HAMWORTHY HEATING LTD
11
SHAFTESBURY HE
500001049/N
Shaftesbury
HE110
R
I
I
I
F
HE150
R
I
I
I
I
F
HE190
R
I
I
I
I
FI
F
HE220
R
RI
I
I
I
I
FI
F
HE250
R
RI
I
I
I
I
I
FI
F
HE280
R
RI
I
I
I
I
I
FI
FI
F
HE310
R
RI
RI
I
I
I
I
I
FI
FI
F
HE340
R
RI
RI
I
I
I
I
I
I
FI
FI
F
HE370
R
RI
RI
I
I
I
I
I
I
FI
FI
FI
F
HE400
R
RI
RI
RI
I
I
I
I
I
I
FI
FI
FI
F
Section No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Section Type
R - REAR SECTION
RI - REAR INTERMEDIATE SECTION
I - INTERMEDIATE SECTION FI - FRONT INTERMEDIATE SECTION
Figure 10.1 – Composition of Sections within Heat Exchanger
10.0 BOILER
ASSEMBLY
The following procedure should be adopted for the
initial site build of the boiler or following any disman-
tling due to maintenance.
10.1 Boiler
Sections
The heat exchanger is made up from five different
types of section, each plain section weighing around
70 kg (140kg for assembled front and rear), as fol-
lows:-
a.
One complete front section (assembled with
access doors etc.)
b.
One complete rear section (assembled with
access doors etc.)
c.
A number of plain intermediate sections which
are converted to the correct number of front, rear
and central intermediate sections by the addition of
flue plates.
Prior to building the boiler the flue plates and their
retaining nuts and bolts should be located and iden-
tified in the accessory kit
. Reference MUST be
made to Figures 10.1 & 10.2 .
Having determined
the size of boiler to be built the numbers of each of
the three sections required (RI, I and FI) can be
read from Figure 10.1. The correct number of each
section
MUST
then be made up by inserting the flue
plates and locking nuts into position with nuts and
bolts. The plates
MUST
be inserted into the sec-
tions in the slots provided and the number and posi-
tion of the plates
MUST
be in accordance with the
detail shown in Figure 10.2.
For the purposes of identification, the intermediate
sections (I) have SIX flue plates fitted into the flue-
ways. The front intermediate section (FI) has TWO
plates fitted across the centreline of the flueways
and the Rear Intermediate section has FOUR plates
fitted at 45
o
around the flueways.
NOTE:
The as-
sembled front and rear castings of the boiler are
already fitted with flue plates.
When fully assembled, the flue gas flow path
through one half of the boiler is as illustrated in Fig.
10.10.
IT IS MOST IMPORTANT THAT THE BOILER IS
BUILT WITH THE CORRECT NUMBER AND
TYPE OF INTERMEDIATE SECTIONS IN THE
CORRECT ORDER.
10.2 Preparation
Place boiler sections in boiler room, adjacent to pro-
posed site for boiler, in order of build to allow quick
and easy handling and assembly.
Clean both upper and lower ports on each section.
Thoroughly clean the machined joint faces on both
sides of each section to leave a smooth, clean,
paint-free finish.
Open fittings crate and remove lacing bolts, sealing
mastic, guide rings, and 'O'-ring sealing gaskets.
N.B.
Ensure these gaskets are kept dry and free
from dirt, grit, oil and grease.
Position the steel cradle on the level surface
prepared for the boiler. Refer to Section 4 - Boiler
Location.
10.3 Assembly
of
Sections
Assemble the sections as follows, referring to Fig-
ures 10.3 - 10.10 and Figure 15.1.