background image

P/N G610B 
April, 2016 (Rev 0)

 

 

Page 1

 

 

 

 

 

SHOULD OR MAY:

 Indicates a recommendation or 

that which is advised.  
 

APPLIANCE: 

For the purpose of this manual, 

appliance means a residential-type kitchen range 
supplied by gas or electricity to power and heat range 
top burners. 
 

G600-B:

 The Guardian Model G600-B is the standard 

model offered for typical installations

 

when used in 

conjunction with a flat faced (bottom) exhaust hood or 
microwave hood only. 
 

G600B-C:

 The Guardian Model G600B-C is an 

alternate model designed for environment’s that could 
periodically subject the system to vibration or jarring. 
See Page 16 for further explanation and additional 
limitations. 

TABLE OF CONTENTS 

Pg.    

 

DEFINITIONS ..................................................... 1 
LIST OF ILLISTRATIONS ................................. 1 
INTRODUCTION ................................................ 2 
APPLICATION AND LIMITATION .................. 2 
GUARDIAN G600-B SYSTEM COMPONENT . 3 
ENCLOSURE/EXTINGUISHER ASSY ............. 4 
CPU UNIT CONTROL BOARD ......................... 5 
DETECTION SENSOR ASSEMBLY ................. 7 
DISTRIBUTION ASSEMBLY ............................ 7 
SYSTEM INSTALLATION INSTRUCTIONS ... 8 
AIMING NOZZLES ............................................. 10 
ELECTRIC SHUTOFFS ...................................... 11 
GAS SHUTOFFS ................................................. 13 
ARMING THE SYSTEM..................................... 15 
ALTERNATE CAM ACTIVATION ................... 16 
ACCESSORIES ................................................... 17 
INSPECTION AND MAINTENANCE ............... 19 
AFTER A DISCHARGE ...................................... 20 
PARTS LIST ........................................................ 21 
TROUBLE SHOOTING GUIDE ......................... 22 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

ILLUSTRATIONS

 

 

FIGURE 1 

Guardian G600-B System Components 

FIGURE 2 

System (Enclosure/Extinguisher Assy.) 

FIGURE 3 

Central Processing Unit Control Board 

FIGURE 4 

Temp. Activated Sensor Assy./Dist Assy. 

FIGURE 5 

Minimum and Maximum Heights 

FIGURE 6 

System Location 

FIGURE 7 

Overview Under Hood 

FIGURE 8 

Distribution Assembly Installation 

FIGURE 9 

Nozzle Adjustment 

FIGURE 10 

Nozzle Aiming Gauge 

FIGURE 11A  3-Prong Shutoff 
FIGURE 11B  4-Prong Shutoff 
FIGURE 11C  Hardwire Shutoff 
FIGURE 12 

Electric Shutoff Connector Configuration 

FIGURE 13 

Electric Shutoff Interconnect Identification 

FIGURE 14 

Electric Shutoff Installation 

FIGURE 15 

Gas Shutoff Valve Installation 

FIGURE 16 

Gas Shutoff Control Box Installation 

FIGURE 17 

Gas Shutoff  Connection Identification. 

FIGURE 18 

G602-C Main CPU for Motor/ Cam 

FIGURE 19 

G600B-C Motor/Cam Activated System 

FIGURE 20 

Building Alarm Interface 

FIGURE 21 

Installation of Remote Pull Station 

FIGURE 22 

Wiring of Remote Pull Station 

FIGURE 23 

Manual Remote Pull Station 

FIGURE 24 

Wireless Receiver 

FIGURE 25 

Wireless Transmitter 

FIGURE 26 

Alarm / Strobe Assy. 

FIGURE 27 

Interface Enclosure Assembly 

FIGURE 28 

Solenoid Position 

FIGURE 29 

Cylinder Pressure/Temperature Graph 

 
 
 
 
 
 
 
 
 
 
 

NOTICE:

 

Attn: End User/Customer 

 

 

 

In  the  event  of  a  system  discharge  it  is  extremely  important  that  the  agent  be 
cleaned up immediately with soap and water. Due to the high PH level of the agent, 
any residual liquid left on stoves and counters for an extended period of time could 
have  a  negative  affect  and  cause  significant  damage  to  the  stove  top  and 
electronics. Guardian Safety Solutions International, Inc. is not liable or responsible 
for clean up or damages incurred due to a discharge. 

DEFINITIONS: 

 
WET  CHEMICAL:

  A  water  based,  potassium 

carbonate  and  potassium  acetate  solution  which  is 
used as the extinguishing agent.  
 

LISTED:

 Equipment or  materials included in a list 

published  by  Underwriters  Laboratories,  UL  LLC 
(UL)  and  acceptable  to  the  local  authority  having 
jurisdiction,  which  identifies  the  equipment  or 
materials as having been tested and determined to be 
acceptable for use for the specified purpose. 
 

SHALL, MUST or NEVER:

 Indicates a mandatory 

requirement.  
 

Permit Number:

20-04649

Summary of Contents for G600-B

Page 1: ...OPERATION INSPECTION AND MAINTENANCE MANUAL MODEL G600 B RESIDENTIAL RANGE TOP EXTINGUISHER UNIT UL FILE NO EX 3940 P N G610B APRIL 2016 REV 0 8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Per...

Page 2: ...11B 4 Prong Shutoff FIGURE 11C Hardwire Shutoff FIGURE 12 Electric Shutoff Connector Configuration FIGURE 13 Electric Shutoff Interconnect Identification FIGURE 14 Electric Shutoff Installation FIGUR...

Page 3: ...al range tops when installed in conjunction with a 30 inch wide exhaust hood or microwave exhaust hood combination with a flat ferromagnetic underside The extinguishing system is intended for installa...

Page 4: ...ectrical or gas stoves ready for installation in the kitchen cabinet and range hood over the stove Sensor Assembly P N G605 A Distribution Assembly P N 604 A Enclosure Extinguisher Assembly P N G699 B...

Page 5: ...GUARDIAN G600 B AS A HAND HELD PORTABLE EXTINGUISHER SERIOUS INJURY COULD RESULT FROM MISUSE THE CHEMICAL AGENT USED IN THE GUARDIAN G600 B IS NOT REGARDED AS A TOXIC MATERIAL BUT CAN CAUSE IRRITATIO...

Page 6: ...owly flashing red indicator If the main unit passes all 6 tests upon reset the result is a display of the green indictor for 2 seconds whereupon it enters Fire Detect Mode and the system is armed 2 Di...

Page 7: ...if the diagnostic failure is a low battery Approximately once per minute the battery is checked If it is low there will be a short chirp to indicate that the battery needs to be replaced The unit will...

Page 8: ...nd for easy connection to the valve head of the extinguisher Inside the housing there are 2 nozzles mounted in fittings connected by a stainless steel tube The assembly is installed underneath the hoo...

Page 9: ...xtinguisher Assembly Before Drilling measure the route and make certain that the sensor cable and stainless steel braided hose are long enough to connect to the Guardian G600 B System Enclosure Exting...

Page 10: ...crews to anchor into the hood above and two 1 1 4 screws to secure to the wall behind Screws in the wall must be located where they will go into the walls studs or into a wall anchor Screws going into...

Page 11: ...ng Gauge provided adjust the nozzles to the correct angle based on the height determined in step 14 This is done by placing the Gauge in the housing and aligning the nozzles spray hole with the corres...

Page 12: ...he electric shutoff is activated or an interruption in power occurs it must be reset See Reset Stove p 12 INSTALLATION NOTE Ensure the Electric Shutoff is installed within the same room as the Main CP...

Page 13: ...and 25 Reset Stove 1 The electric stove shutoff unit may be reset by locating the circuit breaker supplying power to the stove and turning it off and then back on or 2 Momentarily unplugging the shuto...

Page 14: ...6 1 on the incoming service line to the stove Adhere to manufacturers installation and maintenance instructions Wiring must comply with local and national electrical codes The solenoid valve is design...

Page 15: ...s compatible with both the interconnect cable and the Wireless Tx Rx Either interconnect option is available and can plug into the gas shutoff In some cases a wireless version of the shutoff device ma...

Page 16: ...ic Failure Code occurs 1 Verify that the fuel shut off is powered and is reset See page 12 for Electric page 14 for Gas 2 Next check that the solenoid release latch is engaged See Figure 28 p 19 and t...

Page 17: ...on of the Main CPU board includes a Motor Test Advance Button and includes a TRIP MOTOR connection on the board instead of a VALVE connection See Figure 26 Note Test the Trip Motor and Cam Monthly by...

Page 18: ...he range top burners and activate the alarm or other electrical accessory Once activated the automatic sequence cannot be interrupted The manual pull station is installed at a height not exceeding 60...

Page 19: ...vide an interface for a 120 volt 5A alarm strobe This assembly has a Plug Play configuration for ease of installation Install in optimum location for visibility This feature is mainly used with the st...

Page 20: ...ng fire extinguisher unit appliance nozzles sensor distribution assembly and shutoffs Replace battery in the central processing unit control board annually from the date of installation Use only Durac...

Page 21: ...gent cylinder has been completely expelled and the pull pin is re installed in the handle prior to disconnecting the quick connect 4 Disconnect the quick connect below the handle and remove the distri...

Page 22: ...1 18 24 25 G615 A Wireless Tx and Rx and AC DC 18 24 G702 Wireless Receiver Rx Assembly 18 25 G701 Wireless Transmitter Tx Assembly 14 17 G316 A Gas Shutoff Assembly 1 14 17 G316 1 Gas Valve 1 14 17 G...

Page 23: ...and that the connectors are fully mated Press the reset button on the Main CPU and verify the green indicator momentarily lights up Verify power is getting to stove by testing a burner If there is no...

Page 24: ...f any unknown wireless interference occurs from a site condition the Interconnect Cable may have to be used Gas Shutoff P N G316 A Problem No Electrical Power To Stove Confirm that power is supplied a...

Page 25: ...switch to open the gas valve to the stove The gas flow indicator light will illuminate Verify that the Interconnect cable between the Main CPU control board and the Gas Shutoff Control box is plugged...

Page 26: ...perform Arming the System on page 15 again If power gas to the stove stays on after a diagnostic test and there are no Diagnostic Code beeps then replace the Main CPU board If the stove successfully...

Page 27: ...TRAC 1 800 535 5053 Account Number 78764 SECTION II Hazard Identification GHS Classification Acute Toxicity Category 5 Eye Irritation Category 2B Skin Irritation Category 3 GHS Label Elements Hazard S...

Page 28: ...on is an extinguishing media There are NO extinguishing media which must not be used for safety reasons NO special protective equipment is needed for fire fighters Wear protective equipment appropriat...

Page 29: ...o C About 230 o F Flash point None to boiling Flammability solid gas Not flammable Explosive properties Not explosive Oxidizing properties Not an oxidizer Vapor Pressure About 12mm Hg Relative Densit...

Page 30: ...harm to the environment is expected from this preparation Please Note Although this material is not considered hazardous when contained in a stored pressure fire extinguisher pressurized with a nonfl...

Page 31: ...l advice S 36 Wear suitable protective clothing THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT BUT DOES NOT PURPORT TO BE ALL INCLUSIVE AND SHALL BE USED ONLY AS A GUIDE GUARDIAN SAFETY SOLUTIONS INT...

Page 32: ...8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Toll Free 800 786 2178 Fax 972 594 7826 www guardianssi com Permit Number 20 04649...

Reviews: