Instruction Manual PSE2xxDN
18
f) Assigning mapping I/O assemblies to available I/O connections
The PSE2xxDN allows the user to change how mapping I/O assemblies are assigned
to available I/O connections. The current settings for each type of I/O connection are
recorded in the connection object (class ID 5), instance 0, attr. 100-104. The following
provides possible settings and default values:
Name
Attr.
No.
Function
Range of
values
Back
up?
Delivery
state
R/W
select
input_poll
100
assembly instance that the device uses
when establishing a poll connection for
sending messages to the master (i.e., for
a poll response message)
100, 101
8 bit
no
100
R/W
select
output_poll
101
assembly instance that the device uses
when establishing a poll connection for
receiving messages from the master (i.e.,
for a poll command message)
103
8 bit
no
103
R/W
select
input_bit
strobe
102
assembly instance that the device uses
when establishing a bit-strobe connection
for sending messages to the master (i.e.,
for a bit-strobe response message)
101
8 bit
no
101
R/W
select
output_bit
strobe
103
assembly instance that the device uses
when establishing a bit-strobe connection
for receiving messages from the master
(i.e., for a bit-strobe command message)
104
8 bit
no
104
R/W
select
input_COS
104
assembly instance that the device uses
when establishing a change-of-
state/cyclic connection for sending
messages to the master
100, 101
8 bit
no
100
R/W
g) Identifiers used for available I/O connections
The identifiers used for available I/O connections can be determined from the
predefined master/slave connection set:
Bits for identifier
Meaning
10 9 8 7 6 5 4 3 2 1 0
1
0
slave MAC ID
1 0 1 poll command message (master)
0
1 1 1 1
slave MAC ID
poll response message (slave)
1
0
master MAC ID
0 0 0 bit-strobe command message (master)
0
1 1 1 0
slave MAC ID
bit-strobe response message (slave)
0
1 1 0 1
slave MAC ID
change-of-state/cyclic message (slave)
1
0
slave MAC ID
0 1 0 change-of-state/cyclic acknowledge message
(master)