background image

P/N G610B 
April, 2016 (Rev 0)

 

 

Page 22

 

 

 

 

 

TROUBLESHOOTING GUIDE  

 
CAUTION: DURING TROUBLESHOOTING PROCEDURES MAKE SURE A SPARE SAFETY PULL 
PIN IS INSTALLED IN THE EXTINGUISHER HANDLE. THE SPARE SAFETY PULL PIN MUST BE 
REMOVED FROM THE HANDLE WHEN TROUBLESHOOTING IS COMPLETE.

 

Main CPU Board 

(P/N G602)

 

 

 

Problem:

 

No Fire Detect Mode

 

 
Check the following: (See 

FIGURE 3

  

 

The  Main  CPU  has  built  in  self-diagnostics,  see 
page 5, “Diagnostic Test”. 

 

Release Solenoid Latch 

 

Problem:

 

 No Activation of Latch 

 

Check the following: (See 

FIGURE 3

 

 

The  solenoid  plug  is  connected  to  the  correct 
position on the main CPU and is fully mated. 

 

 

Place  a  spare  Pull  pin  in  the  Handle. 

Use  a 

Multi-meter  to  measure  the  DC  Voltage  signal 
across J9 (VALVE) connector on the board when 
the  system  is  manually  activated  by  pulling  the 
pull  station  or  placing  a  temporary  short  across 
J3  (REMOTE  PULL).  If  signal  does  not  appear, 
replace  the  CPU  board.  If  signal  exists,  perform 
next step.  

 

 

Disconnect the solenoid valve plug from the main 
CPU,  use  a  Multi-meter  to  measure  the 
resistance  between  the  two  contacts  in  the  plug 
coming from the solenoid. The resistance should 
be  approximately  190  ohms.    If  there  is  no  
indication of resistance, replace solenoid.  

 

Electric Shutoffs

 (P/N G319) 

 
Verify  the  configuration  and  determine  if  the  electric 
shutoff is a 3 Prong, 4 Prong or Hardwired version.  

 

Problem:

 No Electrical Power To Stove using 

 

Interconnect Cable Configuration 

 

 

Review installation instruction on pages 8-12 and 
make  sure  that  the  shut-off  is  properly  installed. 
Perform Reset Stove procedure on Page 12.  

 

 

Verify  that  the  Interconnect  cable  between  the 
Main  CPU  control  board  and  shut-off  is  fully 
plugged  into  to  the  correct  connector  on  both 
ends  of  the  cable  and  that  the  connectors  are 
fully mated. 
 

 

Press  the  reset  button  on  the  Main  CPU  and 
verify the green indicator momentarily lights up. 

 

 

Verify  power  is  getting  to  stove  by  testing  a 
burner.  If  there  is  no  power,  disconnect  the 
electric shutoff and plug the stove directly into the 
wall.  

 

 

If power to the stove exists by plugging it directly 
into  the  wall,  replace  the  electric  shutoff.  If  no 
power exist to the stove, check site condition. 

 

 

For  hardwired  versions,  have  a  licensed 
electrician  verify  that  the  source  power  is 
supplied to the same side of the contactor as the 
orange wires from the ESO printed circuit board.  

 

Problem:

 No Shutoff Activation using the 

 

Interconnect Cable 

 
 

 

Confirm  that  power  is  supplied  to  the  stove 
through the electric shutoff. 
 

 

Press  the  “Reset”  button  on  the  main  CPU  and 
make  sure  that  the  green  indicator  momentarily 
illuminates.  If  green indicator does not  illuminate 
then  run  “Diagnostic  Test”  on  pages  5-6  of  this 
manual. 

 

 

Verify  that  the  Interconnect  cable  between  the 
Main  CPU  control  board  and  shut-off  is  plugged 
into to the correct connector on both ends of the 
cable and that the connectors are fully mated. 
 

 

Perform  “Arming  the  System”  procedures  on 
Page  15.  If  power  to  the  stove  stays  on  after  a 
diagnostic test, and there are no Diagnostic Code 
“beeps”, then perform the next step below. 

 

 

Disconnect  the  interconnect  cable  from  the 
Electric  shut  off.  Using  a  small  piece  of  wire, 
create a short across the two outside pins of the 
white 4 pin socket on the shut-off. 

Note- Do not 

make  contact  with  either  of  the  two  inner 
pins

.  Activation  of  the  shut-off  should  occur.    If 

activation does NOT occur, replace the shutoff.  

  

 

If  activation  occurs,  reset  the  shutoff,  reconnect 
the  interconnect  cable  and  perform 

Arming  the 

System

 on page 15 again.

 

If power to the stove 

stays on after a diagnostic test, and there are no 
Diagnostic  Code  “beeps”  then  replace  the  Main 
CPU board. 

 

 

 
 

Permit Number:

20-04649

Summary of Contents for G600-B

Page 1: ...OPERATION INSPECTION AND MAINTENANCE MANUAL MODEL G600 B RESIDENTIAL RANGE TOP EXTINGUISHER UNIT UL FILE NO EX 3940 P N G610B APRIL 2016 REV 0 8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Per...

Page 2: ...11B 4 Prong Shutoff FIGURE 11C Hardwire Shutoff FIGURE 12 Electric Shutoff Connector Configuration FIGURE 13 Electric Shutoff Interconnect Identification FIGURE 14 Electric Shutoff Installation FIGUR...

Page 3: ...al range tops when installed in conjunction with a 30 inch wide exhaust hood or microwave exhaust hood combination with a flat ferromagnetic underside The extinguishing system is intended for installa...

Page 4: ...ectrical or gas stoves ready for installation in the kitchen cabinet and range hood over the stove Sensor Assembly P N G605 A Distribution Assembly P N 604 A Enclosure Extinguisher Assembly P N G699 B...

Page 5: ...GUARDIAN G600 B AS A HAND HELD PORTABLE EXTINGUISHER SERIOUS INJURY COULD RESULT FROM MISUSE THE CHEMICAL AGENT USED IN THE GUARDIAN G600 B IS NOT REGARDED AS A TOXIC MATERIAL BUT CAN CAUSE IRRITATIO...

Page 6: ...owly flashing red indicator If the main unit passes all 6 tests upon reset the result is a display of the green indictor for 2 seconds whereupon it enters Fire Detect Mode and the system is armed 2 Di...

Page 7: ...if the diagnostic failure is a low battery Approximately once per minute the battery is checked If it is low there will be a short chirp to indicate that the battery needs to be replaced The unit will...

Page 8: ...nd for easy connection to the valve head of the extinguisher Inside the housing there are 2 nozzles mounted in fittings connected by a stainless steel tube The assembly is installed underneath the hoo...

Page 9: ...xtinguisher Assembly Before Drilling measure the route and make certain that the sensor cable and stainless steel braided hose are long enough to connect to the Guardian G600 B System Enclosure Exting...

Page 10: ...crews to anchor into the hood above and two 1 1 4 screws to secure to the wall behind Screws in the wall must be located where they will go into the walls studs or into a wall anchor Screws going into...

Page 11: ...ng Gauge provided adjust the nozzles to the correct angle based on the height determined in step 14 This is done by placing the Gauge in the housing and aligning the nozzles spray hole with the corres...

Page 12: ...he electric shutoff is activated or an interruption in power occurs it must be reset See Reset Stove p 12 INSTALLATION NOTE Ensure the Electric Shutoff is installed within the same room as the Main CP...

Page 13: ...and 25 Reset Stove 1 The electric stove shutoff unit may be reset by locating the circuit breaker supplying power to the stove and turning it off and then back on or 2 Momentarily unplugging the shuto...

Page 14: ...6 1 on the incoming service line to the stove Adhere to manufacturers installation and maintenance instructions Wiring must comply with local and national electrical codes The solenoid valve is design...

Page 15: ...s compatible with both the interconnect cable and the Wireless Tx Rx Either interconnect option is available and can plug into the gas shutoff In some cases a wireless version of the shutoff device ma...

Page 16: ...ic Failure Code occurs 1 Verify that the fuel shut off is powered and is reset See page 12 for Electric page 14 for Gas 2 Next check that the solenoid release latch is engaged See Figure 28 p 19 and t...

Page 17: ...on of the Main CPU board includes a Motor Test Advance Button and includes a TRIP MOTOR connection on the board instead of a VALVE connection See Figure 26 Note Test the Trip Motor and Cam Monthly by...

Page 18: ...he range top burners and activate the alarm or other electrical accessory Once activated the automatic sequence cannot be interrupted The manual pull station is installed at a height not exceeding 60...

Page 19: ...vide an interface for a 120 volt 5A alarm strobe This assembly has a Plug Play configuration for ease of installation Install in optimum location for visibility This feature is mainly used with the st...

Page 20: ...ng fire extinguisher unit appliance nozzles sensor distribution assembly and shutoffs Replace battery in the central processing unit control board annually from the date of installation Use only Durac...

Page 21: ...gent cylinder has been completely expelled and the pull pin is re installed in the handle prior to disconnecting the quick connect 4 Disconnect the quick connect below the handle and remove the distri...

Page 22: ...1 18 24 25 G615 A Wireless Tx and Rx and AC DC 18 24 G702 Wireless Receiver Rx Assembly 18 25 G701 Wireless Transmitter Tx Assembly 14 17 G316 A Gas Shutoff Assembly 1 14 17 G316 1 Gas Valve 1 14 17 G...

Page 23: ...and that the connectors are fully mated Press the reset button on the Main CPU and verify the green indicator momentarily lights up Verify power is getting to stove by testing a burner If there is no...

Page 24: ...f any unknown wireless interference occurs from a site condition the Interconnect Cable may have to be used Gas Shutoff P N G316 A Problem No Electrical Power To Stove Confirm that power is supplied a...

Page 25: ...switch to open the gas valve to the stove The gas flow indicator light will illuminate Verify that the Interconnect cable between the Main CPU control board and the Gas Shutoff Control box is plugged...

Page 26: ...perform Arming the System on page 15 again If power gas to the stove stays on after a diagnostic test and there are no Diagnostic Code beeps then replace the Main CPU board If the stove successfully...

Page 27: ...TRAC 1 800 535 5053 Account Number 78764 SECTION II Hazard Identification GHS Classification Acute Toxicity Category 5 Eye Irritation Category 2B Skin Irritation Category 3 GHS Label Elements Hazard S...

Page 28: ...on is an extinguishing media There are NO extinguishing media which must not be used for safety reasons NO special protective equipment is needed for fire fighters Wear protective equipment appropriat...

Page 29: ...o C About 230 o F Flash point None to boiling Flammability solid gas Not flammable Explosive properties Not explosive Oxidizing properties Not an oxidizer Vapor Pressure About 12mm Hg Relative Densit...

Page 30: ...harm to the environment is expected from this preparation Please Note Although this material is not considered hazardous when contained in a stored pressure fire extinguisher pressurized with a nonfl...

Page 31: ...l advice S 36 Wear suitable protective clothing THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT BUT DOES NOT PURPORT TO BE ALL INCLUSIVE AND SHALL BE USED ONLY AS A GUIDE GUARDIAN SAFETY SOLUTIONS INT...

Page 32: ...8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Toll Free 800 786 2178 Fax 972 594 7826 www guardianssi com Permit Number 20 04649...

Reviews: