5-78
11. Allen-Bradley PLC
SLC500 Series, Micro Logix 100:
Transmission Parameter Setting
CPU Port Channel 0
Set up the parameters for CPU port channel 0 using the software specifically designed for
this purpose.
1747-KE
Set up the parameters for 1747-KE using the software specifically designed for this
purpose.
Baud Rate
: 19200
Duplicate Detect
: ON
ACK Timeout (x 20 ms)
: 20
Control Line
: No Handshaking
Parity
: EVEN
Error Detection
: BCC
NAK Retries
: 3
ENQ Retries
: 3
Embedded Responses
: AUTO-DETECT
DF1 Port Setup Menu
Baudrate
: 19200
Bits Per Character
: 8
Parity
: Even
Stop Bits
: 1
DF1 Full-Duplex Setup Parameters
Duplicate Packet Detection
: Enabled
Checksum
: BCC
Constant Carrier Detect
: Disabled
Message Timeout
: 400
Hardware Handshaking
: Disabled
Embedded Response Detect
: Auto Detect
ACK Timeout (
×
5 ms)
: 90
ENQuiry Retries
: 3
NAK Received Retries
: 3