GAS SHUTOFF

 

(P/N G316-A)

 

 

The  Gas  Shutoff  Assembly  G316-A  is  the  shutoff 
supplied  with  the  Guardian  G600-B  system  when 
protecting  a  gas  stove.    Features  provided  with  this 
shutoff include the following: 
 

1.  It is designed with a “Fail Safe Mode” consisting 

of  a  Normally  Closed  (N/C)  valve  that  is 
energized  continually.   

Loss  of  power

  or 

activation

  due  to  a  fire  will  close  the  valve, 

shutting  off  “gas  flow”  and  “electrical  power”  to 
the stove. 

2.  The  standard  Interconnect  Cable  will  be 

provided 

or 

an 

optional 

“Wireless 

Transmitter/Receiver” is available upon request. 

3.  An  extra  set  of  dry  contacts  for  switching 

external  devices  during  system  activation  are 
provided  via  the  optional  Interface  Enclosure 
Assembly (P/N G317-A) 

4.  The  shutoff  also  has  a  manual  “power  reset” 

feature  to  eliminate  any  possibility  of  an 
automatic reset/activation of the valve occurring 
after a fire or loss of power. 

 

INSTALLATION OF GAS STOVE SHUTOFF 

 

NOTE: 

 

Gas  stove  shutoff  must  be  installed  within 
the  same  room  as  the  central  processing 
unit  control  board  (Part  #G602)  for  proper 
unit operation.

 

 

Turn  “OFF”  electric  power  and  gas  to  the 
stove prior to installation.

 

 

VALVE INSTALLATION 

 
It  is  suggested  that  a  licensed  plumber  familiar  with 
local  and  state  codes  install  the  gas  valve  (P/N  # 
G316-1)  on  the  incoming  service  line  to  the  stove.  
Adhere to manufacturers installation and maintenance 
instructions. 
 
Wiring  must  comply  with  local  and  national  electrical 
codes. 
 
The solenoid valve is designed for a continuous duty 
cycle.    When  the  solenoid  valve  is  energized  for  a 
long  period,  the  enclosure  becomes  hot  and  can  be 
touched  by  hand  only  for  an  instant.    This  is  a  safe 
operating temperature. 
 
Normally, the valve is installed between the gas lines 
manual  shutoff  and  the  flexible  service  line  from  the 
stove. Be sure that the manual valve is closed prior to 
installation of valve. (See

 FIGURE 15

 

NOTE:  The  gas  valve  has  an  "in"  and  "out" 
orientation.  The  Installer  must  make  certain  that 
the valve is installed correctly.  

 
Install the “Gas Shutoff Control Box” before relocating 
the stove back for regular cooking conditions. 

 
 
 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

GAS SHUTOFF CONTROL BOX 

INSTALLATION 

 

 

1.  Locate  required  tools  and  hardware  for 

installation. 

 

2.  If stove is not unplugged, remove the plug from 

the outlet. 

 

3.  Determine the optimal location either behind the 

stove or in an adjoining cabinet for installation of 
the  Gas  Shutoff  Control  Box  (Part  #  G316-2). 
(See

  FIGURE  16

)        Consider  accessibility  to 

activate the manual reset.  From the Gas Shutoff 
Control  Box  route  the  cables  to  gas  valve  and 
power cord to wall outlet.  

 
NOTE:

  Check  the  length  of  cables  for 

adequate  length  prior  to  installation  of  the  Gas 
Shutoff Control Box. 
 
 
 
 
 
 
 
 
 
 
 
 

FLEX SERVICE LINE 

TWO WAY 
N/C

 

VALVE 

MANUAL GAS SHUTOFF VALVE 

FIGURE 15 

FIGURE 16 

Permit Number:

20-04649

Summary of Contents for G600-B

Page 1: ...OPERATION INSPECTION AND MAINTENANCE MANUAL MODEL G600 B RESIDENTIAL RANGE TOP EXTINGUISHER UNIT UL FILE NO EX 3940 P N G610B APRIL 2016 REV 0 8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Per...

Page 2: ...11B 4 Prong Shutoff FIGURE 11C Hardwire Shutoff FIGURE 12 Electric Shutoff Connector Configuration FIGURE 13 Electric Shutoff Interconnect Identification FIGURE 14 Electric Shutoff Installation FIGUR...

Page 3: ...al range tops when installed in conjunction with a 30 inch wide exhaust hood or microwave exhaust hood combination with a flat ferromagnetic underside The extinguishing system is intended for installa...

Page 4: ...ectrical or gas stoves ready for installation in the kitchen cabinet and range hood over the stove Sensor Assembly P N G605 A Distribution Assembly P N 604 A Enclosure Extinguisher Assembly P N G699 B...

Page 5: ...GUARDIAN G600 B AS A HAND HELD PORTABLE EXTINGUISHER SERIOUS INJURY COULD RESULT FROM MISUSE THE CHEMICAL AGENT USED IN THE GUARDIAN G600 B IS NOT REGARDED AS A TOXIC MATERIAL BUT CAN CAUSE IRRITATIO...

Page 6: ...owly flashing red indicator If the main unit passes all 6 tests upon reset the result is a display of the green indictor for 2 seconds whereupon it enters Fire Detect Mode and the system is armed 2 Di...

Page 7: ...if the diagnostic failure is a low battery Approximately once per minute the battery is checked If it is low there will be a short chirp to indicate that the battery needs to be replaced The unit will...

Page 8: ...nd for easy connection to the valve head of the extinguisher Inside the housing there are 2 nozzles mounted in fittings connected by a stainless steel tube The assembly is installed underneath the hoo...

Page 9: ...xtinguisher Assembly Before Drilling measure the route and make certain that the sensor cable and stainless steel braided hose are long enough to connect to the Guardian G600 B System Enclosure Exting...

Page 10: ...crews to anchor into the hood above and two 1 1 4 screws to secure to the wall behind Screws in the wall must be located where they will go into the walls studs or into a wall anchor Screws going into...

Page 11: ...ng Gauge provided adjust the nozzles to the correct angle based on the height determined in step 14 This is done by placing the Gauge in the housing and aligning the nozzles spray hole with the corres...

Page 12: ...he electric shutoff is activated or an interruption in power occurs it must be reset See Reset Stove p 12 INSTALLATION NOTE Ensure the Electric Shutoff is installed within the same room as the Main CP...

Page 13: ...and 25 Reset Stove 1 The electric stove shutoff unit may be reset by locating the circuit breaker supplying power to the stove and turning it off and then back on or 2 Momentarily unplugging the shuto...

Page 14: ...6 1 on the incoming service line to the stove Adhere to manufacturers installation and maintenance instructions Wiring must comply with local and national electrical codes The solenoid valve is design...

Page 15: ...s compatible with both the interconnect cable and the Wireless Tx Rx Either interconnect option is available and can plug into the gas shutoff In some cases a wireless version of the shutoff device ma...

Page 16: ...ic Failure Code occurs 1 Verify that the fuel shut off is powered and is reset See page 12 for Electric page 14 for Gas 2 Next check that the solenoid release latch is engaged See Figure 28 p 19 and t...

Page 17: ...on of the Main CPU board includes a Motor Test Advance Button and includes a TRIP MOTOR connection on the board instead of a VALVE connection See Figure 26 Note Test the Trip Motor and Cam Monthly by...

Page 18: ...he range top burners and activate the alarm or other electrical accessory Once activated the automatic sequence cannot be interrupted The manual pull station is installed at a height not exceeding 60...

Page 19: ...vide an interface for a 120 volt 5A alarm strobe This assembly has a Plug Play configuration for ease of installation Install in optimum location for visibility This feature is mainly used with the st...

Page 20: ...ng fire extinguisher unit appliance nozzles sensor distribution assembly and shutoffs Replace battery in the central processing unit control board annually from the date of installation Use only Durac...

Page 21: ...gent cylinder has been completely expelled and the pull pin is re installed in the handle prior to disconnecting the quick connect 4 Disconnect the quick connect below the handle and remove the distri...

Page 22: ...1 18 24 25 G615 A Wireless Tx and Rx and AC DC 18 24 G702 Wireless Receiver Rx Assembly 18 25 G701 Wireless Transmitter Tx Assembly 14 17 G316 A Gas Shutoff Assembly 1 14 17 G316 1 Gas Valve 1 14 17 G...

Page 23: ...and that the connectors are fully mated Press the reset button on the Main CPU and verify the green indicator momentarily lights up Verify power is getting to stove by testing a burner If there is no...

Page 24: ...f any unknown wireless interference occurs from a site condition the Interconnect Cable may have to be used Gas Shutoff P N G316 A Problem No Electrical Power To Stove Confirm that power is supplied a...

Page 25: ...switch to open the gas valve to the stove The gas flow indicator light will illuminate Verify that the Interconnect cable between the Main CPU control board and the Gas Shutoff Control box is plugged...

Page 26: ...perform Arming the System on page 15 again If power gas to the stove stays on after a diagnostic test and there are no Diagnostic Code beeps then replace the Main CPU board If the stove successfully...

Page 27: ...TRAC 1 800 535 5053 Account Number 78764 SECTION II Hazard Identification GHS Classification Acute Toxicity Category 5 Eye Irritation Category 2B Skin Irritation Category 3 GHS Label Elements Hazard S...

Page 28: ...on is an extinguishing media There are NO extinguishing media which must not be used for safety reasons NO special protective equipment is needed for fire fighters Wear protective equipment appropriat...

Page 29: ...o C About 230 o F Flash point None to boiling Flammability solid gas Not flammable Explosive properties Not explosive Oxidizing properties Not an oxidizer Vapor Pressure About 12mm Hg Relative Densit...

Page 30: ...harm to the environment is expected from this preparation Please Note Although this material is not considered hazardous when contained in a stored pressure fire extinguisher pressurized with a nonfl...

Page 31: ...l advice S 36 Wear suitable protective clothing THE ABOVE INFORMATION IS BELIEVED TO BE CORRECT BUT DOES NOT PURPORT TO BE ALL INCLUSIVE AND SHALL BE USED ONLY AS A GUIDE GUARDIAN SAFETY SOLUTIONS INT...

Page 32: ...8701 John Carpenter Freeway Suite 230 Dallas TX 75247 Toll Free 800 786 2178 Fax 972 594 7826 www guardianssi com Permit Number 20 04649...

Reviews: