Description
A fault
in the Hydro MPC booster set or one of the components
monitored can cause an alarm
or a warning
. Besides the
fault signal via the fault signal relay and the red indicator light on
CU 351, an alarm can also cause a change of operating mode,
for instance from
Normal
to
Stop
. A warning only causes a fault
indication.
The table shows the possible causes of fault together with an
alarm code number, and whether they result in an alarm or a
warning. It also shows to what operating mode the booster set
changes in case of alarm, and whether restart of the booster set
and reset of the alarm is manual or automatic.
The table also shows that the reaction to some of the fault causes
mentioned can be set in the
Settings
menu. See
10.7.32 Monitoring functions (4.4)
to
* Level 1 is the tank level where a warning
is indicated in case
of water shortage. Level 2 is the tank level where an alarm
is indicated and the pumps stop in case of water shortage. For
further information, see
10.7.34 Dry-running protection with
pressure/level switch (4.4.1.1)
tion with level transmitter (4.4.1.3)
TM
03
22
91
40
05
Fault
W
arning(
)/
ala
rm(
)
Change
of
operating
m
ode
to
Reset
of
ala
rm
Restar
t
Set
in
the
Settings
me
n
u
Alar
m
code
Water shortage,
level 1*
Auto
206
Water shortage,
level 2*
Stop
Man/auto
X
214
Max. pressure
Stop
Auto
210
Min. pressure
Auto
X
211
Stop
Man
Alarm, all pumps
Stop
Auto 203
External fault
Auto
X
3
Stop
Man
Dissimilar sensor
signals
Auto
204
Primary sensor
(without redundant
primary sensor)
Stop
Auto
89
Fault, sensor
Auto
88
Communication
fault
Auto
10
Phase failure
Auto
2
Undervoltage,
pump
Auto
7,40,
42,73
Overvoltage, pump
Auto
32
Overload, pump
Auto
48,50,
51,54
Overtemperature,
pump
Auto
65,67
Other fault, pump
Auto
76,83
Internal fault,
CU 351
Auto
72,83,
157
Internal fault,
IO 351
Stop
Auto
72,83,
157
VFD, not ready
Auto
213
Fault, Ethernet
Auto
231,
232,
233
www.motralec.com / [email protected] / 01.39.97.65.10