5-108
19. LG PLC
19. LG PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
MASTER-K10/60/200
MASTER-K500/1000
*1 For signal level RS-422, baud rate is fixed to 9600 bps.
Select PLC Type
PLC
Connection
MASTER-K10/60/200
K10/60/200
RS-232C
[Wiring Diagram 1]
MASTER-K500/1000
K500/1000
RS-232C
[Wiring Diagram 2]
RS-422
[Wiring Diagram 5]
MASTER-KxxxS
K200S/K300S/K1000S CPU port
RS-232C
[Wiring Diagram 3]
MASTER-KxxxS CNET
K4F-CUEA
RS-232C
[Wiring Diagram 4]
RS-422
[Wiring Diagram 6]
GLOFA CNET
G4L-CUEA
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
9600 bps (fixed)
−
Parity
None (fixed)
−
Transmission code
Data length
8 (fixed)
−
Stop bit
1 (fixed)
−
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
*1
19200 bps
Parity
None (fixed)
−
Transmission code
Data length
8 (fixed)
−
Stop bit
1 (fixed)
−