58 NS3000 UPS 60KVA~120KVA User Manual
7. Product Specification
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics.
7.1 Applicable Standards
The UPS has been designed to conform to the following European and
international standards:
Table 7.1 Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS
used in operator access areas
EN50091-1-1/IEC62040-1/AS 62040-1-1
Electromagnetic compatibility (EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2
(
C3
)
Method of specifying the performance
and test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3
(
VFI
SS 111
)
Note
The above mentioned product standards incorporate relevant compliance clauses with
generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission
and immunity (IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and
60950).
7.2 Environmental Characteristics
Table 7.2 Environmental Characteristics
Item
Unit
Requirements
Acoustic noise level
at 1 meter
dB
65dB @ 100% load, 62dB @ 45% load
Altitude of Operation
m
≤1000,load derated 1% per 100m from 1000m
and 2000m
Relative Humidity
%
0-95,non condensing
Operating Temperature
℃
0-40,Battery life is halved for every 10°C
increase above 20°C
UPS Storage
Temperature
℃
-40-70
7.3 Mechanical Characteristic
Table 7.3 Mechanical Characteristics for Cabinet
Model
NS3060
NS3090 NS30120
Capacity(KVA)
60
90
120
Mechanical Dimension
(W*D*H)(mm)
600*980*950
600*980*1400
Summary of Contents for NS3000 Series