29
4.1.2.7)
Fig. 29
Setting of alternative setpoints 2 to 7
For each alternative setpoint, select the digital input to activate
the setpoint.
It is possible to set a setpoint for closed loop and for open loop.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Primary controller
with
or
and press
.
3. Mark
Alternative setpoint
with
or
and press
.
4. Select the alternative setpoint with
or
and press
.
5. Mark Go to setting of digital input with
or
and press
.
Now the display
Overview of digital inputs (4.3.7)
appears. Set
the input and return with
.
6. Mark the menu line of the setpoint (closed or open loop) with
or
.
7. Set the required setpoint with
or
and save with
.
Set both setpoints if Hydro MPC is to be controlled both in
open and closed loop.
Factory setting
No alternative setpoints have been set.
10.7.5 Setpoint influence (4.1.3)
Fig. 30
Setpoint influence
Description
The setpoint may be influenced by several factors so that the
current setpoint is adapted to parameters which are to influence
for instance the discharge pressure of the booster set.
The parameters which influence the performance of the booster
set are shown as a percentage from 0 to 100%. They can only
reduce the setpoint, as the influence is multiplied with the
setpoint:
The influence values can be set individually.
Factory setting
Setpoint influence is not activated.
10.7.6 External setpoint influence (4.1.3.1)
Fig. 31
External setpoint influence
Description
This function makes it possible to make an external analog signal
influence the setpoint. The analog signal may be a 0-100% signal
from another control unit, a signal transmitter such as a flow
sensor, or a parameter in the system.
The function is linked to a selected analog input (AI), and the
relation between the measuring parameter and the desired
influence in percentage is described in a table with maximum
eight points.
Setting range
The following parameters can be selected:
•
Not used
•
0-100% signal
•
Inlet pressure
•
Discharge pressure
•
External pressure
•
Differential pressure of pump
•
Flow rate
•
Tank level, discharge side
•
Tank level, suction side.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Primary controller
with
or
and press
.
3. Mark
Setpoint influence
with
or
and press
.
4. Mark
External setpoint influence
with
or
and press
.
5. Mark the parameter which is to influence the setpoint with
or
and press
.
6. Mark
Go to setting of analog input
with
or
and
press .
Now the display
Overview of analog inputs (4.3.8)
Select the analog input (AI) and set the measuring parameter.
T
M
03
23
84
40
05
TM
03
23
77
40
05
TM
03
23
79
400
5
Setpoint
Current
Setpoint
Select.
Influence(1)
×
Influence(2)
×
=