GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page
27
L
120VAC / 60Hz
220VAC / 50Hz
CIRCUIT BREAKER
AC-DC Switch Power
-V
+V1
BROWN
BLUE
YELLOW/GREEN
-V
+V2
N
L
O
F
F
O
F
F
N
Fig 2.21
Note:
Verify all cables are correctly connected before connecting power supply.
Please make sure the mains power is in line with the rated voltage marked on
the panel’s label.
Connect a wire from the grounding stud in the cabinet to a known solid earth ground in the
buildings. Refer to Fig 2.1 for location of the stud. This connection is vital for maintaining
the FACP
’s immunity to unwanted transients generated by lightning and electrostatic
discharge. Apply AC power to the panel only after the system is completely installed and
visually checked. The FACP shall be connected to a dedicated 15 Amp branch circuit.
2.5.2 Battery Connection
Batteries wire is connected to
XT3
of power box, as shown in the figure below Fig 2.22
FUSE
BATTERY
BATTERY
POWER
MANAGEMENT
BOARD
XT3
RED
BLACK
Fig 2.22
Before connecting the batteries to the FACP, make certain that the interconnect cable