Booster sets with motors connected to external frequency converters
Hydro MPC-EF
Hydro MPC-EDF
Hydro MPC-F
Hydro MPC booster set with three CR
pumps each connected to an external
frequency converter in the control
cabinet.
Hydro MPC booster set with two CR
pumps connected to external frequency
converters in the control cabinet and one
mains-operated CR pump.
Hydro MPC booster set with three CR
pumps connected to an external
frequency converter in the control
cabinet. The speed-controlled operation
alternates between the pumps.
TM
03
09
95
09
05
TM
03
09
97
09
05
TM
03
12
65
15
05
One CR pump in operation.
One CR pump connected to an external
frequency converter in operation.
One CR pump connected to an external
frequency converter in operation.
TM
00
79
95
22
96
TM
00
79
95
22
96
TM
00
79
95
22
96
Three CR pumps in operation.
Two CR pumps connected to external
frequency converters and one mains-
operated CR pump in operation.
One CR pump connected to an external
frequency converter and two mains-operated
CR pumps in operation.
TM
00
79
96
22
96
TM
03
08
14
05
05
TM
00
79
98
22
96
• Hydro MPC-EF maintains a constant
pressure through continuous adjustment
of the speed of the pumps connected.
• The system performance is adjusted to
the demand through cutting in/out the
required number of pumps and through
parallel control of the pumps in operation.
• Pump changeover is automatic and
depends on load, time and fault.
• All pumps in operation will run at equal
speed.
• Hydro MPC-EDF maintains a constant
pressure through continuous adjustment
of the speed of two CR pumps connected
to external frequency converters, while the
third CR pump is mains-operated.
• One CR pump connected to an external
frequency converter always starts first. If
the pressure cannot be maintained by the
pump, the second CR pump connected to
an external frequency converter will be cut
in. If the pressure cannot be maintained
by the two pumps, a mains-operated CR
pump will be cut in.
• Pump changeover is automatic and
depends on load, time and fault.
• Hydro MPC-F maintains a constant
pressure through continuous adjustment
of the speed of the CR pump connected to
an external frequency converter. The
speed controlled operation alternates
between the pumps.
• One CR pump connected to the external
frequency converter always starts first. If
the pressure cannot be maintained by the
pump, one or two mains-operated CR
pumps will be cut in.
• Pump changeover is automatic and
depends on load, time and fault.