4-20 mA analog input
Digital output / Relay output
Digital input - S4/S5 JP1:2 and JP5:6 set
Digital input - S4/S5 JP1:2 and JP5:6 not set
Flow switch input
Description
Unit
D-320-GF1-230
D-320-GF3-230
Number of inputs
1
Connection
Terminal block, stripped wire, AWG 28-12
Input resistance
[Ohm]
100
Galvanic isolation
[kV]
1 kV to system ground/earth
Minimum input current
[mA]
0
Maximum input current
[mA]
20
Resolution of reading
12-bit
Response time
[ms]
< 1
Drift over full temperature range
[uA]
+30 µA to +0 µA at 10 mA
Uncertainty
[uA]
< 30
Description
Unit
D-320-GF1-230
D-320-GF3-230
Number of NO relays
2
Number of NO/NC relays (error relays)
1
Connection
Terminal block, stripped wire, AWG 28-12
Maximal RMS current
[A]
< 6
Maximal working voltage
[VAC]
< 240
Maximal switchable load
[A]
< 6
Maximal number of operating cycles
[VA]
< 600
Required external protection
Depending on the load, additional snubber circuits may be required.
Description
Unit
D-320-GF1-230
D-320-GF3-230
Number of inputs
2
Connection
Terminal block, stripped wire, AWG 28-12
Intended use
Digital input for external mechanical relay/switch
Galvanic isolation
[kV]
none
Maximum input frequency
[Hz]
100
Low input voltage
[V]
< 7
High input voltage
[V]
> 8
Input resistance
[Ohm]
> 1000
Description
Unit
D-320-GF1-230
D-320-GF3-230
Number of inputs
2
Connection
Terminal block, stripped wire, AWG 28-12
Intended use
Digital input for external voltage output
Galvanic isolation
[kV]
1 kV to system ground/earth
Maximum input frequency
[Hz]
100
High input
[Ohm]
> 2000
Low input
[Ohm]
< 100
Description
Unit
D-320-GF1-230
D-320-GF3-230
Number of inputs
1
Connection
Terminal block, stripped wire, AWG 28-12
Intended use
For use with s::can flow detector