![Halytech HYDROSPIDER2 User Manual Download Page 102](http://html1.mh-extra.com/html/halytech/hydrospider2/hydrospider2_user-manual_3381833102.webp)
Halytech
hydroSpider2 User’s Manual v1.23
Page 98
Appendix E.
LiveSMS (Software Option)
LiveSMS functionality is available as a software option for the hydroSpider2.
It allows the hydroSpider to receive, reply and act on SMS messages in real time, and to remotely
access the unit via a web browser. This allows the user to instantly change settings, request reports,
get system information at any time, and acknowledge alarms.
LiveSMS is configured in the
Change Advanced Settings
page, which is reached by clicking the
“Advanced” link in the
Change Setup
page.
LiveSMS will cause the hydroSpider to consume a lot more power as the modem may be left on for
long periods of time.
The following
Type
options are available:
Always: the modem is on at all times
Sc Alarms: the modem is on at selected times, and when waiting for SMS alarm
acknowledgement.
Alarms Only: the modem is only left on when waiting for SMS alarm acknowledgement.
Note: If LiveSMS is set to Always, SMS Recovery (see 5.7.5 - SMS Recovery) will no longer be
available as it is unnecessary.
SMS Messages which may be sent/received if LiveSMS is enabled:
Command Comment
Example
HELP
Request list of supported commands
HELP
GET ST
Get current state of all inputs (System Channels Included)
GET ST
GET CN
Get current state of all controls
GET CN
GET AL
Get current state of all alarms
GET AL
ACK ALx
Acknowledge Alarm x (x is 1 - 8)
ACK AL6
ACK ALL
Acknowledge All Alarms
ACK ALL
ON CNx
Activate Control x (x is 1 = Switched Power, 2 = Open Collector)
(no PIN)
ON CN2
yyyy ON
CNx
Activate Control x (x is 1 = Switched Power, 2 = Open Collector)
(PIN = yyyy)
1234 ON CN2
OFF CNx
Deactivate Control x (x is 1 = Switched Power, 2 = Open
Collector) (no PIN)
OFF CN2
yyyy OFF
CNx
Deactivate Control x (x is 1 = Switched Power, 2 = Open
Collector) (PIN = yyyy)
1234 OFF CN2
PULSE CNx
Pulse Control x for 1 second (x is 1 = Switched Power, 2 = Open
Collector) (no PIN)
PULSE CN2
yyyy PULSE
CNx
Pulse Control x for 1 second (x is 1 = Switched Power, 2 = Open
Collector) (PIN = yyyy)
1234 PULSE CN2
GET REP
Request Current Day’s Report (sends out via FTP/Email using
normal report settings)
GET REP