12
7.1.7 GENIbus address
The GENIbus address of the IO 112 can be set with
the DIP switches 8, 9 and 10. If "Bus configuration,
ID 46" is selected, the address is set automatically
for instance by the MP 204 module.
7.2 Potentiometer
The potentiometer is used for setting the following
limits:
Analog input and temperature sensor input
• Alarm limit
• Limit 1
• Limit 2.
Counter input
• Alarm limit.
Note:
Limits 1 and 2 are not possible for the counter
input.
Fig. 6
Potentiometer
When the input (AI, PT or CNT) has been selected,
the indicator light of the selected input will flash.
5 seconds after the limit has been set with the poten-
tiometer, the setting is saved, and the indicator light
will be off. When setting the limits with the potenti-
ometer it is only possible to set the limit to one of the
six specified values.
Switches 8, 9 and 10
Description
GENIbus
Bus configuration via PC Tool, ID 46.
GENIbus address = ID 48 (unit No 1)
GENIbus address = ID 49 (unit No 2)
GENIbus address = ID 50 (unit No 3)
GENIbus address = ID 51 (unit No 4)
GENIbus address = ID 52 (unit No 5)
GENIbus address = ID 53 (unit No 6)
GENIbus address = ID 54 (unit No 7)
ON
DIP
1 2 3 4 5 6 7 8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
DIP
8 9 10
TM
03 34
15 030
6