ACCESSORIES
Building Alarm Interface
(P/N G502INT)
DESCRIPTION:
The optional Building Alarm Interface (P/N G502INT)
is provided to allow easy interfacing to external device
i.e. automatic telephone dialers, monitored security
alarm systems, building fire alarm systems and other
warning/protective equipment. It allows for remote
monitoring of the system in case of system discharge
or diagnostic failure. The Building Alarm Interface
provides one set of dry latching contacts that switch
when an Alarm Sequence occurs (See section “5.
Alarm Sequence” page 6) and one set of dry latching
contacts that switch in the event of a Shutoff
Sequence (See section “4. Shutoff Sequence” page
6.) The Building Alarm Interface connects to the G602
CPU board and easily mounts on the side of the
cylinder enclosure. Contact Rating is 0.6A 125VAC,
2A 30VDC. (See
Figures 2, 3, and 20
)
Manual Remote Pull Station
(G309-A)
DESCRIPTION:
A manual remote pull station is available where local
fire codes or circumstances require the capability to
manually activate the range top extinguisher system.
(See
FIGURES 21, 22 & 23
)
Manual activation of the system will cause the
extinguisher unit to fully discharge extinguishing
agent, shut off the range top burners and activate the
alarm or other electrical accessory. Once activated,
the automatic sequence cannot be interrupted.
The manual pull station is installed at a height not
exceeding 60" from the floor and should be located in
the path of exit. Avoid locating the manual pull station
where the occupant would have to reach over the
range top-cooking element to activate the system.
(Some jurisdictions require certain distances.)
NOTE:
An Identification sign shall be installed
indicating
"Pull Station for Range Top Fire
Suppression ONLY."
Installation:
1.
Determine the best location for the manual pull
station. The location must be accessible as
required.
2.
Install cable in conduit or attach using cable
clamps as required by jurisdiction.
3.
Feed the cable wire through the access hole into
the system enclosure.
4.
Position the cable wire on the same side of the
cylinder as the sensor wires.
5.
Plug the connector into the “REMOTE PULL”
connector on the Main CPU.(see
Figure 3 and 21
)
6.
Cut the wire to length, strip and crimp ends and
connect to terminal strip contact on remote
pull.(see
Figure 22
)
7.
Verify that manual remote pull station is working
after “Arming the System” page 15.
Caution:
Temporarily install a spare pull pin in the
handle when testing the Manual Remote Pull to
prevent fire suppressant dump.
FIGURE 22
FIGURE 21
FIGURE 20
FIGURE 23
Terminal Strip
Contacts
Wire Length
Supplied = 30ft