English (GB)
16
Changing the requirement for acknowledging an alarm
1. Select "
Require ack.:
" with the [Up] and [Down] buttons.
Confirm with [OK].
2. Select "
Yes
" or "
No
" with the [Up] and [Down] buttons.
Confirm with [OK].
Changing the lower limit for triggering an alarm
1. Select "
Al. lower:
" with the [Up] and [Down] buttons. Confirm
with [OK].
2. Change the lower limit value with the [Up], [Down], [Left] or
[Right] buttons. Confirm with [OK].
Changing the upper limit for triggering an alarm
1. Select "
Al. upper:
" with the [Up] and [Down] buttons. Confirm
with [OK].
2. Change the upper limit value with the [Up], [Down], [Left] or
[Right] buttons. Confirm with [OK].
Defining the output of an alarm
1. Select "
Output:
" with the [Up] and [Down] buttons. Confirm
with [OK].
2. Select "
None
", "
DigOut #1
" or "
DigOut #2
" with the [Up] and
[Down] buttons. Confirm with [OK].
3. If "
DigOut #1
" or "
DigOut #2
" is selected, the submenu "
Invert
pol. :
" is shown.
– The contact type of the digital output can be changed with
"
Invert pol. :
".
Defining if the error relay is activated on an alarm
1. Select "
Use Sys-Error:
" with the [Up] and [Down] buttons.
Confirm with [OK].
2. Select "
Yes
" or "
No
" with the [Up] and [Down] buttons.
Confirm with [OK].
9.4.5 Outputs
The following outputs can be selected:
• Analog output: "
4-20mA #
1", "
4-20mA #
2", "
4-20mA #
3"
• Digital output: "
Level
", "
PULSE
", "
PWM
"
Changing the output
1. Select "
Output:
" with the [Up] and [Down] buttons. Confirm
with [OK].
2. Change the output with the [Up] and [Down] buttons. Confirm
with [OK].
9.4.6
Output settings...
In the "
Output settings...
" menu a parameter can be allocated to
an analog output or a digital output.
Analog outputs
Parameter values between these two limits are calculated
according to a linear calibration.
Assigning the parameter value for 4 mA
1. Select "
[4mA]:
" with the [Up] and [Down] buttons. Confirm with
[OK].
2. Change the parameter value with the [Up], [Down], [Left] and
[Right] buttons. Confirm with [OK].
Assigning the parameter value for 20 mA
1. Select "
[20mA]:
" with the [Up] and [Down] buttons. Confirm
with [OK].
2. Change the parameter value with the [Up], [Down], [Left] and
[Right] buttons. Confirm with [OK].
Digital outputs
The following output types can be defined:
•
Level
•
PULSE
•
PWM
Level
Changing the digital output to "
Level
"
1. Select "
Type:
" with the [Up] and [Down] buttons. Confirm with
[OK].
2. Select "
Level
" with the [Up] and [Down] buttons. Confirm with
[OK].
– An additional row is shown.
Changing the threshold value
1. Select "
Threshold:
" with the [Up] and [Down] buttons. Confirm
with [OK].
2. Change the threshold value with the [Up], [Down], [Left] and
[Right] buttons. Confirm with [OK].
P2
Alarm settings...
►
Require ack.:
Yes
Al. lower:
6.5
Al. upper:
7.5
Output:
None
Use Sys-Error:
No
"
Require ack.:
"
Acknowledgement of an alarm
"
Al. lower:
"
Lower limit for an alarm
"
Al. upper:
"
Upper limit for an alarm
"
Output:
"
Output of an alarm
"
Use Sys-Error:
" Output of an alarm on the error relay
P2
Output settings...
►
[4mA]:
0.00
[20mA]:
14.00
"
[4mA]:
"
The parameter value for 4 mA
"
[20mA]:
" The parameter value for 20 mA
P2
Output settings...
►
Type:
Level
Threshold:
7.00
"
Threshold:
" "
Threshold:
" defines the limits for 0 or 1.
Below the defined threshold the output is 0 (Relay
NO = open). Above the defined threshold the
output is 1 (Relay NO = closed).