8. Toyopuc PLC
5-55
Co
nne
8.
Toyopuc PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Set [Trans. Mode] in the [Detail] tab window of the [Comm. Parameter] dialog of the V-SFT
editor.
- PC3J:
Select [Single Data Area] or [Split Data Area].
- L2/PC2 series:
Select [Single Data Area].
Switch Setting
Baud rate: 19200 bps
Select PLC Type
PLC
Unit/Port
Connection
TOYOPUC
L2/PC2 series
PC3J
CMP-LINK
RS-422
[Wiring Diagram 1]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
0
0
Parity
Even
Even
Transmission code
Data length
7 (ASCII)
7
Stop bit
2
2
Transmission Mode
Contents
Single Data Area
Data area is common.
Split Data Area
Each PLC device is divided into program files.
Switch
Setting
Contents
SW1
0
Station address (lower half)
SW2
0
Station address (upper half)
SW3
1
Baud rate
1: 19200
2: 9600
3: 4800
4: 2400
5: 1200
6: 600
Switch
Short Bar
Contents
SET2
Provided
Data length: 7 bits
SET3
Provided
Stop bit: 2 bits