5-46
6. YOKOGAWA PLC
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
FA500
FA-M3/FA-M3R
*1 The maximum baud rate available with the V7 series is 115200 bps.
Select the appropriate baud rate depending on the used PLC and environment.
*2 When directing connecting to the programming tool port on the CPU module, the data length is
fixed to “8.” Select [8-bit] for [Data Length] in the [comm. Parameter] dialog of the V7 series.
Also, set “CPU Communication Port” of “Configuration” in the ladder creation tool as below.
Personal computer link function: Use
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
1
1
Parity
Even
Even
Transmission code
Data length
7
7
Stop bit
1
1
Sumcheck
Provided (fixed)
−
Terminal character
None (fixed)
−
Protection function
None (fixed)
−
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
*1
19200 bps
19200 bps
Port
1
1
Parity
Even
Even
Transmission code
Data length
*2
7
7
Stop bit
1
1
Sumcheck
Provided
Provided
Terminal character
None (fixed)
−
Protection function
None (fixed)
−