HAMWORTHY HEATING LTD
36
SHAFTESBURY HE
500001049/N
BOILER MODEL - SHAFTESBURY HE
110
150
190
220
250
280
310
340
370
400
GENERAL DATA
No. OF SECTIONS
5
6
7
8
9
10
11
12
13
14
BOILER INPUT - maximum
kW
125.5 171.2 216.3 250.5 284.7 309.9 343.2 377.9 404.2
430
(nett) 34.06 MJ/m
3
Btu/hr x 1000
428.2 584.1
738
854.7 971.4 1057 1171 1289 1379 1467
BOILER INPUT - maximum
kW
139.37 190.1 240.2 278.2 316.7 344.0 380.9 419.4 448.6 477.2
(gross) 37.8 MJ/m
3
Btu/hr x 1000
475.5 648.6 819.5 949.2 1080.6 1174 1300 1431 1531 1628
BOILER OUTPUT - maximum
kW
110
150
190
220
250
280
310
340
370
400
Btu/hr x 1000
375
511
648
751
853
955
1058 1160 1262 1365
FLUE DATA
NOMINAL FLUE DIA.
mm
180
in
7
FLUE DRAUGHT REQUIRED
mbar
0.1 - 0.3
AT BOILER OUTLET
in.wg.
0.04 - 0.12
COMBUSTION CHAMBER
mbar
2.8
5.0
4.4
5.9
5.9
3.9
4.6
5.5
6.5
7.4
RESISTANCE (maximum)
in.wg.
1.1
1.96
1.73
2.32
2.32
1.54
1.81
2.17
2.56
2.91
APPROX. FLUE GAS TEMP(gross)
°C
225
APPROX. FLUE GAS VOLUME
m
3
/h
174
236
254
294
335
383
424
467
500
532
@ NTP (wet)
ft
3
/h
6144 8333 8938 10381 11828 13532 14986 16501 17650 18776
GAS DATA
NOMINAL GAS INLET PRESSURE
mbar
20
MAXIMUM GAS INLET PRESSURE
mbar
25
GAS FLOW RATE
m
3
/h
13.3
18.2
22.9
26.5
30.1
32.8
36.3
39.9
42.7
45.4
ft
3
/h
469.5
642.5 808.4 935.5 1062 1157 1281 1410 1509 1605
GAS INLET CONNECTION
Rc 1 ½
WATER DATA
WATER CONNECTIONS - FLOW &
RETURN
4 in N.B.
MAXIMUM WATER
bar g.
5.0
PRESSURE
psi g
73.0
WATER CONTENT
litres
78
92
106
120
134
148
162
176
190
204
UK gal.
17.2
20.3
23.3
26.4
29.5
32.6
35.7
38.8
41.9
44.9
WEIGHT (FULL)
kg
508
592
676
755
834
923
1012 1106 1200 1274
WITHOUT BURNER
lb
1118 1302 1487 1661 1835 2031 2226 2433 2640 2803
230V 1ph ~ 50Hz
ELECTRICAL SUPPLY
Figure 16.4 – Performance and General Data Information (Natural Gas)
Note:
For matched burner/boiler combinations, refer to Figures 11.1, 11.2 & 11.3
For combustion target figures, refer to Figure 11.5
For data relating to Propane and Oil refer to Appendices A & B.
DESIGN FLOW RATE
(11 ° C.
∆
T)
MINIMUM FLOW RATE
(20 ° C.
∆
T)
FLOW RATE
PRESS. DROP
FLOW RATE
PRESS. DROP
l/min
UK gal/min
mbar
in. wg
l/min
UK gal/min
mbar
in. wg
HE110
158.5
34.8
3.5
1.4
80
17.6
1.0
0.4
HE150
206.7
45.4
6.5
2.6
108
23.8
1.8
0.7
HE190
247.6
54.5
8.5
3.3
136.2
30.0
2.9
1.1
HE220
286.7
63.1
11.5
4.5
157.7
34.7
3.7
1.5
HE250
325.7
71.7
13.0
5.1
179.1
39.5
4.2
1.6
HE280
357.5
78.6
16.5
6.6
196.3
43.2
5.0
2.0
HE310
397.0
87.3
18.5
7.4
218.3
48.0
5.6
2.3
HE340
435.0
95.7
21.0
8.4
240.0
52.8
6.4
2.6
HE370
475.6
104.6
23.5
9.5
262.0
57.7
7.1
2.9
HE400
514.9
113.3
26.0
10.5
283.3
62.4
7.9
3.2
BOILER
MODEL
Shaftesbury
Figure 3.1 - Water Flow Rates and Pressure Drops