Function Blocks PSx-3__-PN
16
Th
e outputs „Error“ and „ErrorID“ of MC_Move are always updated – also if
the input „Release“ is not set.
If the drive reports multiple errors, the ErrorID with the highest priority is shown. This priority
corresponds to the order in the following table (highest priority has 16#x1xx):
ErrorID
Description
16#x1xx
FB internal error
16#x2xx
Invalid PD input address
16#x3xx
Invalid PD output address
16#x4xx
Error while reading PD
16#x5xx
Error while writing PD
16#xxx2
Under- or overvoltage motor supply
16#xxx4
Temperature exceeded
16#xxx5
Absolute measuring system error
16#xxx8
Incorrect target value
16#xxx9
Under- or overvoltage during run
16#xxx6
Block or overcurrent error
16#xxx7
Manual displacement
16#xxxA
Lower position limit exceeded
16#xxxB
Upper position limit exceeded
16#xxx3
Positioning run aborted
16#xxx1
Drag error