87
Pipe specification
Note: 6.35mm pipe diameter is recommended for piping with liquid pipe length of 5 meters or less.
Outdoor Model
Gas pipe(mm)
Liquid pipe(mm)
AW042/062SSCHA
15.88
6.35
AW082/102SNCHA
15.88
9.52
Electric wiring and the application
General check
•
Make sure that the following conditions related to power supply installation are satisfied:The power capacity of
the electrical installation is large enough to support the power demand of the HAIER system.
The power supply voltage is within ±10% of the rated voltage.
The impedance of the power supply line is low enough to avoid any voltage drop of more than 15% of the rated
voltage.
• Following the Council Directive 2004/108/EC, relating to electromagnetic compatibility, the table below indicates
the Maximum permitted system impedance Zmax at the interface point of the user’s supply, in accordance with
EN61000 3 11.
Model
Power supply
ZMax.(Ω)
AW042SSCHA
1PH,
220-240V~,
50Hz
0.24
AW062SSCHA
0.24
AW082SNCHA
0.24
AW102SNCHA
0.24
WARNING
• Switch off the main power switch of the indoor and outdoor machine for more than 1 minutes before the wiring
or regular inspection.
• To prevent the destruction of wires and electrical components by rats or other animals. Serious, it may lead to
the occurrence of fire.
• To avoid damage to the wire, avoid contact with refrigerant pipes, steel edges and electrical components.
Serious, it may lead to the occurrence of fire.
CAUTION
• Secure the power cord with a wire tie in the machine.
CAUTION
• In the case of 3 phase 5 wire type, the power supply of the indoor machine must be connected use L1 line and
N line, prohibit the use of L1-L2, L1-L3, Otherwise the electrical part will be damaged.
Note:
when the wiring of the outdoor machine is not using the wire, it should be fixed with the rubber ring.
The cord of the H07RN-F type or the electrically
equivalent type must be used for power connection
and interconnection between outdoor unit and
indoor unit.