English (GB)
27
Cleaning output
Sensor
Control unit specifications
Operating conditions
Storage
Description
Unit
D-320-GF1-230
D-320-GF3-230
Number of outputs
1
Connection
Terminal block, stripped wire, AWG 28-12
Intended use
For use with s::can cleaning valve B-44 or flow-cell autobrush F-446-2/
F-446-1
Description
Unit
D-320-GF1-230
D-320-GF3-230
Connection
1 x Buccaneer 400 Series
1 x Terminal block, stripped wire, AWG 28-12
Intended use
For use with s::can sensors
Maximum load
[W]
7 (constant), < 15 (peak)
Description
Unit
D-320-GF1-230
D-320-GF3-230
Housing material
Polycarbonate, RAL 9005
Material other
Polyamide, Polyurethane, EPDM
Weight
[kg]
1.3
Dimensions (WxHxL)
[mm]
213 x 185 x 118
Mains connection
1.5 mm
2
, 3-wire P/N/PE, fixed installation, M20 cable-gland entry
Mains supply voltage
[VAC]
100-240/50-60 Hz
Power consumption (typical)
[VA]
33, cos
φ
= 0.66
Power consumption (maximum)
[A]
AC inrush current: < 30
AC current: < 0.15
Terminal connections
4 x M12 cable-gland entry (one used by flow-switch)
1 x M16 cable-gland entry
IP rating
IP65
Memory
[MB]
512, industrial grade SLC
Display
[mm]
128 x 64 graphical display,
70 x 40 viewing area, transreflective, white background
Data transfer
USB host mode support for data transfer with USB stick, Supports FAT/
FAT32
Firmware update
USB stick with FAT/FAT32 and firmware image.
Integrated RTC
Uncertainty < 2 minutes/month at 25 °C
Installation
A circuit breaker must be included in the installation.
• The circuit breaker must be easily accessible.
• The circuit breaker must be marked as the disconnecting device.
Conformity - EMC
EN 61326-1:2013
Conformity - safety
EN 61010-1:2010
Conformity - RoHS2 (2011/65/EU)
EN 50581:2012
Approvals
cTUVus, CE, CSA
Description
Unit
D-320-GF1-230
D-320-GF3-230
Operating temperature limits
[°C]
-20 to +45
Humidity limits
[%]
5 to 90, non-condensing
Maximum altitude
[m]
3000
Manual cleaning
Cleaning with hand-warm water and mild detergents, such as dish-
washing soap
Description
Unit
D-320-GF1-230
D-320-GF3-230
Temperature limits
[°C]
-20 to +50
Humidity limits
[%]
5 to 90, non-condensing