P/N G610B
April, 2016 (Rev 0)
Page 1
SHOULD OR MAY:
Indicates a recommendation or
that which is advised.
APPLIANCE:
For the purpose of this manual,
appliance means a residential-type kitchen range
supplied by gas or electricity to power and heat range
top burners.
G600-B:
The Guardian Model G600-B is the standard
model offered for typical installations
when used in
conjunction with a flat faced (bottom) exhaust hood or
microwave hood only.
G600B-C:
The Guardian Model G600B-C is an
alternate model designed for environment’s that could
periodically subject the system to vibration or jarring.
See Page 16 for further explanation and additional
limitations.
TABLE OF CONTENTS
Pg.
DEFINITIONS ..................................................... 1
LIST OF ILLISTRATIONS ................................. 1
INTRODUCTION ................................................ 2
APPLICATION AND LIMITATION .................. 2
GUARDIAN G600-B SYSTEM COMPONENT . 3
ENCLOSURE/EXTINGUISHER ASSY ............. 4
CPU UNIT CONTROL BOARD ......................... 5
DETECTION SENSOR ASSEMBLY ................. 7
DISTRIBUTION ASSEMBLY ............................ 7
SYSTEM INSTALLATION INSTRUCTIONS ... 8
AIMING NOZZLES ............................................. 10
ELECTRIC SHUTOFFS ...................................... 11
GAS SHUTOFFS ................................................. 13
ARMING THE SYSTEM..................................... 15
ALTERNATE CAM ACTIVATION ................... 16
ACCESSORIES ................................................... 17
INSPECTION AND MAINTENANCE ............... 19
AFTER A DISCHARGE ...................................... 20
PARTS LIST ........................................................ 21
TROUBLE SHOOTING GUIDE ......................... 22
ILLUSTRATIONS
FIGURE 1
Guardian G600-B System Components
FIGURE 2
System (Enclosure/Extinguisher Assy.)
FIGURE 3
Central Processing Unit Control Board
FIGURE 4
Temp. Activated Sensor Assy./Dist Assy.
FIGURE 5
Minimum and Maximum Heights
FIGURE 6
System Location
FIGURE 7
Overview Under Hood
FIGURE 8
Distribution Assembly Installation
FIGURE 9
Nozzle Adjustment
FIGURE 10
Nozzle Aiming Gauge
FIGURE 11A 3-Prong Shutoff
FIGURE 11B 4-Prong Shutoff
FIGURE 11C Hardwire Shutoff
FIGURE 12
Electric Shutoff Connector Configuration
FIGURE 13
Electric Shutoff Interconnect Identification
FIGURE 14
Electric Shutoff Installation
FIGURE 15
Gas Shutoff Valve Installation
FIGURE 16
Gas Shutoff Control Box Installation
FIGURE 17
Gas Shutoff Connection Identification.
FIGURE 18
G602-C Main CPU for Motor/ Cam
FIGURE 19
G600B-C Motor/Cam Activated System
FIGURE 20
Building Alarm Interface
FIGURE 21
Installation of Remote Pull Station
FIGURE 22
Wiring of Remote Pull Station
FIGURE 23
Manual Remote Pull Station
FIGURE 24
Wireless Receiver
FIGURE 25
Wireless Transmitter
FIGURE 26
Alarm / Strobe Assy.
FIGURE 27
Interface Enclosure Assembly
FIGURE 28
Solenoid Position
FIGURE 29
Cylinder Pressure/Temperature Graph
NOTICE:
Attn: End User/Customer
In the event of a system discharge it is extremely important that the agent be
cleaned up immediately with soap and water. Due to the high PH level of the agent,
any residual liquid left on stoves and counters for an extended period of time could
have a negative affect and cause significant damage to the stove top and
electronics. Guardian Safety Solutions International, Inc. is not liable or responsible
for clean up or damages incurred due to a discharge.
DEFINITIONS:
WET CHEMICAL:
A water based, potassium
carbonate and potassium acetate solution which is
used as the extinguishing agent.
LISTED:
Equipment or materials included in a list
published by Underwriters Laboratories, UL LLC
(UL) and acceptable to the local authority having
jurisdiction, which identifies the equipment or
materials as having been tested and determined to be
acceptable for use for the specified purpose.
SHALL, MUST or NEVER:
Indicates a mandatory
requirement.
Permit Number:
20-04649