NS3000 UPS 60KVA~120KVA User Manual
45
TEST COMMAND
Battery Test
By touching the icon
,
the system transfer to the Battery mode to test the condition
of the battery. Ensure the bypass is working normally and the capacity of the battery is no
less than 25%.
Battery Maintenance
By touching the icon
, the system transfers to the Battery mode. This function is
used for maintaining the battery, which requires the normality of the bypass and minimum
capacity of 25% for the battery.
Battery Boost
By touching the icon
, the system starts boost charging.
Battery Float
By touching the icon
, the system starts float charging.
Stop Test
By touching the icon
, the system stops battery test or battery maintenance.
4.3.6 Scope
Touch the icon
, (At the bottom right of the screen), and the system enters the page
of the Scope, as it is shown in Figure 4-11.
220.2
220.0
220.1
Figure 4-11
Scope Menu
Users can view the waves for output voltage, output current and bypass voltage by
touching the corresponding icon in the left side of the interface. The waves can be zoomed
in and zoom out.
Touch the icon to display the 3 phase output voltage.