122
Inverter outdoor unit failure code
Code
Error code definition
Notes
20
Defrosting temp. sensor (Te) failure
Restorable
21
Ambient temp. sensor (Ta) failure
Restorable
22
Suction temp. sensor (Ts) failure
Restorable
23
Discharging temp. sensor (Td) failure
Restorable
26
Communication failure with indoor
Restorable
28
High pressure sensor failure
Restorable
29
Low pressure sensor failure
Restorable
30
High pressure switch HPS failure
Unrecoverable after locking
33
Outdoor EEPROM failure
Unrecoverable
34
Discharging temp too high protection (Td)
Unrecoverable after locking
35
4-way valve reversing failure
Unrecoverable after locking
38
High pressure too low protection(Pd)
Unrecoverable after locking
39
Low pressure too low(Ps)/compres-sion ratio too high protection/
compres-sion ratio too low protection
Unrecoverable after locking
40
High pressure too high protection(Pd)
Unrecoverable after locking
43
Discharging temp too low protection (Td)
Unrecoverable after locking
46
Discharging communication fault with IGBT Power Moudule
Restorable
71
DC FAN failure
Unrecoverable after locking
78
Too little refrigerant
Restorable
81
Radiator of transducer temp too hiah
Unrecoverable after locking
82
Compressor current protection
Unrecoverable after locking
87
Defrosting with too low water temperature
Restorable
110
Module hardware excess current
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
111
Compressor out of step
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
112
Radiator of transducer temp too high
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
113
Transducer overload
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
114
Voltage too low of DC bus line
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
115
Voltage too high of DC bus line
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
116
Communication abnormal between transducerand control PCB If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
117
Transducer over current (software)
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
118
Compressor startup failure
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
119
Current detecting circuit abnormal of transducer
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
120
Module power supply abnormal
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
121
Power supply of inverter board is abnormal
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking
122
Radiator temp. sensor abnormal
If it occurs 3 times in an hour, lock the
failure, unrecoverable after locking