53
Table 2
– Minimum floor area
m
c
(kg)
Minimum floor area/ A
min
total (m
2
)
H=1.15m
H=1.20m
H=1.30m
H=1.40m
H=1.50m
H=1.60m
H=1.70m
H=1.80m
1.84
7.84
7.20
6.15
5.71
5.33
4.99
4.70
4.44
1.86
8.02
7.36
6.27
5.77
5.39
5.05
4.75
4.49
1.88
8.19
7.52
6.41
5.83
5.44
5.10
4.80
4.54
1.90
8.36
7.68
6.54
5.89
5.50
5.16
4.85
4.58
1.92
8.54
7.84
6.68
5.96
5.56
5.21
4.91
4.63
1.94
8.72
8.01
6.82
6.02
5.62
5.27
4.96
4.68
1.96
8.90
8.17
6.96
6.08
5.68
5.32
5.01
4.73
1.98
9.08
8.34
7.11
6.14
5.73
5.37
5.06
4.78
2.00
9.27
8.51
7.25
6.25
5.79
5.43
5.11
4.83
2.02
9.45
8.68
7.40
6.38
5.85
5.48
5.16
4.87
2.04
9.64
8.85
7.54
6.51
5.91
5.54
5.21
4.92
2.06
9.83
9.03
7.69
6.63
5.96
5.59
5.26
4.97
2.08
10.02
9.21
7.84
6.76
6.02
5.65
5.31
5.02
2.10
10.22
9.38
8.00
6.89
6.08
5.70
5.37
5.07
2.12
10.41
9.56
8.15
7.03
6.14
5.75
5.42
5.12
2.14
10.61
9.74
8.30
7.16
6.24
5.81
5.47
5.16
2.16
10.81
9.93
8.46
7.29
6.35
5.86
5.52
5.21
2.18
11.01
10.11
8.62
7.43
6.47
5.92
5.57
5.26
2.20
11.21
10.30
8.77
7.57
6.59
5.97
5.62
5.31
2.22
11.42
10.49
8.94
7.70
6.71
6.03
5.67
5.36
2.24
11.62
10.68
9.10
7.84
6.83
6.08
5.72
5.40
2.26
11.83
10.87
9.26
7.98
6.96
6.13
5.77
5.45
2.27
11.94
10.96
9.34
8.06
7.02
6.17
5.80
5.48
• For intermediate H values, the value that corresponds to the lower H value from the table considered.
Example:
For H=1.25 m, the value that corresponds to H=1.20 m is considered.
• For intermediate m
c
values, the value that corresponds to the higher m
c
value from the table is considered.
Example:
If mc =1.85 kg, the value that corresponds to mc =1.86 kg is considered.
•
Systems with total refrigerant charge lower than 1.84 kg are not subjected to any room area requirements.
• Charges above 2.27 kg are not allowed in the unit.