NS3000 UPS 60KVA~120KVA User Manual
21
settable.
Default: Low battery alarming
J8-3
BAT_LOW_ALARM_GND Common terminal for J8-1 and J8-2
J9-1
GENERAL_ALARM_NC
Output dry contact, (Normally closed) function
is settable.
Default: Fault alarming
J9-2
GENERAL_ALARM_NO
Output dry contact, (Normally open) function is
settable.
Default: Fault alarming
J9-3
GENERAL_ALARM_GND Common terminal for J9-1 and J9-2
J10-1
UTILITY_FAIL_NC
Output dry contact, (Normally closed) function
is settable.
Default: Utility abnormal alarming
J10-2
UTILITY_FAIL_NO
Output dry contact, (Normally open) function is
settable.
Default: Utility abnormal alarming
J10-3
UTILITY_FAIL_GND
Common terminal for J10-1 and J10-2
Note
The settable functions for each port can be set by the monitor software
.
The default functions of each port are described as follows.
Battery Warning Output Dry Contact Interface
The input dry contact J2 and J3 can detect the temperature of batteries and
environment respectively, which can be used in environment monitoring and
battery temperature compensation.
Interfaces diagram for J2 and J3 are shown in Fig.3-14, the description of
interface is in Table 3.6.
J2
J3
T
E
M
P_
B
A
T
T
E
M
P
_E
N
V
Fig.3-14 J2 and J3 for temperature detecting
Table 3.6 Description of J2 and J3
Port
Name
Function
J2-1
TEMP_BAT
Detection of battery temperature
J2-2
TEMP_COM
common terminal
J3-1
ENV_TEMP
Detection of environmental temperature
J3-2
TEMP_COM
common terminal