page 23: ...eration Result 의 _ The _ on the bottom indicates a flickering cursor Ex If you want to indicate 각 Operation Result 각 _ The _ on the bottom indicates a flickering cursor Ex If you want to indicate 한영넉스 Operation Result 한영넉스 _ The _ on the bottom indicates a flickering cursor Ex If you want to indicate 대한민국 Operation Result 대한민국 _ The _ on the bottom indicates a flickering cursor th300_500_통합본_th300...

Page 24: ...ne second Result 1 2 X 3 9 _ The _ on the bottom indicates a flickering cursor 25 3 2 5 English Input Mode Fig 7 The screen for sign input 3 2 6 Sign Input Mode The screen for English input is shown on the Fig 6 All the keys except the and keys consist of duplicate keys Its basic use is the same as that of the Korean input mode Fig 6 The screen for English input The screen for sign input is shown ...

Page 25: ...rent temperature PV Control output BAR for current humidity MV Current humidity PV Temperature PID Zone No input box Humidity PID Zone No input box Current date time Temperature PV Up Down indication Temperature SV input box Humidity PV Up Down indication Humidity SV input box Running time indication Temperature A T button Humidity A T button Start button for Fix Running Stop button for Fix Runnin...

Page 26: ...hift button Running Stop indication Control output BAR for current temperature MV Current temperature PV Control output BAR for current humidity MV Current humidity PV Operation pattern name Current date time Temperature SV Up Down indication Start pattern No input box When operation stops it either display the pattern number or used as input unit Humidity SV Up Down indication Start segment No in...

Page 27: ...e TSV Currenthumiditycontroloutputamount MV Temperature humidity up down interval indication Temperature humidity maintain indication Temperature humidity standby Wait indication Total operation time Run time Pattern number segment number indication Pattern repetition indication Number of sequence Number of repetition setting Segment repetition indication Number of sequence Number of repetition se...

Page 28: ...xis X axis time Div Low part screen of Y axis Current temperature PV indication Current temperature MV SV indicator shift button Current temperature MV or SV indication Current humidity PV indication Current humidity MV or SV indication Current humidity MV SV indicator shift button Y axis temperature humidity unit shift button Y axis unit indication Graph Save setting button Screen ZOOM IN Screen ...

Page 29: ...g the button will select the fix control Set each of setting lists in the operation setting screen 2 by pressing the button While performing the fix control changing the set value SV will automatically change the PID ZONE applying number in accordance with the set value If users want to use the specific PID zone please input the PID zone number after inputting the set value During operation if and...

Page 30: ...will be displayed Press button and Auto Tuning will be shown on A T button indication in the Sensor Input Setup 4 Temperature Auto Tuning button Turn on and off during running Humidity Auto Tuning button Turn on and off during running When it comes to temperature its PV will be always displayed unless the sensor line is disconnected However as far as humidity is concerned its PV will not be indica...

Page 31: ... again for 40 min and maintain the 70 for 1 hour Program control is especially using widely in the test equipment for environment like as thermostat and electric furnace 3 5 Running of Program control TH500 TH300 Fig 16 Running stopped screen 1 for program control In order to running with program control press the button of the top on the running stopped screen 1 for program control Fig 16 and mov...

Page 32: ...Screen Fig 19 Pattern Set Screen Fig 20 Running stopped screen 1 for program control Fig 21 Running screen 1 for program control Press the button in the program set screen Fig 18 and move to the screen for program pattern set Fig 19 Establish the set item for each segment of pattern in the screen for program pattern set Fig 19 Move to the running stopped screen 1 for program control after input fo...

Page 33: ...de the resulted PID value will be saved into the appropriate PID ZONE If this unit is set to manual PID ZONE reference mode the results PID value will be saved into your designated PID ZONE 34 PID auto tuning interval AT end AT start ON OFF operation PID Control interval Fig 22 PID Auto Tuning Button Pressing the button while it is operating will keep the set value set value which had been set rig...

Page 34: ... program control graph display Fig 25 Graph set screen Graph s display screen is a screen to display the setting value and measured value of temperature and humidity In the graph setting screen X axis s time and Y axis s maximum and minimum range can be set up by pushing each of buttons and set up saving operation status by selecting save period seconds and storing medium In the Y axis s display r...

Page 35: ... of errors through sensor disconnection and external D I is displayed with button on and off in the running screen 2 for program control Fig 26 If you press the button the error occurrence screen will appear In this case the error indicator for temperature humidity disconnection will appear while D I External contact input no 1 to 8 will be displayed on the bottom You can check it by pressing the ...

Page 36: ...g display 4 1 Operating screen 4 Displays Fig 30 Fixed control the 1st working screen Fig 31 Program control the 2nd working screen Fig 32 Fixed control the 2nd working screen Fig 33 Program control Graph screen Fig 34 Fixed control Graph screen Entire displays are mainly composed of three sections which are Working display Function setting display included In program installation and System setti...

Page 37: ...the 1st stop screen Fig 36 Function setting menu screen 4 3 System Setting screen As pushing button in Working display condition Function setting menu screen is shown Pushing the character of Function setting in that time Password input display is shown Pushing after inputting initial value 0 the display of System setting function menu shows It is composed of 8 buttons th300_500_통합본_th300_500_통합본 ...

Page 38: ...ting menu screen There is no need for System setting made separately by driver Because the Basic setting condition of this system s model is set up by the operator you should be careful especially th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 34 페이지 39 ...

Page 39: ...e 1st working stop screen is displayed TH500 TH300 Running Screen will be displayed Function setting menu botton Function setting menu botton Information Information Running Operation Setting screen will be displayed Program Setting Pattern Time Signal setting etc screen will be displayed Enter into Graph screen Enter into axis X Y and storage screen Enter into Date Time Reservation Setting screen...

Page 40: ... Fixed control in selecting Working method 5 1 Operation setting 5 1 1 Function setup 1 Fig 41 Function setup 1 screen RUN MODE T SV RATE H SV RATE Fix RUN TIME ZN TRACKING PROGRAM FIX RUN Select in program control Select in fixed control Set it up as the gradient of temperature variations m per hour minute from current temperature to setting temperature in fixed control Set it up as the gradient ...

Page 41: ...check various input and operation It is used to limit the touch panel input during system control operating Selecting Lock it is impossible to input except and buttons As it is the function to turn off the power of Back Light after the setting time in order to protect the LCD display it can set up Setting time as a unit per a minute Setting 0 when it is not used it is turning on all the time STOP ...

Page 42: ...pattern in this screen Program control will process according to the content sequence of segment designed 5 2 1 Pattern setting Fig 46 Program pattern setup screen Fig 47 Segment selection screen Fig 44 Function setting menu screen TH500 TH300 Fig 45 Program setup menu screen th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 34 페이지 43 ...

Page 43: ... button on the Program Pattern Setting screen Fig 49 or Time Signal number on the Program Pattern Setting 2 screen Fig 50 Time Signal Setting screen Fig 51 will be displayed 5 2 2 Time Signal Setting Name PTN NO SEG Page TEMP SV HUMI SV Hour Min Wait T S Time Signal ALARM Function Enter the pattern number to set or select it by pressing the button Pressing the button it moves each 4 segment Pressi...

Page 44: ...ent is operating Set the Time Signal in ON after setting time is delayed from the beginning of segment Set the Time Signal in ON during setting time from segment in ON Setting Range Each segment 99 hour 59 min 99 hour 59 min Function Time signal segment ON OFF setting method Fig 53 shows an example of using the T S in ON OFF mode It performs turning on and off the T S in the desired segment with t...

Page 45: ...under 25 soak status SEG 6 ON under 75 soak status SEG 1 and SEG 5 ON under Up section SEG 3 ON under Down section SEG 1 to SEG 3 ON SEG 4 to SEG 6 ON SEG 1 to SEG 6 ON under program control running Start program operation Finish program operation T Example of Setting the Time Signal in TIME Setting mode Fig 54 Example of Setting the Time Signal in TIME Operation mode th300_500_통합본_th300_500_통합본 q...

Page 46: ...4 hours it will become OFF ON Delay 00 h 00 m ON Time 04 h 00 m Time signal becomes ON in each of segment 2 4 and 6 and after elapsing ON time it will become OFF Time Signal will be OFF once the program ends regardless of setting modes Pressing button in Fig 44 Function Setting menu screen and pressing button in Fig 45 Pattern REPEAT LINK setup Fig 55 is shown If you set Current Pattern repeat cou...

Page 47: ...etition number Set the partial repeating end segment number Setting 0 will run the next partial repetition number Set the number of current partial repetition Setting 0 will run the next partial repetition number Range 1 100 Pattern 1 999 Time 0 100 Pattern 1 20 Number 0 100 SEG 0 100 SEG 0 255 Time 48 The Segment operation sequence by Section repeat setting If segment in pattern is set from to it...

Page 48: ...aiting operation can be set by each segment of proper pattern In case that Waiting operation of process value PV comes or fails to come within Waiting range of Set value SV wait process of segment during setting Waiting operation time and then go to next segment Only if Waiting operation is set to 0 Waiting operation will not work Fig 56 Pattern WAIT setup screen 5 2 4 Waiting Alarm start mode set...

Page 49: ...n order to cancel the standby operation Range 1 100 Pattern 0 300 TH500 0 600 TH300 0 100 0 99 hour 59 minute Waiting time Waiting Range Standby operation becomes cancelled because PV falls within the standby range S b t s d b Standby operation starts to on because PV did not fall within the standby range S w Start Waiting Operation SEGprogresswithout applyingstandbymode SEGprogresswith applyingst...

Page 50: ...alarm setup screen 5 2 5 Pattern Alarm Setting b Start the standby operation because PV did not fall within the set standby range Cancel the standby operation even though PV did not fall within the set standby range because standby time is elapsed w Standby operation starts to on because PV did not fall within the standby range S O Set standby time standby range Standby operation S a a SEGprogress...

Page 51: ... FIG 60 screen then set alarm code will be cancelled Code 1 2 3 4 5 6 7 8 9 10 Code 11 12 13 14 15 16 17 18 19 20 Alarm Type Upper limit absolute Tangent Hold Lower limit absolute Tangent Hold Upper limit deviation Tangent Hold Lower limit deviation Tangent Hold Upper limit deviation Reciprocal Hold Lower limit deviation Reciprocal Hold Upper lower limit deviation Hold Within the range of upper lo...

Page 52: ... button again In this display it will be shown to Fig 61 S PV Working start setting display 5 2 6 Pattern start mode setting Fig 62 S SV Operation start setting display Fig 61 S PV Operaiton start setting display Name PTN NO T S SV H S SV START MODE S SV S PV Function Enter the pattern number to set or select it by pressing the button Start the operation based on the SV set in the temperature humi...

Page 53: ...py and segment initializing In the left side you should enter the source pattern or segment number used for pattern management In the right side you should enter the target pattern number of segment number to be copied After entering a desired value you can copy it by pressing button in arrow button on the left center is used for initializing all the internal segments of the pattern entered into t...

Page 54: ...ing screen Fig 69 Fixed control the 1st working stop screen 5 3 Date Time Reservation Setting Keep in mind that it is impossible to recover the original contents of the target after copying the pattern segment Once you press the button the original contents of the source cannot be recovered again After copying pattern by using button you should make sure that the related parameter is proper settin...

Page 55: ... Fig 71 Graph view screen Table 3 Time per X axis DIV 1 2 3 4 5 6 7 8 9 10 11 12 13 14 00M 20S 01M 00S 02M 00S 03M 00S 04M 00S 05M 00S 06M 00S 07M 00S 08M 00S 09M 00S 10M 00S 20M 00S 00H 30M 00H 40M Entire Screen Time 00H 03M 20S 00H 10M 00S 00H 20M 00S 00H 30M 00S 00H 40M 00S 00H 50M 00S 01H 00M 00S 01H 10M 00S 01H 20M 00S 01H 30M 00S 01H 40M 00S 03H 20M 00S 05H 00M 06H 40M 15 16 17 18 19 20 21 2...

Page 56: ...ntrolling only Fix Program Save during fixed mode controlling only save during program mode controlling only Delete Initialize Saved Contents in internal memory Do not use USB MEMORY STICK Record on USB MEMORY STICK table 4 Selection of storage condition Data transmission by USB connector As far as the saving operations are concerned the total 86 400 pieces of information on temperature humidity Y...

Page 57: ...aph Viewer program presented 58 Fig 72 USB Uploader Utility If you turn off all contents will be deleted because the value of saved measurement control is saved in Volatile Memory SDRAM When you connect USB you must use USB A B connector cable The USB Plug Play function of some PCs may have errors upon PC booting Therefore it is necessary to connect USB connector after PC booting After PC booting ...

Page 58: ...mperature sensor setting screen Fig 76 The contents of Humidity sensor setting screen Fig 77 is the same as temperature sensor setting But if you select sensor type as Temperature only display Fig 78 will be set up 6 1 Sensor type setting 59 6 System Setting Fig 74 Function setting menu screen Fig 75 System setup menu screen If you push on operation screen function setting menu screen will be disp...

Page 59: ...the sensor type as d c voltage for humidity sensor related setting because output for humidity sensor is 4 20 mA But in case of current output sensor please connect the resistance less than 250 Ω 1 on the external input terminal in parallel Lastly please select OFF for the humidity sensor type when using as the temperature only mode 2 Input range Regarding sensor input range you can use initial va...

Page 60: ...easured temperature 70 10 compensation of measured temperature is necessary This time please touch 80 and enter 70 in the number plate After touching compensation is finished Fig 79 Temperature Bias Fig 80 Humidity Bias 61 100 200 and humidity value is 0 100 R H If you use electronic humidity sensor Model EE99 please set up input range to V d c and contact resistance 250 1 below to the both of inp...

Page 61: ...ntrol output will be OFF Displays Dry bulb temperature Displays Wet bulb temperature Gauze have to be removed Displays relative humidity RH Press and it shows the temperature difference between dir bulb and web bulb It very important to correct Dry Web bulb because relative humidity measurement is based on the temperature difference between two sensors If you push setting correction will be starte...

Page 62: ... 2 1 Control output setting 1 Temperature output type Output period of SSR Output direction Reverse Forward Output range could be set up on the Control Output Setting 1 Fig 83 T SV range H SV range Temp Res Burnout wait time A T Button In order to prevent mistake of user mistake the Temperature SV range can be restrictive as much as wanted range In order to prevent mistake of user mistake the humi...

Page 63: ...ut period of SSR Output direction Reverse Forward Output range could be set up on the Conntrol Output Setting 2 Fig 84 TH500 TH300 Fig 83 Control output setting 1 TH500 TH300 Fig 84 Control output setting 2 th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 35 페이지 64 ...

Page 64: ... Out direct T Out range Select and use S S R or S C R 4 20 d c Select according to the equipment Initial value S S R You can set up when you select S S R output Output cycle means On Off working time in the proportional band Initial Value 1 seconds Select cooling control direct movement or heating control inverse movement Initial Value Inverse movement You can control output and selection range 5 ...

Page 65: ... If output value is different compared to the standard output 50 0 please touch button after setting standard output as 50 0 In this case output signal which is corresponded to 50 0 will be generated Please measure this value after inputting this value on the measured output setting screen please remove button between 0 0 d c and 4 0 d c The contents of Control Output Setting screen 3 Control Outp...

Page 66: ...utput through retransmission output Initialize bias values Contents Button 6 4 1 Inner Signal setup Time Signal is related with segment and Time but Inner Signal is used for signal output of temperature and humidity So Inner Signal is not related with segment section 6 4 Inner Signal and Alarm setting Fig 91 Inner signal setup th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 35 페이지 67 ...

Page 67: ...YS Fig 92 Example of Inner Signal setting NSV temp Time temp Time temp Temp Time Time S Relay or O C Output Relay or O C Output Relay or O C Output I S1 Temperature PV2 operation setting Operation range 50 10 setting Direction of range HYS I S2 Temperature PV2 operation setting Operation range 50 10 setting Direction of range HYS Fig 93 Example of Inner Signal setting TSV Setting item I S Number I...

Page 68: ... Signal setting PV2 Low temperature High temperature A Zone B Zone C Zone D Zone Fig 97 Section of T ON OFF zone 6 4 2 T ON OFF Signal When pressing in the System setting menu screen Inner signal setting screen will be shown up If you press button T ON OFF signal setting screen Fig 96 will be shown up This screen is a zone setting screen based on temperature and humidity setting values Each output...

Page 69: ...nd then set alarm value and Hysteresis 70 Same as Fig 97 range is divided by four zones A B C D by means of L SV M SV H SV Its setting condition is L SV M SV H SV Description Zone A zone PV H SV B zone M SV PV H SV C zone L SV PV M SV D zone PV L SV Always OFF regardless of bias deviation 1 Hd 0 Always OFF regardless of bias 2 Hd 0 Refer to Fig 98 OFF PV SV Hd ON PV SV Hd 1 Lu 0 Always OFF regardl...

Page 70: ...he total 16 PID ZONEs As shown in the chart below the four temperature zones and four humidity zones are combined with each other so you can control the temperature and humidity with the optimized PID value You are free to change the zone boundary of temperature and humidity Humi Zone Temp Zone 0 Humi SV HZ1 HZ1 Humi SV HZ2 HZ2 Humi SV HZ3 HZ3 Humi SV HZ4 100 Temp SV TZ1 Zone 1 Zone 5 Zone 9 Zone ...

Page 71: ...ue of Moving Temp Humi in P I D setting screen Fig 103 by pushing Zone button wanted in the Fig 102 However it is not possible to set HYS Hysteresis setting screen cause it is not activated as a grey color In order to set it set P value as 0 In this case it s possible to set it because ON OFF control is selected when set P value as 0 If you want to use ON OFF control only set P I D zone number as ...

Page 72: ...ge is wide Offset gets larger offset Time Proportional control Proportional Integration P 1 control offset Time Time Integration time is short Integration time is long FIG 108 Proportional Integration P I control Set up proportional band When proportional band is wide the time to reach to setting value is slow because of small quantity of control output regarding the Offset When proportional band ...

Page 73: ...e same time it ignores STEP input and it handles HOLD input only Regardless of control action Running or Stop external D I is always displayed and handled internally according to its input status D I Digital Input is consisted of 3 screens TH500 has 8 points of D I and TH300 has 4 point of D I Active Low Function Start or end the assigned D I input signal according to the operation mode H L set In...

Page 74: ...When selecting Waiting Delay time system will be finished after passing waiting delay time 75 TH500 TH300 Fig 111 D I Setting 3 Fig 110 D I Setting 2 6 6 2 D I Setting 2 It is possible for user to use each D I name or Error name directly by using the combination of KOR ENG NUM SIGN When touching D I name screen mark number input keypad will be shown up By using keyboard change button set the name ...

Page 75: ...ssigned and connected are displayed through the actual terminal The D O assignment is allowed to be redundant except special cases so it is necessary to assign and enter the RELAY and O C carefully When outputboard 3 is used in TH500 Relay13 Relay20 can be assigned through O C1 O C8 Example if Relay15 is desired to be used please set O C3 for Relay15 6 7 D O Configuration Setting Setting item FIG ...

Page 76: ... means of temperature and humidity setting values Each output according to setting condition could be set and used in the D O Configuration Setting 3 screen It will be ON after passing setting time and setting time is applied only to the first ON time 6 7 4 D O Configuration Setting 4 Setting 5 FIG 114 D O Configuration Setting 3 6 7 2 D O Configuration Setting 2 Output assignment against Time Sig...

Page 77: ...collector output FIG 117 D O Configuration Setting 6 Explanation In case of D I input its output becomes ON for a setting time IF RUN STOP STEP and HOLD function input is set its D I will be not included Once program control ends its output becomes ON for a setting time After doing output of I S Inner Signal 1 its output becomes ON after delaying for a setting time After doing output of I S Inner ...

Page 78: ...or O C Output ure PV2 operation setting ge 50 10 setting on of range HYS re PV2 operation setting e 50 10 setting n of range HYS Fig 119 Output by temperature UP HOLD DOWN setting D O Configuration setting 7 FIG 118 is used when turning ON the output within the increase maintain decrease interval of each of temperature humidity set value SV Each set input value of setting lists operates same as FI...

Page 79: ...tion by connecting 4 lines you can use 2 lines by connecting RX with TX doing RX with TX Function Select the communication protocol PCLINK operates by following the format which is assigned by Hanyoung Nux and MODBUS RTU operates by following the standard format Set the communication speed BPS You can select TH500 one out of 9600 19200 38400 57600 115200 TH300 one out of 9600 19200 38400 Set the p...

Page 80: ...rean on one line Name Language Password User information 6 9 1 ETC Setup 1 Function When selecting T PV HOLD It holds a minute temperature hunting When selecting H PV HOLD It holds a minute humidity hunting Control by R H Control by humidity of wet bulb It prevents excessive status and it has a rapid safety Standard control by inner setting Set a available operation date of this equipment Setting ...

Page 81: ...00 set up scaling setting as 0 100 When touching in the Fig 124 Fig 125 Fig 79 Fig 80 will be displayed Low Pass Filter selects suitable time when processed value is chattering due to inflowing of noise through input sensor line 82 FIG 124 Sensor Input Setting 1 FIG 125 Sensor Input Setting 2 7 1 Input related setting 7 Simple Example HANYOUNG NUX is Temperature Humidity Controller Model TH500 300...

Page 82: ... correction Setting item Humi C RNG Dry Temp Wet Temp Rel Humidity D W Adjust Adjust Mode ADJ INIT 7 1 3 Range Setting In order to prevent mistake of user input setting Input temp range when restricting temp SV within its desired range In order to prevent mistake of user input setting Input humidity range when restricting humidity SV within its desired range Select Temp process value and SV as 0 0...

Page 83: ... heating control Reverse operation Initial value Reverse operation Output could be controlled and its range is 5 00 3 2 105 00 20 8 Initial value 0 00 100 00 S S R or S C R 4 20 could be used as a control output Initial value S S R Control output is S S R only T Out type T SSR Out period T Out direct T Out range Fig 130 Humidity Retransmission Output Setting TH500 TH300 7 2 2 Retransmission Output...

Page 84: ...Setting item T Source T Range Out Adjust S Burnout output FIG 131 Inner Signal Set FIG 132 D O Output setup1 When controlling refrigerator and dehumidifier separately by external switch it can be used generally with input output setting only But in case it needs to control On Off refrigerator dehumidifier under desired temperature and humidity it s convenient to use Inner Signal Please refer to th...

Page 85: ... Range 100 30 Subject humidity Range 0 70 Subject Temperature Range 100 50 1 minute 10 seconds 5 seconds Connect 1st refrigerator to 5th Relay Connect dehumidifier to 6th Relay Connect 2nd refrigerator to 7th Relay Signal Subject Signal Type Range Delayed Time Output Allocation D O You have to select temperature range of refrigerator according to its specification If you set up too high temperatur...

Page 86: ...ation screen 87 7 4 3 Operate and STOP of Fix Control FIG 135 Fix control 1st operation stop FIG 136 Fix control 1st operation Press temp humidity setting and set up desired setting value After set up number please press button in order to finish setting finally and it will be back to the 1st Operation Stop Screen of Fix Control Fig 135 FIG 134 Function setup 1 7 4 2 Temperature Humidity Control V...

Page 87: ...l be better to perform Auto Tuning in order to get good control performance To start Auto Tuning press Auto Tuning button at the bottom of picture Fig 136 When T AT button flickering it shows that Auto Tuning is being performed After Auto Tuning finished Auto Tuning values will be set up automatically and it stops flickering Same as temperature Auto Tuning perform auto tuning of humidity by pressi...

Page 88: ...ation of Program Pattern Setting Screen FIG 139 Program pattern setting Explanation Input pattern no directly or select it by using button Press Segment Page Shifting button and it moves to 4 segment per each shifting Press setting screen and set up setting value of temperature of the segment Press setting screen and set up setting value of humidity of the segment Set up operation time of the segm...

Page 89: ...gment setting unit within pattern of program control operation stop FIG 141 screen and press the button then program control operation will be started In order to stop the program control operation press the button on the right bottom of the program control operation FIG 142 screen then program control operation will be stopped When operating the program control the displaying screen will be same ...

Page 90: ...A 250 V a c 5 A N C 30 V d c 1 A 250 V a c 2 A 8 points 2 COM 4 points 1 COM 24 V d c 300 max Open Collector 8 points 1a 8 points 2 COM S C R is not available TH500 TH500 Model Model TH300 TH300 8 1 Input 8 2 Output 8 Specification Input Measurable range Accuracy Contact Input D I R T D VDC Sampling cycle Temperature Humidity Temperature Humidity R T D Resistance Temperature Detector Pt100Ω IEC 75...

Page 91: ... m approx within 1 2 km approx 1 M bps 9600 19200 38400 57600 115200 bps 7 8 bits NONE EVEN ODD 1 2 bit s Bulk Mode PCLINK PCLINK CRC MODBUS RTU 0 999 ms Power supply voltage Frequency Power consumption Insulation Resistance Dielectric Strength External power supply 24V d c 18 W max I O Board 100 240 V a c Change rate of voltage 10 50 60 Hz 20 VA max 10 VA max More than 500 V d c 10 Power supply t...

Page 92: ...0 segments 6 000 max segments 2 000 max segments 16 Groups Temp 4 zones x Humidity 4 zones Auto Tuning according to SV Setting Value Temp 0 00 600 00 Humidity 0 00 200 00 0 00 ON OFF control 0 0 6 000 sec 0 sec OFF 0 0 6 000 sec 0 sec OFF Set the Proportional Band as 0 0 Select Direct or Reverse action in control output 0 1 300 0 1 600 0 In case of humidity it is a web bulb temperature or converte...

Page 93: ...le English Chinese Traditional 8 6 Touch LCD Model TH500 TH300 Usable surrounding temperature Usable surrounding humidity Storage Temperature Vibration Shock Dimension Weight 0 50 20 90 R H No condensation 25 70 10 55 Hz amplitude 0 75 3 directions 4 times 5 min cycle 147 3 directions 3 times 183 W X 144 H 96 W X 96 H Approx 2 35 Kg Including packing materials Approx 0 85 Kg Including packing mate...

Page 94: ...pecification 24 V d c 500 Asynchronous Serial Communication RS232C max 38400 bps max 5 m Operate the front switch Memory stick USB MERORY STICK FAT16 32 32 Mb Nonvolatile USB POWER ACT DUMP CLEAR The place where insert USB Stick Red LED for displaying power supply Green LED for displaying data storage Flickering in case of recording Copy button When touching DUMP button data on inner memory will b...

Page 95: ...96 9 3 Dimension and Panel Cutout 9 4 Connection Diagram POWER 24 V d c RX TX EM310 TH500 S G RX TX S G 1 5 6 2 3 th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 36 페이지 96 ...

Page 96: ...th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 36 페이지 97 ...

Page 97: ...th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 36 페이지 98 ...

Page 98: ...th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 36 페이지 99 ...

Page 99: ...0801E180411 HEAD OFFICE 28 Gilpa ro 71beon gil Nam gu Incheon Korea TEL 82 32 876 4697 FAX 82 32 876 4696 http www hynux com E mail overseas hynux com th300_500_통합본_th300_500_통합본 qxp 19 6 26 오후 1 32 페이지 1 ...

Reviews: