Appendix D Battery Calculations
Power Requirements (All currents are in amperes)
Model Type
Description
Qty.
Standby
Total
Standby
Alarm
Total
Alarm
GST-IFP4M
FACP
1
X
0.30
=
0.50
=
GST-IFP4M
AUX Load
1
X
(max.0.2
5)
=
(max.0.2
5)
=
PR-400 or
PR-400B
Ancillary Printer
1
X
0.01
=
0.30
=
LC-401
Single Loop Card
X
0.040
=
0.060
=
LC-402
Dual Loop Card
X
0.070
=
0.080
=
P-9981
Zone Display Panel
X
0.008
=
0.016
=
P-9981F
Zone Display Panel
X
0.008
=
0.016
=
P-9982
Zone Display and
Control Panel
X
0.008
=
0.016
=
P-9982F
Zone Display and
Control Panel
X
0.008
=
0.016
=
P-9966A
CAN Class A
Network Card
X
0.050
=
0.050
=
P-9983
Fiber-Optical
Network Card
X
0.030
=
0.030
=
P-9956
Modbus Card
X
0.030
=
0.030
=
I-9102(UL)
Intelligent
Photoelectric
Smoke Detector
X
0.0008
=
0.002
=
I-9103(UL)
Intelligent Rate of
Rise and Fixed
Temperature Heat
Detector
X
0.0008
=
0.002
=
DI-M9101
Intelligent
Combination Heat
Photoelectric
Smoke Detector
X
0.0008
=
0.0018
=