ACCESSORIES

 
Building Alarm Interface 

(P/N G502INT) 

 
DESCRIPTION:  

 

The  optional  Building  Alarm  Interface  (P/N  G502INT) 
is provided to allow easy interfacing to external device 
i.e.  automatic  telephone  dialers,  monitored  security 
alarm systems, building fire alarm systems and other 
warning/protective  equipment.  It  allows  for  remote 
monitoring of the system in case of system discharge 
or  diagnostic  failure.  The  Building  Alarm  Interface 
provides  one  set  of  dry  latching  contacts  that  switch 
when  an  Alarm  Sequence  occurs  (See  section  “5. 
Alarm Sequence” page 6) and one set of dry latching 
contacts  that  switch  in  the  event  of  a  Shutoff 
Sequence  (See  section  “4.  Shutoff  Sequence”  page 
6.) The Building Alarm Interface connects to the G602 
CPU  board  and  easily  mounts  on  the  side  of  the 
cylinder  enclosure.  Contact  Rating  is  0.6A  125VAC, 
2A 30VDC. (See 

Figures 2, 3, and 20

 

 

 
 
 
 
 
 
 
 
 
 

 
 

Manual Remote Pull Station 

(G309-A) 

 

DESCRIPTION:  

 

A manual remote pull station is available where local 
fire codes or circumstances require the capability to 
manually activate the range top extinguisher system. 
(See 

FIGURES 21, 22 & 23

)  

 
 
 
 
 
 
 
 

 
 
 
 
 
Manual  activation  of  the  system  will  cause  the 
extinguisher  unit  to  fully  discharge  extinguishing 
agent, shut off the range top burners and activate the 
alarm  or  other  electrical  accessory.  Once  activated, 
the automatic sequence cannot be interrupted.  
 
The  manual  pull  station  is  installed  at  a  height  not 
exceeding 60" from the floor and should be located in 
the path of exit. Avoid locating the manual pull station 
where  the  occupant  would  have  to  reach  over  the 
range  top-cooking  element  to  activate  the  system. 
(Some jurisdictions require certain distances.)  

 

NOTE:

  An  Identification  sign  shall  be  installed 

indicating 

"Pull  Station  for  Range  Top  Fire 

Suppression ONLY."

  

 

Installation: 

  

1. 

Determine  the  best  location  for  the  manual  pull 
station.  The  location  must  be  accessible  as 
required.  

2. 

Install  cable  in  conduit  or  attach  using  cable 
clamps as required by jurisdiction.  

3. 

Feed  the  cable  wire  through  the  access  hole  into 
the system enclosure.  

4. 

Position  the  cable  wire  on  the  same  side  of  the 
cylinder as the sensor wires.  

5. 

Plug  the  connector  into  the  “REMOTE  PULL” 
connector on the Main CPU.(see 

Figure 3 and 21

6. 

Cut  the  wire  to  length,  strip  and  crimp  ends  and 
connect  to  terminal  strip  contact  on  remote 
pull.(see 

Figure 22

7. 

Verify  that  manual  remote  pull  station  is  working 
after  “Arming  the  System”  page  15. 

Caution: 

Temporarily  install  a  spare  pull  pin  in  the 
handle when testing the Manual Remote Pull to 
prevent fire suppressant dump. 

FIGURE 22 

FIGURE 21 

FIGURE 20 

FIGURE 23 

Terminal Strip 

Contacts 

Wire Length 

Supplied = 30ft 

Permit Number:

20-04649

Summary of Contents for G600-B

Page 1: ...OPERATION INSPECTION AND MAINTENANCE MANUAL MODEL G600 B RESIDENTIAL RANGE TOP EXTINGUISHER UNIT UL FILE NO EX 3940 P N G610B APRIL 2016 REV 0 8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Per...

Page 2: ...11B 4 Prong Shutoff FIGURE 11C Hardwire Shutoff FIGURE 12 Electric Shutoff Connector Configuration FIGURE 13 Electric Shutoff Interconnect Identification FIGURE 14 Electric Shutoff Installation FIGUR...

Page 3: ...al range tops when installed in conjunction with a 30 inch wide exhaust hood or microwave exhaust hood combination with a flat ferromagnetic underside The extinguishing system is intended for installa...

Page 4: ...ectrical or gas stoves ready for installation in the kitchen cabinet and range hood over the stove Sensor Assembly P N G605 A Distribution Assembly P N 604 A Enclosure Extinguisher Assembly P N G699 B...

Page 5: ...GUARDIAN G600 B AS A HAND HELD PORTABLE EXTINGUISHER SERIOUS INJURY COULD RESULT FROM MISUSE THE CHEMICAL AGENT USED IN THE GUARDIAN G600 B IS NOT REGARDED AS A TOXIC MATERIAL BUT CAN CAUSE IRRITATIO...

Page 6: ...owly flashing red indicator If the main unit passes all 6 tests upon reset the result is a display of the green indictor for 2 seconds whereupon it enters Fire Detect Mode and the system is armed 2 Di...

Page 7: ...if the diagnostic failure is a low battery Approximately once per minute the battery is checked If it is low there will be a short chirp to indicate that the battery needs to be replaced The unit will...

Page 8: ...nd for easy connection to the valve head of the extinguisher Inside the housing there are 2 nozzles mounted in fittings connected by a stainless steel tube The assembly is installed underneath the hoo...

Page 9: ...xtinguisher Assembly Before Drilling measure the route and make certain that the sensor cable and stainless steel braided hose are long enough to connect to the Guardian G600 B System Enclosure Exting...

Page 10: ...crews to anchor into the hood above and two 1 1 4 screws to secure to the wall behind Screws in the wall must be located where they will go into the walls studs or into a wall anchor Screws going into...

Page 11: ...ng Gauge provided adjust the nozzles to the correct angle based on the height determined in step 14 This is done by placing the Gauge in the housing and aligning the nozzles spray hole with the corres...

Page 12: ...he electric shutoff is activated or an interruption in power occurs it must be reset See Reset Stove p 12 INSTALLATION NOTE Ensure the Electric Shutoff is installed within the same room as the Main CP...

Page 13: ...and 25 Reset Stove 1 The electric stove shutoff unit may be reset by locating the circuit breaker supplying power to the stove and turning it off and then back on or 2 Momentarily unplugging the shuto...

Page 14: ...6 1 on the incoming service line to the stove Adhere to manufacturers installation and maintenance instructions Wiring must comply with local and national electrical codes The solenoid valve is design...

Page 15: ...s compatible with both the interconnect cable and the Wireless Tx Rx Either interconnect option is available and can plug into the gas shutoff In some cases a wireless version of the shutoff device ma...

Page 16: ...ic Failure Code occurs 1 Verify that the fuel shut off is powered and is reset See page 12 for Electric page 14 for Gas 2 Next check that the solenoid release latch is engaged See Figure 28 p 19 and t...

Page 17: ...on of the Main CPU board includes a Motor Test Advance Button and includes a TRIP MOTOR connection on the board instead of a VALVE connection See Figure 26 Note Test the Trip Motor and Cam Monthly by...

Page 18: ...he range top burners and activate the alarm or other electrical accessory Once activated the automatic sequence cannot be interrupted The manual pull station is installed at a height not exceeding 60...

Page 19: ...vide an interface for a 120 volt 5A alarm strobe This assembly has a Plug Play configuration for ease of installation Install in optimum location for visibility This feature is mainly used with the st...

Page 20: ...ng fire extinguisher unit appliance nozzles sensor distribution assembly and shutoffs Replace battery in the central processing unit control board annually from the date of installation Use only Durac...

Page 21: ...gent cylinder has been completely expelled and the pull pin is re installed in the handle prior to disconnecting the quick connect 4 Disconnect the quick connect below the handle and remove the distri...

Page 22: ...1 18 24 25 G615 A Wireless Tx and Rx and AC DC 18 24 G702 Wireless Receiver Rx Assembly 18 25 G701 Wireless Transmitter Tx Assembly 14 17 G316 A Gas Shutoff Assembly 1 14 17 G316 1 Gas Valve 1 14 17 G...

Page 23: ...and that the connectors are fully mated Press the reset button on the Main CPU and verify the green indicator momentarily lights up Verify power is getting to stove by testing a burner If there is no...

Page 24: ...f any unknown wireless interference occurs from a site condition the Interconnect Cable may have to be used Gas Shutoff P N G316 A Problem No Electrical Power To Stove Confirm that power is supplied a...

Page 25: ...switch to open the gas valve to the stove The gas flow indicator light will illuminate Verify that the Interconnect cable between the Main CPU control board and the Gas Shutoff Control box is plugged...

Page 26: ...perform Arming the System on page 15 again If power gas to the stove stays on after a diagnostic test and there are no Diagnostic Code beeps then replace the Main CPU board If the stove successfully...

Page 27: ...TRAC 1 800 535 5053 Account Number 78764 SECTION II Hazard Identification GHS Classification Acute Toxicity Category 5 Eye Irritation Category 2B Skin Irritation Category 3 GHS Label Elements Hazard S...

Page 28: ...on is an extinguishing media There are NO extinguishing media which must not be used for safety reasons NO special protective equipment is needed for fire fighters Wear protective equipment appropriat...

Page 29: ...o C About 230 o F Flash point None to boiling Flammability solid gas Not flammable Explosive properties Not explosive Oxidizing properties Not an oxidizer Vapor Pressure About 12mm Hg Relative Densit...

Page 30: ...harm to the environment is expected from this preparation Please Note Although this material is not considered hazardous when contained in a stored pressure fire extinguisher pressurized with a nonfl...

Page 31: ...l advice S 36 Wear suitable protective clothing THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT BUT DOES NOT PURPORT TO BE ALL INCLUSIVE AND SHALL BE USED ONLY AS A GUIDE GUARDIAN SAFETY SOLUTIONS INT...

Page 32: ...8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Toll Free 800 786 2178 Fax 972 594 7826 www guardianssi com Permit Number 20 04649...

Reviews: