110
Outdoor unit valves control
SMG2-2 SMG1-1 SMG1-2
Function
Digital tube display
6
0
2
Manually control 4WV
•
Parts current state: 1 ON; 0 OFF
• Press ENTER (SW7) for 3 seconds and digital tube
displays "111", to the setting state: falshing display,
UP (SW4) for ON, DOWN (SW5) for OFF;
• Press EXIT (SW6) for 3 seconds and digital tube
displays "000", exit the setting state, flash stops
6
1
2
Manually control SV1
6
3
2
Manually control SV2
6
11 (B)
2
Manually control CHi
6
13 (D)
2
Manually control CHa
6
15(F)
2
Cancel all manual control
(parts)
• Press ENTER (SW7) for 3 seconds and digital tube
displays "111" to cancel, or press EXIT (SW6) for 3
seconds and digital tube displays "000" to cancel.
• Cancel includes: All manaully control of outdoor unit
operating parts including Compressor, Fan motor,
LEV, Solenoid valve etc. (also include evacuation
and injection, not include rated/forced operation,
indoor ON/OFF)
E2 parameters view
SMG2-2 SMG1-1 SMG1-2
Function
Digital tube display
12 (C)
0
0
The EE data of address 000H (Version E2)
000H-0FFH address EE data display;
Address calculation: addr=SMG1-1*10H
+SMG1-2
Data display: hexadecimal display, H
represents hexadecimal number
0
1
The EE data of address 001H
…
…
…
0
F
The EE data of address 00FH
1
0
The EE data of address 010H
…
…
…
1
F
The EE data of address 01FH
…
…
…
F
F
The EE data of address 0FFH
13 (D)
0
0
The EE data of address 100H
100H-13FH address EE data display
Location: addr=100 H+SMG1-1*10H
+SMG1-2
Data display: hexadecimal display, H
represents hexadecimal number
0
1
The EE data of address 101H
……
……
……
3
F
The EE data of address 13FH
4
0
The EE data of address 140H
140H-1FFH address is fault information
area
……
……
……
F
F
The EE data of address 1FFH