background image

English (GB)

5

Description and use of the terminals

6.2 Connecting the sensors to the CU 382 control unit

All sensors for the DID have plugs.
Sensors for immersion have fixed cables with plugs.
1. Make sure that the sensor plug and the socket of the CU 382 

control unit are dry and clean.

– Otherwise communication errors may occur and the DID 

might be damaged.

2. Connect the sensor to a compatible socket on the CU 382 

control unit using the connection cable provided.

3. Cover the connectors that are not used with protective caps.

6.3 Connecting the valve for automatic cleaning

Only DID with sensor for tank immersion with valve for automatic 
cleaning:
• Connect the valve to terminals 10 ("Valve", "12 VDC") and 11 

(GND). See fig. 

3

.

• If an external cleaning signal is used, connect the signal line to 

terminal 12 ("Clean In", minimum 5 V).

6.4 Connecting further inputs and outputs

Observe the supplier manuals when connecting actuator devices, 
such as dosing pumps or regulators.

6.5 Connecting the CU 382 to the power supply

• Install an earth leakage circuit breaker for the power supply.
• If the installation is in an area prone to lightning strikes, install 

surge protection.

• Use an AC power supply with an earthed conductor wire.

– PE: potential earth

• Connect the process medium (e.g. waste water) to the same 

earth ground with less than 0.5 Ohm.

6.6 Start-up of the operating software

If the CU 382 control unit is connected to the power supply, it 
starts up and shows the s::can logo for 5 seconds. At first start-up 
or if the internal settings have been reset to default, the CU 382 
control unit starts with the selection of the language. See also 
section 

9.3.7

Select language...

.

After this, the parameter screen is shown and the most recent 
information is displayed.

6.7 Sensor initialisation

Every sensor that is connected to the CU 382 control unit must be 
installed and initiated individually. This can be done using the 
software-supported initialisation process.
• Connect only the sensor you want to initialise to the CU 382.

– An individual address is allocated to the initialised sensor. 

If no sensor was connected before, the CU 382 jumps into the 
"

Add MODBUS sensor...

" menu to check for connected sensors, 

right after setting the language.

Terminal Description

Use

1

Phase

Power supply 

(100-240 V, 

50-60 Hz)

2

Neutral

3

PE

4

PE

5-8

Unused, can be used to connect S::CAN sensors

9

12 V output

Cleaning valve 

control

10

Cleaning valve output (provides 
power for the valve +12 V)

11

GND, for cleaning valve and 
external trigger

12

External trigger for cleaning valve

13

4-20 mA output #1 (+)

Analog outputs

14

4-20 mA output #1 (-)

15

Shield connections (optional)

16
17

4-20 mA-output #2 (+)

18

4-20 mA-output #2 (-)

19

Shield connections (optional)

20
21

4-20 mA-output #3 (+)

22

4-20 mA-output #3 (-)

23

Power supply for 4-20 mA input 
(only for passive sources)

Analog input

24

4-20 mA-input #1 (-)

25

4-20 mA-input #1 (+)

26

Shield connection (optional)

27

Digital input #1 (+), relay to switch 
on/off or as pulse source

Digital inputs

28

Digital input #1 (-)

29

Digital input #2 (+), relay to switch 
on/off or as pulse source

30

Digital input #2 (-)

31

Flow #1, flow switch of bypass flow 
cell, pre-wired in BF1/BF3

Flow cell - flow 

switch

32

Flow #1, flow switch of bypass flow 
cell, pre-wired in BF1/BF3

33

RS485 A-

Modbus to 

upper controls 

(CU 382 is 

slave)

34

RS485 B+

35

RS485 GND

36

RS485 shield

37-46

Unused, for later add-ons

47

Relay 1-NO, switches on/off or 
provides pulse frequency

Digital output 

(with relays)

48

Relay 1-C, common connector

49

Relay 2-NO, switches on/off or 
provides pulse frequency

50

Relay 2-C, common connector

51

Alarm relay NO
Relay closes on alarm

Alarm relay

52

Alarm relay C, common connector

53

Alarm relay NC
Relay opens on alarm

54

Alarm relay C, common connector, 
duplication of 52

WARNING
Electric shock

- Switch off the power supply before connecting the 

CU 382 control unit.

- IP65 only applies, if the housing cover and the 

terminal compartment of the CU 382 are properly 
closed, and the appropriate cable glands or 
dummy caps are fitted.

- Electrical connection must be carried out by 

qualified and authorised persons.

Summary of Contents for DID BF1

Page 1: ...DID Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 99037650...

Page 2: ...ety instructions 3 3 Receiving the product 3 3 1 Inspecting the product 3 3 2 Transporting the product 3 4 Installation 3 4 1 Installation location 3 4 2 Installation of the DID 3 4 3 Hydraulic connec...

Page 3: ...installation of the DID with flow cell on a flat wall See also sections 8 Product introduction and 12 4 Dimensions DID with sensor for tank immersion The CU 382 control unit of the DID with sensor for...

Page 4: ...ease of the flow 5 Starting up the product 5 1 Initial startup 1 Connect all sensors to the CU 382 control unit See also section 6 2 Connecting the sensors to the CU 382 control unit 2 Slowly open the...

Page 5: ...ialisation process Connect only the sensor you want to initialise to the CU 382 An individual address is allocated to the initialised sensor If no sensor was connected before the CU 382 jumps into the...

Page 6: ...f DID with flow cell Fig 5 Components of DID with immersed sensor TM06 8088 3416 9 5 4 3 2 1 11 10 10 12 13 14 15 15 15 15 7 6 6a 8 18 T OK W X S 19 6c 6b TM06 8089 3416 Pos Description 1 Water inlet...

Page 7: ...n marks 8 QR code 9 Type 10 Voltage V 11 Frequency Hz 12 Power consumption W 13 Humidity limits 14 Temperature limits 1 2 3 5 7 8 10 11 12 13 14 4 6 9 TM06 8610 0817 Pos Description 1 s can product na...

Page 8: ...Moves the marker to the line above The first character of the selected line is a triangle Increases values Function button Enters the setup menus Disables or deletes values Left button Moves the mark...

Page 9: ...05B1 pH 15 YYYY MM DD Serial 9999999 9 49 Type PID Running ls below Waiting 1 s Temp pH 4 20mA 2 lower alarm limit YYYY MM DD hh nn ss 22 1 C AV SP 6 86 7 00 ext General setup Parameter setup Controll...

Page 10: ...0mA digital outputs PULSE or PWM AV SP AV is the actual value input parameter reading SP is the setpoint desired value of the input parameter reading Source of the setpoint External Manual AP001 A1 1...

Page 11: ...he Up and Down buttons Confirm with OK To add a MODBUS sensor select Add MODBUS sensor with the Up and Down buttons Confirm with OK The MODBUS port for a new sensor is searched and the new sensor is a...

Page 12: ...e configured in the MODBUS slave menu Changing the Modbus address 1 Select Address with the Up and Down buttons Confirm with OK 2 Change the address value with the Up and Down buttons Confirm with OK...

Page 13: ...Digital Input Read in all digital inputs Internal Sensors Read in all internal sensors USB Measure the performance of the USB stick Date Time Set the time and the date Hardware Read out the hardware r...

Page 14: ...he second reference solution Select the value in the Lab 2 field with the Up and Down buttons Confirm with OK Use a temperature compensated value 11 Select Sample 2 with the Up and Down buttons Confir...

Page 15: ...ith the Up and Down buttons Confirm with OK 2 The default display settings are loaded from the sensor All modifications of the display settings are documented in the logbook of the CU 382 control unit...

Page 16: ...ut settings menu a parameter can be allocated to an analog output or a digital output Analog outputs Parameter values between these two limits are calculated according to a linear calibration Assignin...

Page 17: ...ect Period s with the Up and Down buttons Confirm with OK 2 Change the value for the duration of one pulse with the Up Down Left and Right buttons Confirm with OK 9 4 7 Parameter info The Parameter in...

Page 18: ...e type to Manual 1 Select Type with the Up and Down buttons Confirm with OK 2 Select Manual with the Up and Down buttons Confirm with OK Changing the setpoint of the controller 1 Select Setpoint with...

Page 19: ...1 Select D factor with the Up and Down buttons Confirm with OK 2 Change the disturbance factor with the Up Down Left and Right buttons Confirm with OK Changing the direction of the controller 1 Select...

Page 20: ...er that can be changed is the maximum of pulses min for 100 output Changing the maximum of pulses min for 100 output 1 Select Pulses Min with the Up and Down buttons Confirm with OK 2 Change the maxim...

Page 21: ...all logfiles to the USB stick 1 Select Copy logfile with the Up and Down buttons 2 Confirm with OK to copy the data to the USB stick Deleting all logfiles 1 Select Delete logs with the Up and Down but...

Page 22: ...arefully with water and a soft brush 8 Screw in the flow detector back 9 Reconnect the wires of the flow detector to the CU 382 10 Refit the hose 11 Screw on the hose connection 10 1 3 Sensor See the...

Page 23: ...layed DID All hoses and fittings are tight CU 382 control unit The digital output of the flow detector is ok Outlet Water is flowing out of the outlet hose Water is visible within the hoses Flow cell...

Page 24: ...s no flow a The inlet valve is closed Open the inlet valve b The inlet strainer is blocked Clean the inlet strainer 8 Water is not visible in the hoses a The inlet valve is closed Open the inlet valve...

Page 25: ...n data Internal thread of inlet and outlet Rp1 2 Size of inlet and outlet connection thread G 5 8 Inlet outlet hose connections metric ID OD mm 4 6 6 9 6 12 or 9 12 Inlet outlet hose connections inch...

Page 26: ...age VAC 240 Maximal switchable load A 6 Maximal number of operating cycles VA 600 Required external protection Depending on the load additional snubber circuits may be required Description Unit D 320...

Page 27: ...5 Terminal connections 4 x M12 cable gland entry one used by flow switch 1 x M16 cable gland entry IP rating IP65 Memory MB 512 industrial grade SLC Display mm 128 x 64 graphical display 70 x 40 viewi...

Page 28: ...3 FCL2 ORP 4 710 8 765 DID 3 BF3 FCL2 PH ORP 4 960 9 165 DID 1 BF1 PH 4 250 8 085 DID 1 TI1 PH 2 075 5 875 DID 1 TI1 ORP 2 075 5 875 DID 3 TI2 ORP PH 2 850 6 800 DID 3 BF3 ORP PH 4 700 8 755 DID 1 BF1...

Page 29: ...tact the nearest Grundfos company or service workshop TM06 5897 0216 TM06 6025 0416 Fig 12 Dimensions of CU 382 control unit front and side in mm Fig 13 Dimensions of CU 382 control unit for wall moun...

Page 30: ...t of the sensors The sensors must always be immersed in water Avoid siphon effect Use a vented outlet or a pressure loading valve Avoid power loss of the sensors that are equipped with electrolyte and...

Page 31: ...Documents as listed Type of product Measurement Process Control Name of product DID Model number D 320 GF1 230 D 320 GF3 230 Low Voltage Directive 2014 35 EU Standard used EN 61010 1 2010 RoHS2 2011...

Page 32: ...an GRUNDFOS Pumps K K 1 2 3 Shin Miyakoda Kita ku Hamamatsu 431 2103 Japan Phone 81 53 428 4760 Telefax 81 53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam...

Page 33: ...NDFOS Pumps K K 1 2 3 Shin Miyakoda Kita ku Hamamatsu 431 2103 Japan Phone 81 53 428 4760 Telefax 81 53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135...

Page 34: ...1168 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Reviews: