Automatic Defrosting
There are two defrosting periods in the refrigerator, and they are automatic.
1. Periodical Defrosting
Temperature of the refrigerator shall be kept stabilized and the cycling switch of refrigerating
compressor be kept operated. When the compressor stops operating, a small heater will be
powered-on and thaw the frost layer on the refrigerating coil. This has no obvious influence on
temperature in the inner chamber.
2. Forced Defrosting
When the ambient humidity is high or large amount of wet articles are placed in the box, periodical
defrosting may be unable to remove all the frost on refrigerating coil. The machine will automatically
enter forced defrosting period. Once the forced defrosting is finished, the refrigerator will restore
normal operation and the temperature in the box may rise 1-2
℃
during the defrosting period.
2
1
3
4
5
Button operation
Display
Long press the “SET” for 5s
Press the “SET”
Press “Plus”(0.1
℃
higher/time) or
“Minus”(0.1
℃
lower/time)
Display the temperature in box
Display“TS”
(
Please do the next operation
within 60s. Otherwise the display panel will
return to the inner temperature
)
The original temperature set value 4
℃
changes accordingly
,
until the temperature
displayed on the display panel is 4.5
℃
Return to previous level, display “TS”, and
then back to the normal mode, display the
inner temperature
Press “Set” to return to the previous level,
and then long press “Set” for 5s, the new
temperature will be saved and back to the
normal display mode
The original temperature set value 4
℃
flickers.(Please do the next operation within
60s. Otherwise the display panel will return
to display “TS”)
SN. Alarm items
Buzzing
Light
flashing
3
Fault of
sensor
Conditions of alarm start
Display
requirements
Note
Display board
displays the
alternation between
the mean value of
temperature of both
upper and lower
sensors and E3,
wherein, E3
displaying for 2s
while the temperature
displaying for 6s.
Control sensor is in short circuit
or broken circuit, fault code: E3
Defrosting sensor is in short
circuit or broken circuit, fault
code: E4
Alarming sensor is in short
circuit or broken circuit, fault
code: E5
1Hz
Continuously
Buzzing
Alarm
light
flashes
Display board
displays the
alternation between
the mean value of
temperature of both
upper and lower
sensors and E4,
wherein, E4
displaying for 2s
while the temperature
displaying for 6s
Display board
displays the
alternation between
the mean value of
temperature of both
upper and lower
sensors and E5,
wherein, E5
displaying for 2s
while the temperature
displaying for 6s.
Start remote alarm.
Pressing “Slience” will
cancel the functions of
buzzer and remote
alarm. If it is still in an
alarming state after a
period of Fd (user
parameters can be set,
the default value is
30 min), the buzzer
and remote alarm will
be restarted.
4
Door
opening
alarm
Opening the door (including
slight opening) enables the
function of door opening alarm.
Delay 2 min
(delay 1 – 12
min is
adjustable,
set by user
parameter
dAt, the
buzzer will
continuously
buzz with
1Hz)
Alarm
light
flashes
Display the actual
conditions
Function of remote
alarm isn’t started.
HXC-1308/1308B