39
10.7.27 Max. duty (4.3.14.2)
Fig. 54
Max. duty
Description
The function makes it possible for a set number of pumps to run
at maximum speed when the function is activated.
Setting range
In this display the number of pumps to run in the operating mode
Max.
can be set. All pumps run at 100% speed.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Secondary functions
with
or
and press
.
3. Mark
Min., max. and user-defined duty
with
or
and
press .
4. Mark
Max. duty
with
or
and press
.
5. Mark
Number of pumps in operation
with
or
.
6. Set the number with
or
and save with
.
Factory setting
10.7.28 User-defined duty (4.3.14.3)
Fig. 55
User-defined duty
Description
In this display it is possible to set a user-defined performance,
typically a performance between min. and max. duty.
The function makes it possible to set a pump performance by
selecting the number of pumps to run and the speed of variable-
speed pumps.
This function primarily selects the variable-speed pumps. If the
number of selected pumps exceeds the number of variable-speed
pumps, mains-operated pumps are started too.
Setting range
•
Number of pumps in operation.
•
Speed as percentage for variable-speed pumps.
Note:
In Hydro MPC booster sets with only variable-speed
pumps the speed can be set between 25 and 100%; in booster
sets with both variable-speed pumps and mains-operated
pumps the speed can be set between 70 and 100%.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Secondary functions
with
or
and press
.
3. Mark
Min., max. and user-defined duty
with
or
and
press .
4. Mark
Set user-defined
with
or
and press
.
5. Mark
Number of pumps in operation
with
or
.
6. Set the number with
or
and save with
.
7. Mark
Speed
with
or
.
8. Set the value with
or
and save with
.
Factory setting
The function is not activated as the following has been set:
10.7.29 Pump curve data (4.3.19)
Fig. 56
Pump curve data
Description
The CU 351 has a number of functions using the pump
performance curves. At delivery the CU 351 contains data
describing these performance curves, but it is also possible to
enter these data. For this purpose use the pump nameplate which
contains data on nominal flow rate, Q
nom
, nominal head, H
nom
,
and maximum head, H
max
.
T
M
03
23
53
40
05
Number of pumps in operation
during max. duty:
All pumps (except standby
pumps)
T
M
03
23
52
40
05
Number of pumps in operation during user-defined duty:
0
TM
03
23
43
400
5