Date : 20/09/2012
6T 8206-02a
tebis touch panel Installer Manual
EXAMPLE FOR QUICK START-UP
18
3.2.2.1 Installation of the plug-in on ETS
Configuration of the system can be done from the tebis touch panel itself or from ETS. In this example, we will cover the
general scenario with ETS.
-
Install the plug-in from the HAGER products ETS database.
(Download the database file from your HAGER internet site.)
-
Declare the tebis touch panel in your project topology.
-
Set the Physical Address:
o
Put the tebis touch panel in addressing mode. There are 2 options:
With the ‘’Cfg’’ button found on the back of the product. Using a pen, press the button until the
halo is illuminated.
With the ‘physical address' menu
To do this, press the
symbol located at the top right of the screen to access the menu,
followed by
to access the configuration menu.
Click on
and select ‘physical address’.
Click on
to activate the physical address.
o
In the topology for your project, select your tebis touch panel.
o
By right-clicking on the mouse, select Download followed by Program Individ. Address.
Programming is finished when the light on the back of the product goes off or when the tebis touch panel
displays the new physical address.
Comment: After programming the new physical address, the addressing mode is automatically deactivated.