7.1.2 Analog input (falling/rising)
With DIP switch 3 it is possible to set whether an
alarm is to be given when the value from the analog
sensor
rises
above or
falls
below the limit set.
If "rising" has been selected, the indicator lights will
illuminate from the bottom and upwards as the value
rises.
If "falling" has been selected, the indicator lights will
illuminate from the top and downwards as the value
falls.
7.1.3 Temperature sensor input (falling/rising)
With DIP switch 4 it is possible to set whether an
alarm is to be given when the value from the Pt1000
sensor
rises
above or
falls
below the limit set.
If "rising" has been selected, the indicator lights will
illuminate from the bottom and upwards as the value
rises.
If "falling" has been selected, the indicator lights will
illuminate from the top and downwards as the value
falls.
7.1.4 Counter input (falling/rising)
With DIP switch 5 it is possible to set whether an
alarm is to be given when the counter value
rises
above or
falls
below the limit set.
If "rising" has been selected, the indicator lights will
illuminate from the bottom and upwards as the value
rises.
If "falling" has been selected, the indicator lights will
illuminate from the top and downwards as the value
falls.
Switch 3
Description
Trips if the measured value is falling (>= limit).
Trips if the measured value is rising (<= limit).
ON
DIP
1 2 3 4 5 6 7 8 9 10
3
3
Switch 4
Description
Trips if the measured value is falling (>= limit).
Trips if the measured value is rising (<= limit).
ON
DIP
1 2 3 4 5 6 7 8 9 10
4
4
Switch 5
Description
Trips if the measured value is falling (>= limit).
Trips if the measured value is rising (<= limit).
ON
DIP
1 2 3 4 5 6 7 8 9 10
5
5