NS3000 UPS 60KVA~120KVA User Manual
17
3.5 Cable Entry
Cables can enter the UPS cabinet from the bottom. Cable entry is made
possible through a blanking plate fitted at the bottom of the equipment. The
cable entry is shown in Fig.3-11.
Cable Entry
Fig.3-11 Cable entry
3.6 Power Cables
3.6.1 Specifications
The UPS power cables are recommended in Table 3.2.
Table 3.2 Recommended cables for power cables
Contents
60KVA
90KVA
120KVA
Main Input
Main Input Current(A)
110
165
220
Cable
Section
(
mm²
)
A
35
50
95
B
35
50
95
C
35
50
95
N
35
50
95
Main Output
Main Output Current(A)
91
136
182
Cable
Section
(
mm²
)
A
25
35
70
B
25
35
70
C
25
35
70
N
25
35
70
Bypass Input
(
Optional
)
Bypass Input Current(A)
91
136
182
Cable
Section
(
mm²
)
A
25
35
70
B
25
35
70
C
25
35
70
N
25
35
70
Battery Input
Battery Input current(A)
138
206
275
+
50
70
95
Summary of Contents for NS3000 Series
Page 6: ......