GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page
31
I-
I+
SLCx
1K
Ω
(PartNo.
30108576)
FACP
+
-
AUX
O+
O-
SLCx
47K
Ω
(PartNo
.30107534)
IN
Z1
Z2
IN
I1
I2
OUT
Z2
Z1
OUT
I2
I1
O1 O2
Strobes
Horn/Strobes
DI-M9305
47K
Ω
(PartNo
.30107534)
IN
Z1
Z2
IN
I1
I2
OUT
Z2
Z1
OUT
I2
I1
O1 O2
Strobes
Horn/Strobes
DI-M9305
Fig 2.29
For NAC solution using DI-M9305 above, when a system is intended to provide signaling
service to two or more physically separated buildings or zones, reenergization of the
previously deactivated notification appliance circuits from a subsequent alarm may be
programmed on a zone basis (Refer to Fig 4.16 for the setting method). Consult with
AHJs for permissible applications.
2.5.5 Relays
Relays labelled as “Alarm”, “supervisory” and “Trouble” are designated as “Common”.
Other relays are designated as “Programmable”.
The relay outputs can be set to normally open/close contact output. When connecting
COM
and
NOx
with a jumper, this relay output is set to normally open contact output,
shown as Fig 2.30.
RELAY
NOx
COM
NCx
Jumper
Fig 2.30
2.5.6 INPUT (Limit to non-monitored)
The INPUT interface wiring diagram is as following Fig 2.31: