4.2.2 Download thru Ethernet interface ( the external computer
connected must be located at the same room with the control panel )
After programming the FACP using GST-IFPx-Def Defining Tool, connect Ethernet port of
the programming computer to the Ethernet interface on FACP’s SD-400 LCD Driver Board
through a switch, a router or a cross-over Ethernet cable. In
Advanced Setting
menu,
select
TCP/IP Setup
as shown in the figure below Fig 4.38. On the programming window
to the right, key in IP Address, Subnet Mask and Gateway address. Note that FA
CP’s IP
address shall be in the same subnet as the programming computer.
Fig 4.38
The screen as shown in Fig4.39. At this time, the configurations and definitions can be
downloaded to the FACP accordingly.
Fig 4.39
Canceled during upload/download, communication between the programming computer
and FACP will be terminated.
4.2.3 Dongle
In some projects, data protection is required. In unauthorized way, configuration in the
control panel, uplodading and downloading can’t be modified. So, the control panel is
added with a function that can be locked or unlocked through GST-IFPx-Def Defining Tool.
USB Dongle is purchased from us to protect data not modifing by random.
4.2.4 Remote access to read panel status
After connecting computer to the panel via Erthernet port, authorized service engineer can
remote access panels
to diagnose troubles. Engineer should use
Graphic Monitor