Table 3 Minimum venting opening area for natural ventilation
m
c
(kg) m
max
(kg)
m
excess
(kg)
= m
c
- m
max
Minimum venting opening area (VA
min
) (cm
2
)
H=
1.15m
H=
1.20m
H=
1.30m
H=
1.40m
H=
1.50m
H=
1.60m
H=
1.70m
H=
1.80m
2.27
0.1
2.17
634
621
596
575
555
538
522
507
2.27
0.3
1.97
576
564
541
522
504
488
473
460
2.27
0.5
1.77
517
506
486
469
453
438
425
413
2.27
0.7
1.57
459
449
431
416
402
389
377
367
2.27
0.9
1.37
400
392
377
363
351
339
329
320
2.27
1.1
1.17
342
335
322
310
299
290
281
273
2.27
1.3
0.97
283
277
267
257
248
240
233
227
2.27
1.5
0.77
225
220
212
204
197
191
185
180
2.27
1.7
0.57
170
163
157
151
146
141
137
133
2.27
1.9
0.37
117
112
103
98
95
92
89
86
• For intermediate H values, the value that corresponds to the lower H value from the table considered.
Example:
For H=1.25 m, the value that corresponds to H=1.20 m is considered.
• For intermediate mexcess values, the value that corresponds to the higher mexcess value from the table is
considered.
Example:
If mexcess =1.45 kg, the value that corresponds to m
c
=1.6 kg is considered.
Attached Accessories
No.
Accessories part
Qty.
Remarks
Place position
1
Installation plate I
1
/
Fixed on wooden base
2
Installation plate II
1
/
Fixed on wooden base
3
Installation manual
1
/
Accesory bag
4
Reducing pipe
1
Only for HU062WAMNA
Accesory bag