9
4.
Specifications
Item
Unit
HU062WAMNA
HU102WAMNA
Operation
Range
Outdoor
Ambient
°C
Cooling: 10 ~ 48
Heating: -25 ~ 35
Cooling: 10 ~ 48
Heating: -25 ~ 35
Water Outlet
°C
Cooling: 5/25
Heating: 20 / 50
(Outdoor Ambient temp≤-15 °C)
Heating: 15 / 60
(Outdoor Ambient temp
>
-15 °C)
Cooling: 5/25
Heating: 20 / 50
(Outdoor Ambient temp≤-15 °C)
Heating: 15 / 60
(Outdoor Ambient temp
>
-15 °C)
Internal Pressure Differential
kPa
Cooling:20
Heating: 20
Cooling:30
Heating: 30
Noise Level (dB)
Sound
power level
42
42
Dimension
Height
mm
850
850
Width
mm
480
480
Depth
mm
310
310
Net Weight
kg
41
43
Refrigerant
Pipe Diameter
Liquid
mm
9.52
9.52
Gas
mm
15.88
15.88
Water Pipe
Diameter
Inlet
mm
25.4
25.4
Outlet
mm
25.4
25.4
Pump
Motor Type
DC Motor
DC Motor
Input Power
W
75
75
Hot Water Coil
Type
Brazed Plate
Brazed Plate
No. of Plates
52
48
Size(WxHxL)
mm
324*94*82
333*121*87
Pressure Relief Valve Water
Circuit
kPa
Open: 550, Close: ≤500
Open: 550, Close: ≤500
Flow Switch
Electronic Sensor
Electronic Sensor
Expansion
Vessel
Volume
5
5
MWP
bar
10
10
Capacity of Integrated
Electric Heater
kW
1+3
1+3
Max running current
A
20
20
Built-in circuit breaker
A
63
63